SPLIT-TYPE AIR CONDITIONERS Full Product Line Catalogue 2015
NOTICE
■ Do not install indoor units in areas (e.g., mobile phone base stations) where the emission of VOCs such as phthalate compounds and formaldehyde is known to be high as this may result in a chemical reaction. ■ When installing or relocating or servicing the air conditioners, use only the specified refrigerant (R410A) to charge the refrigerant lines. Do not mix it with any other refrigerant and do not allow air to remain in the lines. If air is mixed with the refrigerant, then it can be the cause of abnormal high pressure in the refrigerant lines, and may result in an explosion and other hazards. The use of any refrigerant other than that specified for the system will cause mechanical failure, system malfunction or unit breakdown. In the worst case, this could lead to a serious impediment to securing product safety.
Eco Changes is the Mitsubishi Electric Group’s environmental statement, and expresses the Group’s stance on environmental management. Through a wide range of businesses, we are helping contribute to the realization of a sustainable society.
Wrap Yourself in Comfort and Quiet Eco-conscious Technologies from Japan
Full Product Line Catalogue
2015
For luxury mansion and condominium, Maximize the comfortability with a single outdoor unit, Mitsubishi Electric Inverter Multi split Systems
1
Space Savings
Economical Operation
Silent Control
Flexible Choice
The Mitsubishi Electric Inverter Multi split System is designed to allow several indoor units to be connected to a single outdoor unit. This enhances exterior aesthetics by reducing the number of outdoor units necessary, while also providing you with an easy and economical way of adding indoor units at any time.
We are able to offer industry-leading levels of energy-efficient operation for both heating and cooling with the latest innovative inverter technologies. Save energy and money with the Mitsubishi Electric Inverter Multi split System.
Comfort with less noise, based on smooth operation and innovative features such as automatic selection of low-noise mode when operation load is low. Choose a wall-mounted model to create a silent and comfortable space where noise levels are kept low so that soothing peace and quiet can be enjoyed.
Offering the ability to select up to 6 indoor units for a single outdoor unit, Mitsubishi Electric Inverter Multi split Systems satisfy diversified needs. With the cooling capacities of outdoor units ranging from 5.0 to 12.0kW and a line up of different models to suit specific applications, you will not be hard pressed to find a better match for your building dimensions and comfort requirements.
2
Types of Air Conditioning Systems and Suitable Choice for Your Home Enhance room comfort with the air conditioner that best matches the interior. For reliable operation and design, Mitsubishi Electric is the logical choice.
Single Split ■ Suitable for · Small residences like studio apartments · Homes with floor area of 20-50m2 · Installing additional units if required
TABLE OF CONTENTS
INVERTER MULTI SPLIT LINE-UP
Inverter Multi Split (5.0~12.0kW)
CITY MULTI (12.5~25.0kW)
■ Suitable for · Small to medium-sized residences (condominiums or leased apartments) · Homes with floor area of 50-100m2 · Homes with limited space for outdoor unit installation · Increasing usable space at homes (for developers) · s who prefer to keep neat appearance with ceiling-concealed model · Wide variety of indoor unit combination
■ Suitable for · Large-scale residences (condominiums or leased apartments) · Homes with floor area of 80m2 or more · Entrance hall or penthouse · Using a centralized control system as integrated control of air conditioning, lighting, security system and other electric appliances · More freedom in air conditioning design due to less piping length restrictions · Increasing usable space in homes (for developers) · s who prefer to keep neat appearance with ceiling-concealed model · Wide variety of indoor unit combination
6
INVERTER TECHNOLOGIES
7- 8
FUNCTIONS
9-14
MXY SERIES (Cooling Only)
15-24
MXZ SERIES (Heat Pump)
25-33
EXTERNAL DIMEMSIONS
34-39
PIPING INSTALLATIONS
40-41
CITY MULTI CITY MULTI S SERIES
43-46
INDOOR UNIT LINE-UP
47-48
SYSTEM CONTROL
49-50
Please refer to page 50 for centralized control.
3
4
INVERTER MULTI SPLIT
LINE-UP INVERTER Models (Cooling Only)
MXY SERIES
5.0kW
7.5kW
7.5kW
9.2kW
Up to 2 indoor units MXY-2E20VA
Up to 3 indoor units MXY-3A28VA
Up to 4 indoor units MXY-4A28VA
Up to 4 indoor units MXY-4A38VA
Capacity Class
Model Name
SERIES INVERTER Models (Heat Pump)
MXZ SERIES Capacity Class
5.2kW
6.8kW
7.1kW
8.0kW
10.0kW
12.0kW
Up to 2 indoor units MXZ-2C52VA
Up to 3 indoor units MXZ-3C68VA
Up to 4 indoor units MXZ-4C71VA
Up to 4 indoor units MXZ-4C80VA
Up to 5 indoor units MXZ-5C100VA
Up to 6 indoor units MXZ-6C120VA
5.0kW
6.0kW
7.1kW
Model Name
Indoor Unit for MXY and MXZ Model Name
Capacity Class
2.5kW
3.5kW
MSY-E Series MSZ-E Series
Wallmounted MSY-G Series MSZ-G Series
MLZ Series
1-way cassette
PLA Series
4-way cassette
SEZ Series
Cellingconcealed
5
6
INVERTER TECHNOLOGIES Mitsubishi Electric inverters ensure superior performance including the optimum control of operation frequency. As a result, optimum power is applied in all heating/cooling ranges and maximum comfort is achieved while consuming minimal energy. Fast, comfortable operation and low running cost — That’s the Mitsubishi Electric promise.
MORE ADVANTAGES WITH MITSUBISHI ELECTRIC PAM (Pulse Amplitude Modulation)
t Lap DC Motor Mitsubishi Electric has developed a unique motor, called the “Poki-Poki Motor” in Japan, which is manufactured using a t lapping technique. This innovative motor operates based on a high-density, high-magnetic force, leading to extremely high efficiency and reliability.
PAM is a technology that controls the current waveform so that it resembles the supply voltage wave, thereby reducing loss and realising more efficient use of electricity. Using PAM control, 98% of the input power supply is used effectively. With PAM control
Without PAM control Supply voltage
INVERTERS – HOW THEY WORK
Time
Current
Inverters electronically control the electrical voltage, current and frequency of electrical devices such as the compressor motor in an air conditioner. They receive information from sensors monitoring operating conditions, and adjust the revolution speed of the compressor, which directly regulates air conditioner output. Optimum control of operation frequency results in eliminating the consumption of excessive electricity and providing the most comfortable room environment.
Time
PAM adjusts the form of the current wave so that it becomes close to that of the supply voltage wave. High harmonics are reduced and 98% of the electricity is utilized.
■ Merits of PAM Control
Reluctance DC Rotary Compressor Powerful neodymium magnets are used in the rotor of the reluctance DC compressor motor. More efficient operation is realised by strong magnetic and reluctance torques produced by the magnets.
ECONOMIC OPERATION Impressively low operating cost is a key advantage of inverter air conditioners. We’ve combined advanced inverter technologies with cutting-edge electronics and mechanical technologies to achieve a synergistic effect that enables improvements in heating/cooling performance efficiency. Better performance and lower energy consumption are the result.
Neodymium magnets
DC compressor motor (rotor)
Significant energy savings Remarkable reduction in power loss saves electricity
Power increased Efficient voltage increase realises increased power
PAM Conventional inverter Limited power Insufficient power when needed
Limited energy savings Electricity is wasted
Power Receiver and Twin LEV Control Mitsubishi Electric has developed a power receiver and twin linear expansion valves (LEVs) circuit that optimise compressor performance. This technology ensures optimum control in response to operating waveform and outdoor temperature. Operating efficiency has been enhanced by tailoring the system to the characteristics of R410A refrigerant.
TRUE COMFORT Simple comparison of air conditioner operation control with and without inverter
Magnetic torque
■ Inverter Operation Image (cooling mode)
+
Cooling capacity (W)
Temperature (°C)
Reluctance torque
Rated capacity
Setting temperature
Indoor temperature
Point 2 Measured capacity
Compressor
Power receiver
Point 1 When room temperature is higher than the setting, capacity rises quickly, adjusting the temperature to the original setting.
Heat exchanger
Heat exchanger
LEV1
LEV2
Rare Earth Magnet Rotor (Compressor) An innovative motor with a rare earth magnet rotor is equipped in the compressor to ensure excellent efficiency. The rare earth magnet has a residual magnetic flux density threefold that of the previously used ferrite magnet.
