Boiler Uptake Fire and Exhaust Gas Economiser Fire
1 of 4
http://marineengineeringonline.com/boiler-uptake-fire/
Search
www.marineengineeringonline.com
Home
MEO Exam
Safety
General
Motor
s
Checklists
Naval
Electrical
Us
Home » General Engineering Knowledge » Boilers » Boiler Uptake Fire and Exhaust Gas Economiser Fire Categories
Select Category August 27, 2015 7:36 pm | 2 Comments | Frozee
Auxiliary boiler uptake or flue gases normally through economisers or air pre-heaters or feed water heaters. All these types of heat exchangers are fin type. Hence large amount of carbon or soot deposits on the fins. Along with the flue gases some un-burnt carbon particles also get deposited on the economisers. Normally dry soot deposits have a very high ignition temperature. But when the soot gets wet with hydrocarbon vapours,
Email *
their ignition temperature comes down to around 150 degree Celsius. This may result in boiler soot fire or boiler uptake fire. When an uptake fire is suspected, never soot blow the economiser. Soot blow with steam causes steam to convert as hydrogen gas and result in metal fire.
Regularly inspect boiler flame to ensure correct air fuel ratio is maintained. This makes complete combustion with clean flue gas. Carry out boiler burner and swirler routines as per PMS. Regularly soot blow economisers and water wash periodically to remove soot deposits. Use proper grade of fuel oil for boiler. Fuel oil used for boiler to be treated well. Avoid low load operation of boiler for long period. Running boiler near full load periodically, helps in expelling out carbon deposits adhered in uptake ages and reduces chances of boiler uptake fire considerably.
A flame appear at the economizer coil during running of main engine at sea while the EGE is put into service with circulation water ing through the coils, it is called economizer fire. It is actually cause by soot fire at the economizer coils. For the economizer coils fire, heat is already presented due to ing the gases of main engine. Air is available due to excess supply of scavenging air into the unit combustion chamber. Thick deposit of unburnt fuel, carbon residue (soots) are sticking at the economizer coils .
High Voltage System on Ships
Soots are formed from incomplete combustion and use of low grade fuel and high carbon content
Insulation Resistance Tests of High
fuel. At the manoeuvring time, the more incomplete combustion may occur and at that time leaving flue
Voltage Equipment
gas velocity is very low, thus unburnt fuel can be adhering on the economizer coils. A flame is produced when air and fuel are proportionally mixed in the sufficient heating temperature.
Earthing Down in High Voltage System Life Boat Release Gear Mechanism on Ships Lambda Controller and Jet Assist System on Ships
1. Smoke smell will get from the economizer. 2. Over heat at economizer body ( external casing of uptake.)
Pneumatic Control Systems on Ships
3. Heavy smoke and sparks will emit from the funnel. 4. Sudden unexpected increase in uptake gas temperature ( Abnormally high stack pyrometer reading) 5. Flame visible in the smoke indicator. air compressors air conditioning boiler boiler blow down boilers cargo cargo
7/17/17, 9:52 PM
Boiler Uptake Fire and Exhaust Gas Economiser Fire
2 of 4
http://marineengineeringonline.com/boiler-uptake-fire/
1. To get complete combustion of fuel, maintain the main engine (ME) in optimum combustion condition.( governor, fuel injection pump, fuel injection valve, fuel injection timing, fuel condition, air cooler, turbocharger, do not run too long ME with slow speed) 2. Regular open up & cleaning smoke side of economiser depending upon soot accumulation. (water washing) 3. Regular soot blowing operation. Check & maintain soot blowing equipment. 4. Regular overhaul boiler burner, correct air fuel ratio & damper.
pumps centrifugal pumps chemical tankers circulation system cooling water system cross head bearing oil system cylinder lube oil
diesel engines explosimeter fire detectors fire fighting fire triangle freshwater generator freshwater
system
generator on ships heat exchangers
indicator diagrams inert gas system invention of diesel engine lube oil system
1. Inform to the bridge and chief engineer. Take the permission to stop main engine. 2. Gradually slowdown the ME and then stop. 3. If fire fighting equipment is fitted, it should be brought into operation. 4. Cool down the economizer by means of boundary cooling. 5. Circulation pump must be run but, if large amount of water lost it must be stopped.
magnetic particle testing main bearing oil
marine engineering marine
system main engine
engineering study materials meo class exam questions panting pid
6. There is no heat source and fire is out. 7. When economizer fire occurs never do soot blow to economizer.
marine main switch board
8. It can cause hydrogen fire and melt down the coils stack. It can cause deformation and tube
controller positive displacement pumps
bulking because intensive heat and high thermal stress formed at economizer coils.
pounding proportional control pumps relief valve safeties in main switch board
sewage treatment plant smoke detectors
1. Cool down to ambient temperature. 2. Open the economizer cover. 3. Clean inside parts of the economizer.
stp systems of main engine types of chemical tankers
4. Check the any defective coil and repair for temporary used by welding or plugging the tubes.
1. Slow down the engine. 2. Shut off oil burners, draught fans, dampers & air . 3. Raise water level full and blow down continuously so as to maintain good flow of water. 4. Reduce boiler pressure by easing gear. 5. Spray water on the external casing of the uptake to cool the affected area. 6. A few times starting and stopping of main engine should be done to blow out collected soots at the uptake.
When the fire causes the metal itself burning at about 700 °C, if steam smothering soot blowing system or water jetting system have been attempted, the big hydrogen fire may result. The applied steam dissociates into hydrogen and oxygen and accelerating the fire. Once such a fire has started, resulting two kind of fires may take place simultaneously, one kind, iron burning in steam, and the other, the hydrogen burning in an air exothermic way. This combined fire being self ing and lasting until the supply of steam is exhausted. The primary objective of dealing the fire is to cool the surface and burning material as quickly as possible.