When room temperature reaches the desired setting, capacity eases in order to maintain the set temperature level.
Grooved Piping High-performance grooved piping is used in heat exchangers to increase the heat exchange area. Grooved piping
Operation time (min)
Rare earth magnet (for MSZ-EF)
Pipe image Cross-sectional view
Point 1
Quick & Powerful
Increasing the compressor motor speed by controlling the operation frequency ensures powerful output at start-up, brings the room temperature to the comfort zone faster than units not equipped with an inverter. Hot rooms are cooled, and cold rooms are heated faster and more efficiently.
7
Point 2
Room Temperature Maintained
The compressor motor operating frequency and the change of room temperature are monitored to calculate the most efficient waveform to maintain the room temperature in the comfort zone. This eliminates the large temperature swings common to non-inverter systems, and guarantees a pleasant, comfortable environment.
DC Fan Motor A highly efficient DC motor drives the fan of the outdoor unit. Efficiency is much higher than an equivalent AC motor.
8
FUNCTIONS (1)
SYSTEM CONTROL Versatile system controls can be realised using optional parts, relay circuits, control s, etc.
AIRSYSTEM DISTRIBUTION MAJOR CONTROL
ENERGY-SAVING Econo Cool Energy-Saving Feature “Econo Cool” is an intelligent temperature control feature that adjusts the amount of air directed towards the body based on the air-outlet temperature. The setting temperature can be raised by as much as 2°C without any loss in comfort, thereby realising a 20% gain in energy efficiency. (Function only available during manual cooling operation.) Ambient temperature
Conventional 35°C
Horizontal Vane
Econo Cool Mode
A comfortable room environment is maintained even when setting the temperature 2°C higher than the conventional cooling mode. Econo Cool on
Conventional cooling mode
25°C
27°C
Perceived temperature
30°C
29.3°C
The airUnit outlet vane swings up and down so that the airflow is spread Indoor M series Indoor Unit evenly throughout the room. Outdoor Unit
In the case of rooms with high & ceilings, outlet-air volume can be S series P series the Indoor Unit increased to ensure that air is circulated all the way to the floor. MXZ Series Outdoor
MXZ Series Outdoor
Vertical Vane
Low Ceiling Mode MAC397IF-E
If the room has a low ceiling, the airflow volume can be reduced for less draft.
The air outlet fin swings from side to side so that theIndoor airflow reaches unit every part ofControl the room. PAR-30MAA PAR-21MAA Control
Econo Cool 35°C
Set temperature
High Ceiling Mode
System Examples
Outdoor unit
PAR-30MAA PAR-21MAA
PAR-30MAA PAR-21MAA
Auto Fan Speed Mode
Temperature distribution (°C) 14
16
18
20
22
24
26
28
The airflow speed mode adjusts the fan speed of the indoor unit Standard equipment automatically according to thewith present roomcontrollers) conditions. (for indoor units compatible wired remote
• Wired remote controller can be connected to indoor unit
Details
Wide and Long Airflow
• MAC-397IF-E (Interface)
ATTRACTIVE Pure White
of the room.
• PAR-21MAA (Wired remote controller)
Auto Vane
Pure white is adopted for the unit colour; white expressing the essence of cleanliness and easily matching virtually all interior décor.
• PAR-30MAA (Wired remote controller)
• PAR-30MAA (Wired remote controller) for large spaces, helping to ensure that air is well circulated and reaches every corner Major Parts Required The Optional wide and long airflow function is especially beneficial • PAR-21MAA (Wired remote controller)
The vane closes automatically when the air conditioner is not running, concealing the air outlet and creating a flat surface that is aesthetically appealing.
Indoor unit
Indoor unit
CONVENIENCE MAC-397IF-E
System Group Control
On/Off Operation Timer
Outdoor unit
Outdoor unit
MAC-397IF-E
PAR-30MAA PAR-21MAA
PAR-30MAA PAR-21MAA
Use the remote controller to set the times of turning the air conditioner On/Off.
AIR QUALITY Catechin Filter
Fresh-air Intake Indoor air quality is enhanced by the direct intake of fresh exterior air.
Anti-allergy Enzyme Filter The anti-allergy enzyme filter works to trap allergens such as molds and bacteria and decompose them using enzymes retained in the filter.
Catechin is a bioflavonoid by-product of green tea with both antiviral and antioxidant qualities. It also has an excellent deodorising effect, which is why Mitsubishi Electric uses the compound in its air conditioner filters. In addition to improving air quality, it prevents the spreading of bacteria and viruses throughout the room. Easily removed for cleaning and maintenance, when the filter is washed regularly the deodorising action is rated to last more than 10 years.
High-efficiency Filter This high-performance filter has a much finer mesh compared to standard filters, and is capable of capturing minute particulates floating in the air that were not previously caught. Nano Platinum
Nano Platinum Filter
The filter has a large capture area and incorporates nanometre-sized platinum-ceramic particles that work to eliminate bacteria and deodourise the circulating air.
Details
Long-life Filter A special process for the entrapment surface improves the filtering effect, making the maintenance cycle longer than that of units equipped with conventional filters.
Filter Check Signal Air conditioner operating time is monitored, and the is notified when filter maintenance is necessary. Electrostatic Anti-allergy
Electrostatic Anti-allergy Enzyme Filter
This function features both the Air Cleaning Filter and Anti-allergy Enzyme Filter.
9
• One remote controller can control plural air conditioners with the same settings simultaneously. • One remote controller can control up to 16 refrigerant systems. (When connected to a MXZ unit, MAC-397IF-E is counted as one system.)
• Up to two remote controller can be connected. “i save” Mode/Smart Set
• MAC-397IF-E (Interface) “i save” is a simplified setting function that recalls the preferred (preset) temperature by pressing a single button on the remote controller. • PAR-30MAA (Wired remote controller) • PAR-21MAA (Wired remote controller) Smart Set : Press the same button twice in repetition to immediately return to the previous temperature setting. Using this function contributes to comfortable waste-free operation, realising the most suitable air conditioning settings and saving on power consumption when, for example, leaving the room or going to bed. Outdoor Outdoor
Major Optional Parts Required
Outdoor unit
unit
Low-temperature Cooling
(AG-150A etc) performance even when the outside temperature isPAC-SC50KA low.
Details
Indoor unit
Auto Restart
City Multi indoor unit
MELANS Intelligent fan speed control in the outdoor unit ensures optimum M-NET Connections system controller MAC-399IF-E
ME remote controller (PAR-F27MEA)
unit
Indoor unit
Indoor unit
PAC-SC50KUA Power supply kit
Indoor unit PAR-30MAA PAR-21MAA
City Multi indoor unit
PAR-30MAA PAR-21MAA MAC-399IF-E
Indoor unit PAR-30MAA PAR-21MAA
PAR-30MAA PAR-21MAA
Especially useful at the time of power outages, the unit turns back on MELANS automatically when power is restored. system controller (AG-150A etc)
Power supply unit
PAC-SC50KA Power supply unit
MELANS system controller (AG-150A etc)
M-NET adapter PAC-SF81MA-E
Low-noise Operation (Outdoor Unit) Ampere Limit• Group Adjustment of air conditioners can be controlled by MELANS system controller (M-NET).
Dipswitch settings can be used to adjust the maximum electrical • MAC-399IF-E (M-NET Interface) current for Parts operation. is highly recommended for MELANS System controller Major Optional RequiredThis •function • PAC-SC50KUA (power supply unit) managing energy costs.
System operation can be adjusted to prioritise less noise from the • PAC-SF81MA-E (M-NET converter) outdoor unit over air conditioning performance. • MELANS System controller • PAC-SC50KUA (power supply unit)
*Maximum capacity is lowered with the use of this function.
MAJOR OPTIONAL PARTS Operation Lock
Auto Changeover
M-NET Interfacespecific use applications, cooling or heating To accommodate Interface to connect with M-NET con-
M-NET interface
operation can be specified when setting the control board of the trollers. outdoor unit. A convenient option when a system needs to be configured for exclusive cooling or heating service.
Air Guide TheDischarge air conditioner automatically switches between heating and coolChanges the direction of air being ing modes to maintain theunit. desired temperature. exhausted from the outdoor
10
FUNCTIONS FUNCTIONS (2)
SYSTEM CONTROL Versatile system controls can be realised using optional parts, relay circuits, control s, etc.
Built-in Weekly Timer Function
MAJOR SYSTEM CONTROL
Easily sets desired temperatures and operation start/stop times to match lifestyle patterns. Reduce wasted energy consumption by using the timer to prevent forgetting to turn off the unit and eliminate temperature setting adjustments. ■ Example Operation Pattern (Winter/Heating mode) Mon.
Tues.
Wed.
Thurs.
Fri.
Sat.
Sun.
ON 20°C
ON 20°C
ON 20°C
ON 20°C
ON 20°C
ON 20°C
ON 20°C
ON 18°C
ON 18°C
System Examples
Indoor Unit
M series Indoor Unit
S series & P series Indoor Unit
Outdoor Unit
MXZ Series Outdoor
MXZ Series Outdoor
Automatically changes to high-power operation at wake-up time MAC397IF-E
OFF
OFF
OFF
OFF
OFF
Midday is warmer, so the temperature is set lower
Automatically turned off during work hours
ON 20°C
ON 20°C
ON 20°C
ON 20°C
ON 20°C
(during sleeping hours)
ON 18°C
ON 18°C
ON 18°C
ON 18°C
ON 20°C
ON 18°C
ON 18°C
PAR-30MAA Control PAR-21MAA Control
PAR-30MAA PAR-21MAA
PAR-30MAA PAR-21MAA
Details
• Wired remote controller can be connected to indoor unit
Standard equipment (for indoor units compatible with wired remote controllers)
Major Optional Parts Required
• MAC-397IF-E (Interface) • PAR-30MAA (Wired remote controller) • PAR-21MAA (Wired remote controller)
• PAR-30MAA (Wired remote controller) • PAR-21MAA (Wired remote controller)
ON 18°C
Automatically lowers temperature at bedtime for energy-saving operation at night
Settings
Outdoor unit
ON 20°C
Automatically raises temperature setting to match time when outside-air temperature is low
Automatically turns on, synchronized with arrival at home
Indoor unit
Pattern Settings: Input up to four settings for each day Settings: • Start/Stop operation • Temperature setting ✽ The operation mode cannot be set.
Indoor unit
Indoor unit
MAC-397IF-E
Cleaning-free Pipe Reuse The application of pipe reuse technology such as Mitsubishi Electric’s original hard alkyl benzene oil makes it possible to reuse the same piping, thereby allowing cleaning-free renewal of air conditioning systems that use R22 refrigerant.
Wiring/Piping Correction Function* The push of a single button is all that is required to confirm that piping and wiring are properly connected. Corrections are made automatically if a wiring error is detected, eliminating the need for complicated wiring confirmation work when expanding the number of rooms served.
Wiring confirmation is time consuming.
The outdoor unit matches pipes and wiring.
System Group Control Outdoor unit
PAR-30MAA PAR-21MAA
PAR-30MAA PAR-21MAA
Details
• One remote controller can control plural air conditioners with the same settings simultaneously. • One remote controller can control up to 16 refrigerant systems. (When connected to a MXZ unit, MAC-397IF-E is counted as one system.) • Up to two remote controller can be connected.
Major Optional Parts Required
• MAC-397IF-E (Interface) • PAR-30MAA (Wired remote controller) • PAR-21MAA (Wired remote controller)
Outdoor unit
* This function cannot be used when the outdoor temperature is below 0°C. The correction process requires 10–20 minutes, and only works when the unit is set to the Cooling mode.
Indoor unit
Outdoor unit
Outdoor unit
Indoor unit
Indoor unit
City Multi indoor unit
M-NET Connections
Drain Pump
Flare Connection
A built-in drain pump enables drain piping to be raised.
Outdoor unit
MAC-397IF-E
ME remote controller (PAR-F27MEA)
Flare connection to cooling pipe work is possible.
MAINTENANCE
MAC-399IF-E
MELANS system controller (AG-150A etc)
PAC-SC50KUA Power supply kit
PAR-30MAA PAR-21MAA
Indoor unit PAR-30MAA PAR-21MAA
City Multi indoor unit
Indoor unit PAR-30MAA PAR-21MAA
PAR-30MAA PAR-21MAA
MAC-399IF-E
MELANS system controller (AG-150A etc)
PAC-SC50KA Power supply unit
PAC-SC50KA Power supply unit
Details
• Group of air conditioners can be controlled by MELANS system controller (M-NET).
Major Optional Parts Required
• MAC-399IF-E (M-NET Interface) • MELANS System controller • PAC-SC50KUA (power supply unit)
MELANS system controller (AG-150A etc)
M-NET adapter PAC-SF81MA-E
• PAC-SF81MA-E (M-NET converter) • MELANS System controller • PAC-SC50KUA (power supply unit)
Easy Clean
MAJOR OPTIONAL PARTS
The cover can be quickly removed for washing and the airflow vents can be opened without any special tools, making it easy to clean the inside of the air conditioner in minutes. Periodic cleaning of the air conditioner is recommended to maintain optimum operating efficiency and energy savings.
Self-Diagnostic Function (Check Code Display) Check codes are displayed on the remote controller or the operation indicator to inform the of malfunctions detected.
11
Failure Recall Function
Air Discharge Guide
M-NET Interface
Interface to connect with M-NET controllers.
M-NET interface
Changes the direction of air being exhausted from the outdoor unit.
Operation failures are recorded, allowing confirmation when needed.
12
FUNCTION LIST
Category Category
Indoor Unit
Icon
Combination
Outdoor Unit DCunit Inverter Indoor MSZ-FD20/35/50VA(S) t Lap DC Motor Reluctance DC Rotary Compressor MUZ MXZ MXZ MXZ MXZ MXZ MXZ Outdoor unit Rare Earth-FD Magnet -2CRotor -3C(Compressor) -4C -5C -6C -8B Technology DC Fan Motor DC Inverter Technology PAM (Pulse Amplitude Modulation) t Lap DC Motor Power Receiver and Twin LEV Control Grooved Magnetic Flux Vector Sine Wave Drive Piping Energy Saving Econo Cool Energy-saving Feature Reluctance DC Rotary Compressor 80 Pure White Attractive Highly Efficient DC Scroll Compressor Auto Vane Fresh-air Intake Rare Earth Magnet Rotor(Compressor) Anti-allergy Enzyme Filter DC Fan Motor Electrostatic Anti-allergy Enzyme Filter Vector-Wave Eco Inverter High-efficiency Filter Air Quality Catechin Filter PAM(Pulse Amplitude Modulation) Nano Platinum Filter Power Receiver and Twin LEV Control Long-life Filter Grooved Piping Filter Check Signal Energy Vane Felt Temperature Control (i-seeHorizontal Sensor) Saving Vertical Mode AREA Temperature Monitor High Ceiling Mode AirEcono Distribution Cool Energy-saving Low Feature Ceiling Mode Functions Auto Fan Speed Mode 'I-Feel' Control Wide and Long Airflow Demand Function Opt On/Off Operation Timer Attractive Pure White VA VA VA VA VA Set VA / Smart VA "i save" Mode Auto Restart Auto Vane Low-noise Operation Air QualityConvenience Plasma Duo Ampere Limit Adjustment Air Cleaning Filter Operation Lock Fresh-air Intake Built-in Weekly Timer Function Anti-allergy Enzyme Filter Cleaning-free Pipe Reuse Wiring/Piping Correction Function Installation Electrostatic Anti-allergy Enzyme Filter Drain Pump High-efficiency Filter Flare Connection Easy Clean Catechin Filter Maintenance Self-Diagonosis Function (Check Code Display) Nano Platinum Filter Failure Recall Function
MSY-EF (10/13/18)
MXY-2E
MXY-3A
M SERIES
MXY-4A
MSY-GE (10/13/18/24/26) MXY-2E
MSZ-EF22/25/35/42/50VE(W)(B)(S)
MXY-3A
MLZ-KA (25/35/50)
MXY-4A
MXY-2E
MSZ-GE22/25/35/42/50/60/71VA
MXY-3A
PLA-RP (50/60/71) MXY-4A
MSZ-SF15/20VA
4A38 4A38 4A38 MUZ MXZ MXZ MXZ MXZ MXZ MXZ MUZ MXZ MXZ MXZ MXZ MXZ MXZ MXZ MXZ MXZ MXZ MXZ MXZ -EF -2C -3C -4C -5C -6C -8B -GE -2C -3C -4C -5C -6C -8B -2C -3C -4C -5C -6C -8B
80
VAW
VAW
Opt
80
VAW
Opt
Opt 10-18 Opt 24/26
Opt
Opt
Opt
10-18
10-18 24/26
10-18 24/26
Opt
Opt
Opt
24/26
24/26
24/26
24/26
*2
*2
24/26
24/26
*2
MUZ MUH MU MUH MUH MUH MU -HC -GA 4A38 -GA -GE -GA -GD -GE
Opt
Opt
Opt
Opt
Opt Opt Opt Opt 22-50 22-50 22-50 22-50 Opt Opt Opt Opt 60/71 60 60/71
4A38
Opt
Opt
60
M SERIES
MU -GA
S SERIES
MFZ-KA25/35/50VA
Opt 22-50 Opt 60/71
MLZ-KA25/35/50VA
Opt Opt 22-50 22-50 4A38 Opt Opt 60/71 60/71
SLZ-KA25/35/50VAL/VAQ
SEZ-KD25/35/50/60/71VAL/VAQ
MU 4A38 SUZ MXZ MXZ MXZ MXZ MXZ MXZ MXZ MXZ MXZ MXZ MXZ MXZ SUZ MXZ MXZ MXZ MXZ MXZ MXZ SUZ MXZ MXZ MXZ MXZ MXZ MXZ -GD -KA -2C -3C -4C -5C -6C -8B -2C -3C -4C -5C -6C -8B -KA -2C -3C -4C -5C -6C -8B -KA -2C -3C -4C -5C -6C -8B
80
80
71
80
Opt
Opt
Opt
4A38
Opt
Opt
Opt
Opt
Opt
Opt
Opt
Opt
Opt
Opt
4A38 Opt
22-50 22-50 22-50 22-50 22-50 22-50 22-50 60/71
MXY-4A
35
Opt
Opt
MXY-3A
MSH- MSH- MSH- MS- MS- MSMSCHC25/35 GE20/25/35 GE50 GA60 GD80 GE50 GA60 GD80 VA(B) VB VB VB VB VB VB VB
Opt
VEW VEW VEW VEW VEW VEW VEW
MXY-2E
80
Opt 10-18 Opt 24/26
Opt
SEZ-KD (25/35/50/60/71)
MXY-4A
80
Opt 10-18 Opt
MXY-3A MSZ-
Opt
4A38 Opt
Opt
Opt
Opt
Opt
Opt
Opt
Opt
Opt
Opt
Opt
Opt
Opt
Opt
60/71 60/71 60/71 60/71
Oil Mist Filter
Category
Long-life Filter
Indoor Unit
Filter Check Signal
Outdoor Unit
DC Inverter t Lap DC Motor Reluctance DC Rotary Compressor High Ceiling Mode Rare Earth Magnet Rotor (Compressor) Technology DC Fan Motor Low Ceiling Mode PAM (Pulse Amplitude Modulation) Auto Fan Speed Mode Power Receiver and Twin LEV Control Wide and Long Airflow Grooved Piping Convenience Energy Econo Cool Energy-saving Feature On/offSaving Operation Timer Pure White "i save" Mode Attractive Auto Vane Auto Changeover *1 *1 *1 *1 Fresh-air Intake *1 Anti-allergy Enzyme Filter Auto Restart Electrostatic Anti-allergy Enzyme Filter Low-temperature Cooling High-efficiency Filter AirLow-noise Quality Operation(Outdoor Unit) Catechin Filter Ampere Limit Adjustment Nano Platinum Filter 80 Long-life Filter Operation Lock Filter Check Signal Built-in Weekly Timer Function Horizontal Vane Rotation, Back-up and 2nd Stage Cut-inVertical Functions Mode High Ceiling Mode System AirPAR-30MAA Opt Opt Opt Opt Opt Opt DistributionControl *3 Control Low Ceiling Mode PAR-21MAA Control *3 Opt Mode Opt Opt Opt Opt Opt Auto Fan Speed Centraliesd On/Off Control Wide *3 and Long Functions Opt Airflow Opt Opt Opt Opt Opt Timer System Group Control *3 On/Off Operation Opt Opt Opt Opt Opt Opt "I save" Mode M-NET Connection *3 Opt Opt Opt Opt Opt Opt Auto Changeover COMPO *4 Auto Restart Low-temperature Cooling Convenience MXZ Connection *2 *2 *2 *2 *2 Low-noise Operation Installation Cleaning-free Pipe Reuse Ampere Limit Adjustment Reuse of Existing Wiring Operation Lock Built-in Weekly Timer Function80 Wiring/Piping Correction Function Cleaning-free Pipe Reuse Drain Pump Wiring/Piping Correction Function Installation Pump Down Switch Drain Pump Flare Connection Flare Connection Easy Clean Maintenance Quick Clean Body Maintenance Self-Diagonosis Function (Check Code Display) Self-Diagnosis Function(Check Code Display)Recall Function Failure
MSZ-EF (25/35/50) MXZ-2C
MXZ-3C
MXZ-4C
Air Horizontal Vane Distribution Vertical Vane
Functions
4C80
VEW *1
*1
VEW *1
Opt
*1
MSZ-GE (25/35/50/60/71) MXZ-5C
Opt
*1
MXZ-2C
60/71
60/71 60/71 60/71 60/71
60/71
60/71 60/71 60/71 60/71
VEW *1
MXZ-6C
VEW *1
*1
Opt
MXZ-3C
MXZ-4C
MXZ-5C
MLZ-KA (25/35/50) MXZ-6C
MXZ-2C
MXZ-3C
4C80
MXZ-4C
PLA-RP (50/60/71) MXZ-5C
MXZ-6C
MXZ-3C
MXZ-4C
4C80
MXZ-6C
MXZ-2C VAQ VAQ VAQ MXZ-4C VAQ VAQ VAQ VAQMXZ-3C
4C80
MXZ-5C
MXZ-6C
4C80
VEW *1
Opt
*1
*1
*1
*1
*1
*1
*1
*1
*1
*1
*1
*1
Opt 25-50
Opt 25-50 Opt 60
Opt 25-50 Opt 60/71
Opt 25-50 Opt 60/71
Opt 25-50 Opt 60/71
Opt
Opt
Opt
Opt
Opt
25-50
25-50 60
25-50 60/71
25-50 60/71
25-50 60/71
Opt
Opt
Opt
Opt
Opt
60/71
60/71
Opt
*1
*1
*1
80
80
80
*1
*1
Opt
60/71
SEZ-KD (25/35/50/60/71)
MXZ-5C
*1
Opt
*1
*1
Opt
80
*1
*1
*1
*1
*1
*1
*1
*1
*1
*1
*1
*1
*1
*1
Opt 80
80
80
60 60/71 60/71 60/71 60/71
60
60/71
Opt
Opt
Opt
Opt
Opt
Opt
Opt
Opt
Opt
Opt
Opt
Opt
Opt
Opt
Opt
Opt
Opt
Opt
Opt
Opt
Opt
Opt
Opt
Opt
Opt
Opt
Opt
Opt
Opt
Opt
Opt
Opt
Opt
Opt
Opt
Opt
Opt
Opt
Opt
Opt
Opt
Opt
Opt
Opt
Opt
Opt
Opt
Opt
Opt
Opt
Opt
Opt
Opt
Opt
Opt
Opt
Opt
Opt
Opt
Opt
Opt
Opt
Opt
Opt
Opt
Opt
Opt
Opt
Opt
Opt
Opt
Opt
Opt
Opt
Opt
Opt
Opt
Opt
Opt
Opt
Opt
Opt
Opt
Opt
Opt
Opt
Opt
Opt
Opt
Opt
Opt
Opt
Opt
Opt
Opt
Opt
Opt
Opt
Opt
Opt
Opt
Opt
Opt
Opt
Opt
Opt
Opt
Opt
Opt
Opt
Opt
Opt
60 Opt
Opt
60/71 Opt Opt
60/71 Opt
Opt
Opt
Opt
Opt
Opt
Opt
Opt
Opt
Opt
Opt
Opt
Opt
Opt
Opt
Opt
Opt
Opt
Opt
Opt
Opt
Opt
Opt
Opt
Opt
Opt
Opt
Opt
Opt
Opt
Opt
Opt
Opt
Opt
Opt
Opt
Opt
Opt
Opt
Opt
Opt
Opt
Opt
Opt
Opt
Opt
Opt
Opt
Opt
Opt
Opt
Opt
Opt
Opt
Opt
Opt
Opt
Opt
Opt
Opt
Opt
Opt
Opt
Opt
Opt
Opt
Opt
Opt
Opt
Opt
Opt
Opt
Opt
Opt
Opt
Opt
Opt
Opt
Opt
Opt
Opt
*1 Opt
Opt
*1Opt
Opt
Opt
Opt
Opt
*1 Opt
Opt
*1Opt
Opt
Opt
Opt
Opt
*1 Opt
Opt
Opt
Opt
Opt
*1 Opt
Opt
*1Opt
Opt
Opt *1
Opt
Opt
*1
Opt
Opt
*1 Opt
Opt
Opt *1
Opt
Opt
Opt
Opt
*1 Opt
Opt
*1Opt
Opt
Opt
Opt
Opt
Opt
*2
*2
*2
*2
*2
*2
*2
*2
*2
*2
*2
*2
*2
*2
*2
*2
*2
*2
*2
*2
*2
*2
*2
*2
*2
*2
*2
*2
*2
*2
*2
*2
Opt
Opt
Opt
Opt
Opt
Opt
*2
*1
*2
*1
22-50*2 22-50*2
*2
*2
*1
4C80
4C80
*1
60
80
60/71 4C80
*1
*1
*1
*2
4C80 80
80
*2
*1
60/71
*1
*2
4C80 60/71
60/71
4C80 80
4C80
*2
*1
*2
*1
4C80 80
80
4C80 Opt
Opt
80
4C80 Opt
Opt
Opt
Opt
*1 When multiple indoor units connected Failure Recall Functionto an MXZ outdoor unit are runnning at the same time, simultaneours cooling and heating is not possible. *2 Smart Set is available for MSY-GE10/13/18VA, "i save" mode is available for MSY-GE24/26VA
13
14
MXY
SELECTION Choose from three types of indoor units and three types of outdoor units. Create the system that best matches the room shapes and the number of rooms.
STEP 1
SELECT INDOOR UNITS Select the indoor unit to be installed in each room.
Wall-mounted
Cassette
Ceiling-concealed
SERIES MSY-EF
MSY-GE(10-18)
MLZ-KA
PLA-RP
SEZ-KD
MSY-GE(24-26)
SELECT OUTDOOR UNITS
STEP 2
Select the best outdoor unit based on the number of indoor units and overall system capacity required.
2-port
3-port
4-port
Connect up to 2 indoor units
Connect up to 3 indoor units
Connect up to 4 indoor units
MXY-2E20VA
MXY-3A28VA
MXY-4A28VA
MXY-4A38VA
CHECK SYSTEM COMPATIBILITY
STEP 3
Possible combinations depends on the outdoor unit chosen. Please check the following points.
Check Indoor Units
Refer to the “Indoor Unit Compatibility Table” to check if the indoor units selected can be used with the outdoor unit selected. (Indoor units not listed in the table cannot be used.)
Check Indoor Unit Capacity Combination
Refer to the “Combination Table” in data book to check if the capacity combination of the indoor unit selected is connectable. (Combinations not listed cannot be connected.)
If the desired combination cannot be found, please change either the indoor or outdoor unit to match one of the combinations shown in the tables.
15
16
MXY
MSY-E
SERIES
Our Inverter Technology adjusts capacity in response to conditions such as the difference between the outside and inside air temperatures, allowing our air conditioners to run more efficiently and reduce energy costs.
SERIES
MSY-EF10/13/18VAW
White
MSY-EF10/13/18VAS
Silver
MSY-EF10/13/18VAB
Black
Developed to complement modern interior room décor, StarMEX ZEN air conditioners are available in three colors specially chosen to blend in naturally wherever installed.
Stylish Line-up Matches Any Room Décor 2-port
3-port
MXY-2E20VA
The streamlined wall-mounted indoor units have eloquent silver-bevelled edges, expressing sophistication and quality. Combining impressively low power consumption and quiet yet powerful performance, these units provide a bestmatch scenario for diverse interior designs while simultaneeously ensuring maximum room and energy savings.
4-port
4-port
MXY-4A38VA
MXY-3A28VA MXY-4A28VA
EXAMPLE SYSTEM MSY-EF
MSY-GE
PLA-RP
Quiet Comfort All Day Long
Superior Exterior and Operating Design Concept
Mitsubishi Electric’s advanced “Silent Mode” fan speed setting provides super-quiet operation as low as 21dB for EF10/13 models. This unique feature makes the StarMEX ZEN series ideal for use in any situation.
The indoor unit of the StarMEX ZEN keeps its amazingly thin form even during operation. The only physical change notable is the movement of the variable vent. As a result, a slim attractive look is maintained.
● Noise Level
Closed
Human
Subway car interior
Quiet enger car interior (40km/h)
Library interior
80dB
60dB
40dB
Open
hearing limits Sound of rustling leaves (Extremely quiet)
MLZ-KA MXY-4A38VA
10dB
21dB
Only (for EF10/13 models)
Handle Up to 4 Rooms with a Single Outdoor Unit The MXY Series offers a four-system line-up to choose from, ranging between 5.0 and 9.2kW. All of them are compatible with specific M, S and P series indoor units. A single outdoor unit can handle a wide range of building layouts.
MXY SERIES
4A38
2A/3A
Built-in Weekly Timer Function Easily sets desired temperatures and operation start/stop times to match lifestyle patterns. Reduce wasted energy consumption by using the timer to prevent forgetting to turn off the unit and eliminate temperature setting adjustments.
3A/4A
Cooling Only MULTI
Type Model Name Power Supply (V/Phase/Hz) Cooling
Capacity Input Dimensions
Outdoor
Ext. Piping
Air Volume Sound Level (SPL) Breaker Size
MXY-2E20VA Rated Min - Max Rated H×W×D Weight Cooling Cooling
Liquid Diameter Gas Total Piping Length (max) Each Indoor Unit Piping Length Max. Height
kW kW kW mm kg m3/min dB(A) A mm mm m m m
5.0 1.10 - 6.55 1.44 550 - 800 - 285 38 31 49 15 6.35 × 2 9.52 × 2 30 20 15 (10)*
"Guaranteed Operating Cooling °C -10 ~ +46 Range(Outdoor)" *If the outdoor unit is installed higher than the indoor unit, max. height is reduced to 10m.
17
Inverter Cooling Only MXY-3A28VA MXY-4A28VA 230/Single/50 7.5 7.5 2.9 - 8.9 3.7 - 8.9 2.18 2.16 710 - 840 - 330 57 58 42.1 42.1 49 49 25 25 6.35 × 3 6.35 × 4 9.52 × 3 9.52 × 3 + 12.7 × 1 60 60 25 25 15 (10)* 15 (10)* -10 ~ +46
-10 ~ +46
MXY-4A38VA 9.2 3.7 - 11.2 2.45 900 - 900 - 320 67 42.2 46 25 6.35 × 4 9.52 × 3 + 12.7 × 1 70 25 15 (10)* -10 ~ +46
Electrostatic Anti-allergy
Nano Platinum
Optional
Optional
Optional
4A
Optional
Type Model Name Power Supply (V/Phase/Hz) Air Volume Silent-Lo-Mid-Hi-SHi* Cooling SPL Operating Current (max.) Demensions H×W×D Weight Diameter Ext.Piping *SHi : Super High
Liquid/Gas
MSY-EF10VAW/B/S 3
m /min dB(A) mm kg mm
4.0 - 4.6 - 6.3 - 8.3 - 10.5 21 - 23 - 29 - 36 - 42 0.14 299 - 895 - 195 11.5 6.35/9.52
Cooling Only MSY-EF13VAW/B/S Outdoor (230/Single/50) 4.0 - 4.6 - 6.3 - 8.3 - 10.5 21 - 24 - 29 - 36 - 42 0.14 299 - 895 - 195 11.5 6.35/9.52
MSY-EF18VAW/B/S 5.8 - 6.8 - 7.9 - 9.3 - 11.0 30 - 33 - 36 - 40 - 43 0.18 299 - 895 - 195 11.5 6.35/12.7
18
MSY-GE10/13/18VA
MLZ-KA25/35/50VA
MSY-G
MLZ
MSY-GE24/26VA
SERIES
The standard model MSY-G units provide excellent energy savings and operation is impressively silent. A vast series line-up is ready to ensure comfortable room environments in response to your air conditioning needs.
SERIES
Introducing a new type of ceiling cassette for the Multi-Split Series with streamed interior dimensions and a sharp, sleek appearance.
Ceiling Mounted
10/13 Only
Wide Line-up
Quiet Operation
Five different indoor units (Model 10-26) are available to meet your diversified air conditioning needs.
A “Silent Mode” setting has been added to the fan speed settings, ensuring super-quiet operation below 20dB for model sizes 13 and under. Perfect for the bedroom; it’s so quiet you’ll check to see if it’s on.
MSY-GE10/13/18VA
19dB
MSY-GE24/26VA 24/26
Stylish and Compact
Nano Platinum Filter
An elegant, high-quality look is achieved through the new stylish design adopted for indoor units. The simple ergonomic square shape and pure white color express a sense of sophistication that matches well with virtually any interior décor.
This filter incorporates nanometre-sized platinum-ceramic particles that generate stable antibacterial and deodourising effects. The size of the three-dimensional surface has been increased as well, enlarging the filter capture area. These features give the Nano Platinum Filter of the MSY-GE24/26 models better dust collection performance than conventional filters. The superior air-cleaning effectiveness raises room comfort yet another level.
Fits neatly above 800mm-wide doors.
MSY-GE10/13/18VA
800mm
Only 798mm
Nano Platinum
Slim Body
Access door not required
Installing the ceiling-mounted MLZ Series unit in a room creates a more spacious feel that enhances room comfort. This overhead format is also an excellent solution when lighting equipment is installed at the centre of the room and fixtures such as book shelves are mounted on wall surfaces.
The new units are designed with a slim body (only 175mm high), ensuring easy installation even when low ceiling cavities limit installation space. The need for ceiling cavity service space is also eliminated, further reducing the dimensions required for installation.
Air Volume Settings by Ceiling Height
Auto Vane Control
Dual-level airflow selection is engineered to accommodate specific ceiling heights. This is a key feature for adjusting airflow effectively when it is either too strong or too weak due to being mismatched with the height of the ceiling.
Outlet vanes can be moved left and right, and up and down using the remote controller. This improved airflow control feature solves the problem of drafts.
175mm
25
35
50
Standard
2.4m
2.4m
2.4m
High ceiling
2.7m
2.7m
2.7m
Left and Right Up and Down
Easy Installation A built-in drain pump (500mm lift) and flexible drain ts make attaching the drain hose in the ceiling cavity easy, resulting in simple and fast installation. Tight yet flexible fittings eliminate the need of wrapping with heat-insulation tape, and ensure that pipe and drain cover connections are free of condensation. ● Drain
In the case of MSY-GE10-18 It is okay to wash the filter with water (air-cleaning effect is maintained)
“i save” Mode “i save” is a simplified setting function that recalls the preferred (preset) temperature by pressing a single button on the remote controller. Press the same button twice in repetition to immediately return to the previous temperature setting. Using this function contributes to comfortable, waste-free operation, realizing the most suitable air conditioning settings and saving on power consumption when, for example, leaving the room or going to bed.
Easy t connections!
3D surface (Waved surface) 24/26*2
Cooling
Installation Example
Piping ers
Built-in drain pump secures drainage water lift of 500mm
Cooling
Insulation material pretreatment eliminates need for wrapping.
o
o
Refrigerant pipe
Insulating material wrapping only required from this point
24 c
22 c
Flexible drain ts
Flexible drain ts simplify drain piping work in narrow ceiling areas
The newly adopted insulation-free cover eliminates the need for wrapping pipes with insulation tape and prevents the forming of condensation.
Drain cover 10 - 18
24/26
10 - 18
24/26
24/26
24/26*1
24/26*2
Nano Platinum
Electrostatic Anti-allergy Optional
24/26
● Easy
Mounting Plate
Suspension work simplified with well-designed mounting plates
Optional
Secure one side
Push the unit to the other side Secure the opposite side
Move unit to the centre
4A
Optional
Optional
Optional Optional
Type Model Name
Power Supply (V/Phase/Hz) Air Silent-LoVolume Cooling Mid-Hi-SHi* SPL Operating Current (max.) Demensions H×W×D
MSY-GE10VA
MSY-GE13VA
Cooling Only MSY-GE18VA Outdoor (230/Single/50)
m3/min
4.2 - 4.9 - 6.7 - 8.9 - 11.4
4.2 - 4.9 - 6.7 - 9.2 - 12.8
6.5 - 7.8 - 9.6 - 11.8 - 15.1
N/A - 9.7 - 13.3 - 15.4 - 17.9
9.7 - 11.5 - 13.3 - 15.4 - 17.9
dB(A)
19 - 21 - 29 - 36 - 40 0.22 295 - 798 - 232 10 6.35/9.52
19 - 22 - 30 - 36 - 45 0.29 295 - 798 - 232 10 6.35/9.52
28 - 33 - 38 - 44 - 49 0.39 295 - 798 - 232 10 6.35/12.7
N/A - 30 - 40 - 45 - 49 0.55 325 - 1100 - 238 16 9.52/15.88
30 - 37 - 41 - 45 - 49 0.55 325 - 1100 - 238 16 9.52/15.88
mm kg mm
Weight Ext.Piping Diameter Liquid/Gas *SHi : Super High *1 Functions and specification may differ depending on the market. *2 Smart Set is available for MSY-GE10/13/18VA.
19
1
MSY-GE24VA*
MSY-GE26VA
Optional 4A
Type Model Name Power Supply (V/Phase/Hz) Air Volume Lo-Mid-Hi Cooling SPL Operating Current (max.) Demensions H×W×D
Weight Ext.Piping
Diameter
Liquid/Gas
Optional
m3/min dB(A) mm kg mm
Optional
Optional
MLZ-KA25VA
Cooling Only MLZ-KA35VA Outdoor (230/Single/50)
MLZ-KA50VA
7.2 - 8.0 - 8.8 29 - 32 - 35 0.4 175 - 1102 - 360 15 6.35/9.52
7.3 - 8.4 - 9.4 31 - 34 - 37 0.4 175 - 1102 - 360 15 6.35/9.52
8.3 - 9.8 - 11.4 34 - 38 - 43 0.4 175 - 1102 - 360 15 6.35/12.7
20
PLA-RP50/60/71 MLZ-KA25/35/50VA
SEZ
PLA MLZ
SERIES SERIES
Slim Body
Access door not required
Installing the ceiling-mounted MLZ Series unit in a room creates a more spacious feel that enhances room comfort. This overhead format is also an excellent solution when lighting equipment is installed at the centre of the room and fixtures such as book shelves are mounted on wall surfaces. Individual Vane Settings Optimum airflow settings provide maximum comfort throughout the room.
The new units are designed with a slim body (only 175mm high), ensuring easy installation even when low ceiling cavities limit installation space. The need for ceiling cavity service space is also eliminated, further reducing the dimensions required for installation.
175mm
Optimum Airflow
Wide Airflow Wide-angle outlets distribute airflow to all corners of the room.
Air Volume Settings by Ceiling Height
Auto Vane Control
Standard
25
35
50
2.4m
2.4m
2.4m
2.7m
2.7m New 4-Way Ceiling Cassette
Horizontal
2.7m
AirflowHigh direction at ceiling each vane can be set using the wired remote controller.
Setting
Wide Airflow
The combination of individual vane setting, which enables the optimal outlet setting for each room layout, and the wide airflow function works to ensure even temperature distribution throughout each room. The result is uniformly comfortable air conditioning.
72 airflow patterns
A built-in drain pump (500mm lift) and flexible drain ts make attaching the drain hose in the ceiling cavity easy, resulting in simple and fast installation. Tight yet flexible fittings eliminate the need of wrapping with heat-insulation tape, and ensure that pipe and drain cover connections are free of condensation.
The New Swing Function Cools All Corners of the Room ● Drain
Installation Example
Piping ers
Wave Airflow Operation Easy t “Wave Airflow” is essentially the advanced control of the vanes connections! drain ts directing the airflow from the unit. Blown-air is repeatedFlexible dispersed Built-in drain pump from the unit in horizontal and downward directions at time-lagged secures drainage waterto liftprovide of 500mm intervals uniform heating throughout theInsulating room. material wrapping only required from this point
Thermograph of Wave Control Effect
Refrigerant pipe
Downward
Horizontal Airflow Wave Airflow Insulation material pretreatment eliminates need for wrapping.
Indoor Unit
Indoor Unit
Downward
Temperature gap Uneven temperature distribution
● Easy
Mounting Plate
Minimized temperature gap Uniform cool air is supplied throughout the room, minimizing uneven temperature distribution.
Suspension work simplified with well-designed mounting plates
Wide Selection of Fan Speed and Static Pressure Level Three fan speeds (Low - Mid - High) and four static pressure levels (5 - 15 - 35 - 50Pa) are available by using the DC fan motor to meet various needs.
Drain Pump (Optional) The PAC-KE07DM-E drain pump is now available as an option. With the pump, a drain hose length of up to 550mm can be used, leading to increased installation possibilities.
Flexible drain ts simplify drain piping work in narrow ceiling areas
The newly adopted insulation-free cover eliminates the need for wrapping pipes with insulation tape and prevents the forming of condensation.
Drain cover
Downward Downward
✽ Vertical swinging mode is adapted in the case of cooling operation
Air inlet Air outlet Access door Ceiling surface Canvas duct Air filter Inlet grille
SEZ-KD35VAL
Up and Down
Downward
A B C D E F G
200
Individual Vane Left and Right
Fixed
Adjustable
Easy Installation
990
Dimension
moved left and right, and up and down using the remote controller. This improved Previous airflow control model the problem of feature solves drafts.
ceiling heights. This is a key feature for adjusting airflow effectively when it is either too strong or too weak due to being mismatched 2-, 3-, 4-way airflow patternthe selection with height of the ceiling.
Compact Ceiling-concealed Units Only the intake-air grille and outlet vents are visible when using this ceiling-concealed indoor unit. The rest of the unit is conveniently hidden in the ceiling cavity, essentially leaving the ceiling and walls free of bulky looking devices and maintaining a high-class interior décor. The compact units require minimal space and can be installed in buildings with lowered ceilings, where exposed units were the rule in the past.
Image of multi-directional air conditioning
In addition to the selection of variable airflow patterns (i.e., 2-, The outlets are larger than those of previous 3- or 4-way), this function allows the independent selection of models and the shape has been improved for vertical airflow levels for selection each vane, thereby maintaining combetter wide-angle ventilation. Dual-level airflow is engineered toa accommodate specific Outlet vanes can be fortable room environment with even temperature distribution.
* Optional shuffle placement is required for 2- and 3-way patterns.
SEZ-KD25-71VAL
This concealed ceiling-mounted indoor unit series is compact, and fits easily into rooms with lowered ceilings. Highly reliable energy-saving performance makes it a best match choice for concealed unit installations.
The Introducing incorporation a new of wide type air-outlet of ceilingand cassette the “i-see for Sensor” the Multi-Split enhances Series airflow with distribution streamed control, interiorachieving dimensions an enhanced and a sharp, levelsleek of comfort appearance. throughout the room. The synergy of higher energy efficiency and more comfortable room environment results in the utmost satisfaction.
Ceiling Mounted
SERIES
Secure one side
Temperature distribution comparison approximately 20min after turning on a PLA-RP71BA 4-Way ceiling cassette. The measurement point for comparison is a plane 1.2m above the floor.
Push the unit to the other side Secure the opposite side
Move unit to the centre 4A
Optional 4A
Optional Optional
Optional
Type Model Name Power Supply (V/Phase/Hz) Air Volume Lo-Mid2Cooling Mid1-Hi SPL Operating Current (max.) Demensions H×W×D Weight Ext.Piping
21
Diameter
Liquid/Gas
m3/min dB(A) mm kg mm
PLA-RP50BA
Cooling Only PLA-RP60BA Outdoor (230/Single/50)
PLA-RP71BA
12.0 - 14.0 - 16.0 - 18.0 28 - 29 - 31 - 32 0.36 258 - 840 - 840 22 6.35/12.7
12.0 - 14.0 - 16.0 - 18.0 28 - 29 - 31 - 32 0.36 258 - 840 - 840 23 6.35·9.52/15.88
14.0 - 16.0 - 18.0 - 21.0 28 - 30 - 32 - 34 0.51 258 - 840 - 840 23 9.52/15.88
Type Model Name Power Supply (V/Phase/Hz) Air Volume Lo-Mid-Hi Cooling SPL Operating Current (max.) Demensions H×W×D Weight Liquid/Gas Ext.Piping Diameter External Static Pressure
Optional
m3/min dB(A) mm kg mm
Optional
SEZ-KD25VAL
SEZ-KD35VAL
Cooling Only SEZ-KD50VAL Outdoor (230/Single/50)
SEZ-KD60VAL
SEZ-KD71VAL
5.5 - 7.0 - 9.0 23 - 26 - 30 0.39 200 - 790 - 700 18 6.35/9.52 5/15/35/50
7.0 - 9.0 - 11.0 23 - 28 - 33 0.46 200 - 990 - 700 21 6.35/9.52 5/15/35/50
10.0 - 12.5 - 15.0 30 - 34 - 37 0.63 200 - 990 - 700 23 6.35/12.7 5/15/35/50
12.0 - 15.0 - 18.0 30 - 34 - 38 0.63 200 - 1190 - 700 27 6.35/15.88 5/15/35/50
12.0 - 16.0 - 20.0 30 - 35 - 40 0.84 200 - 1190 - 700 27 9.52/15.88 5/15/35/50
22
Indoor Unit Compatibility Table Possible combinations of outdoor units and indoor units are shown below. Outdoor Unit
MXY2E20VA
Indoor Unit
3A28VA
4A28VA
4A38VA
MSY-EF10VA
Wall-mounted
MSY-EF13VA
MSY-EF18VA
MSY-EF
MSY-GE10VA
MSY-GE13VA MSY-GE(10-18)
MSY-GE18VA
MSY-GE(24-26)
MSY-GE24VA
MSY-GE26VA
1-way cassette
MLZ-KA25VA
MLZ-KA35VA
MLZ Series
4-way cassette
MLZ-KA50VA
PLA-RP50BA
PLA-RP60BA
PLA Series
Ceiling-concealed
PLA-RP71BA
SEZ-KD35VAL
SEZ-KD50VAL
SEZ-KD60VAL
SEZ Series
SEZ-KD71VAL
23
24
MXZ
SELECTION Choose from three types of indoor units and five types of outdoor units. Create the system that best matches the room shapes and the number of rooms.
STEP 1
SELECT INDOOR UNITS Select the indoor unit to be installed in each room.
Wall-mounted
Cassette
Ceiling-concealed
SERIES MSZ-EF
MSZ-GE(25/35/50)
MLZ-KA
PLA-RP
SEZ-KD
MSZ-GE(60/71)
SELECT OUTDOOR UNITS
STEP 2
Select the best outdoor unit based on the number of indoor units and overall system capacity required.
2-port
3-port
4-port
Connect up to 2 indoor units
Connect up to 3 indoor units
Connect up to 4 indoor units
MXZ-2C52VA
5-port
MXZ-3C68VA
Connect up to 5 indoor units
MXZ-4C71VA
6-port
MXZ-4C80VA
Connect up to 6 indoor units
MXZ-5C100VA
MXZ-6C120VA
CHECK SYSTEM COMPATIBILITY
STEP 3
Possible combinations depends on the outdoor unit chosen. Please check the following points.
Check Indoor Units
Refer to the “Indoor Unit Compatibility Table” to check if the indoor units selected can be used with the outdoor unit selected. (Indoor units not listed in the table cannot be used.)
Check Indoor Unit Capacity Combination
Refer to the “Combination Table” in data book to check if the capacity combination of the indoor unit selected is connectable. (Combinations not listed cannot be connected.)
If the desired combination cannot be found, please change either the indoor or outdoor unit to match one of the combinations shown in the tables.
25
26
MXZ
MSZ-E
SERIES
SERIES
MSZ-EF25/35/50VEW
White
MSZ-EF25/35/50VES
Silver
MSZ-EF25/35/50VEB
Black
Developed to complement modern interior room décor, Kirigamine ZEN air conditioners are available in three colors specially chosen to blend in naturally wherever installed.
Advancements in the MXZ Series include efficiency and flexibility in system expansion capabilities. The best solution when requiring multi-system air conditioning needs.
Stylish Line-up Matches Any Room Décor
2-port
3-port
MXZ-2C52VA
4-port
4-port
5-port
6-port
MXZ-4C80VA MXZ-5C100VA
MXZ-3C68VA MXZ-4C71VA
The streamlined wall-mounted indoor units have eloquent silver-bevelled edges, expressing sophistication and quality. Combining impressively low power consumption and quiet yet powerful performance, these units provide a bestmatch scenario for diverse interior designs while simultaneeously ensuring maximum room and energy savings
MXZ-6C120VA
EXAMPLE SYSTEM MSZ-EF
(example of MXZ-6C120VA system)
MSZ-GE
Quiet Comfort All Day Long
Superior Exterior and Operating Design Concept
Mitsubishi Electric’s advanced “Silent Mode” fan speed setting provides super-quiet operation as low as 21dB for EF25/35 models. This unique feature makes the Kirigamine ZEN series ideal for use in any situation.
The indoor unit of the Kirigamine ZEN keeps its amazingly thin form even during operation. The only physical change notable is the movement of the variable vent. As a result, a slim attractive look is maintained.
● Noise Level
MSZ-GE
Closed
Human
Subway car interior
Quiet enger car interior (40km/h)
Library interior
80dB
60dB
40dB
Open
hearing limits Sound of rustling leaves (Extremely quiet)
MLZ-KA
10dB
21dB
Only (for EF25/35 models)
PLA-BA MXZ-6C120VA
Built-in Weekly Timer Function
SEZ-KD
Handle Up to 6 Rooms with a Single Outdoor Unit The MXZ Series offers a six-system line-up to choose from, ranging between 5.2 and 12.0kW. All of them are compatible with specific M, S and P series indoor units. A single outdoor unit can handle a wide range of building layouts.
MXZ SERIES
4C80-6C
2C/3C/4C
Easily sets desired temperatures and operation start/stop times to match lifestyle patterns. Reduces wasted energy consumption by using the timer to prevent forgetting to turn off the unit and eliminate temperature setting adjustments. ● Easy Set-up Using Dedicated Buttons
The remote controller is equipped with buttons that are used exclusively for setting the Weekly Timer. Setting operation patterns easy and quick.
3C - 6C
INVERTER MULTI
Type Model Name Power Supply (V/Phase/Hz) Rated Capacity Min - Max Cooling Rated Input Rated Capacity Min - Max Heating Rated Input H×W×D Dimensions Weight Cooling Air Volume Heating Outdoor
MXZ-2C52VA kW kW kW kW kW kW mm kg m3/min m3/min
5.2 1.1 - 6.0 1.3 6.4 1.0 - 7.0 1.61 550 - 800 - 285 38 32.9
33.3 dB(A) 49 Sound Level Cooling (SPL) Heating dB(A) 50 A 15 Breaker Size Liquid mm 6.35 × 2 Diameter Gas mm 9.52 × 2 Ext. m 30 Total Piping Length (max) Piping m 20 Each Indoor Unit Piping Length m 15 (10)* Max. Height °C -10 ~ +43 "Guaranteed Operating Cooling Range(Outdoor)" Heating °C -15 ~ +24 * If the outdoor unit is installed higher than the indoor unit, max.height is reduced to 10m.
27
Inverter Heat Pump MXZ-4C71VA MXZ-4C80VA MXZ-5C100VA 230/Single/50 6.8 7.1 8.0 10.0 2.9 - 8.4 3.7 - 8.8 3.7 - 9.2 3.9 - 11.0 1.78 1.68 1.955 2.80 8.6 8.6 9.4 12.0 2.6 - 10.6 3.4 - 10.7 3.4 - 11.6 4.1 - 14.0 2.05 1.71 1.93 2.84 710 - 840 - 330 900 - 900 - 320 57 58 67 68 42.1 42.1 42.1 56.6
MXZ-3C68VA
43 48 52 25 6.35 × 3 9.52 × 3 60 25 15 (10)* -10 ~ +43 -15 ~ +24
43 48 52 25 6.35 × 4 9.52 × 3 + 12.7 × 1 60 25 15 (10)* -10 ~ +43 -15 ~ +24
43.8 46 48 25 6.35 × 4 9.52 × 3 + 12.7 × 1 70 25 15 (10)* -10 ~ +43 -15 ~ +24
59.3 51 54 25 6.35 × 5 9.52 × 4 + 12.7 × 1 80 25 15 (10)* -10 ~ +43 -15 ~ +24
A maximum of 4ON or OFF timers can be set for individual days of the week A maximum of 28 ON or OFF timers can be set for a week.
Setting
E.g. : Runs at 24°C from waking up to leaving home, and runs at 27°C from getting home to going to bed on weekdays. Runs at 27°C from waking up late to going bed early on weekends Mon
Setting1 ON
Fri
6:00
Sat Sun
MXZ-6C120VA 12.0 3.5 - 13.5 3.61 14.0 3.5 - 16.5 3.47 1070 - 900 - 320 88 55.4 69.9 55 57 32 6.35 × 6 9.52 × 5 + 12.7 × 1 80 25 15 (10)* -10 ~ +43 -15 ~ +24
Electrostatic Anti-allergy
24°C
Setting2 OFF
8:30 Setting1 ON
Setting3 ON
27°C
17:30
Setting4 OFF 22:00 Setting2 OFF
27°C
8:00
21:00
Nano Platinum
Optional
Optional
4C/5C/6C
Optional
4C/5C/6C
Optional
Type Model Name Power Supply (V/Phase/Hz) Air Volume Cooling SPL Air Volume Heating SPL Operating Current (max.) H×W×D Demensions Weight Diameter Ext.Piping *SHi : Super High
3
m /min Silent-Lo-Mid-Hi-SHi* m3/min Silent-Lo-Mid-Hi-Shi*
dB(A) dB(A)
Liquid/Gas
mm kg mm
MSZ-EF25VEW/B/S
Inverter Heat Pump MSZ-EF35VEW/B/S Outdoor (230/Single/50)
MSZ-EF50VEW/B/S
4.0 - 4.6 - 6.3 - 8.3 - 10.5 21 - 23 - 29 - 36 - 42 4.0 - 4.6 - 6.2 - 8.9 - 11.9 21 - 24 - 29 - 37 - 45 0.3 299 - 895 - 195 11.5 6.35/9.52
4.0 - 4.6 - 6.3 - 8.3 - 10.5 21 - 24 - 29 - 36 - 42 4.0 - 4.6 - 6.2 - 8.9 - 12.7 21 - 24 - 30 - 38 - 46 0.3 299 - 895 - 195 11.5 6.35/9.52
5.8 - 6.8 - 7.9 - 9.3 - 11.0 30 - 33 - 36 - 40 - 43 6.4 - 7.3 - 9.0 - 11.1 - 13.2 30 - 33 - 37 - 43 - 49 0.4 299 - 895 - 195 11.5 6.35/12.7
28
MSZ-GE25/35/50VA
MLZ-KA25/35/50VA
MSZ-G
MLZ
MSZ-GE60/71VA
SERIES
The standard model MSZ-G units provide excellent energy savings and operation is impressively silent. A vast series line-up is ready to ensure comfortable room environments in response to your air conditioning needs.
SERIES
Introducing a new type of ceiling cassette for the Multi-Split Series with streamed interior dimensions and a sharp, sleek appearance.
Ceiling Mounted 25-35 Only
Wide Line-up
Quiet Operation
Five different indoor units (Model 25-71) are available to meet your diversified air conditioning needs.
A “Silent Mode” setting has been added to the fan speed settings, ensuring super-quiet operation below 20dB for model sizes 35 and under. Perfect for the bedroom; it’s so quiet you’ll check to see if it’s on.
MSZ-GE25/35/50VA
19dB
MSZ-GE60/71VA
Installing the ceiling-mounted MLZ Series unit in a room creates a more spacious feel that enhances room comfort. This overhead format is also an excellent solution when lighting equipment is installed at the centre of the room and fixtures such as book shelves are mounted on wall surfaces.
The new units are designed with a slim body (only 175mm high), ensuring easy installation even when low ceiling cavities limit installation space. The need for ceiling cavity service space is also eliminated, further reducing the dimensions required for installation.
Air Volume Settings by Ceiling Height
Auto Vane Control
Dual-level airflow selection is engineered to accommodate specific ceiling heights. This is a key feature for adjusting airflow effectively when it is either too strong or too weak due to being mismatched with the height of the ceiling.
Outlet vanes can be moved left and right, and up and down using the remote controller. This improved airflow control feature solves the problem of drafts.
175mm
60/71
Stylish and Compact
Nano Platinum Filter
An elegant, high-quality look is achieved through the new stylish design adopted for indoor units. The simple ergonomic square shape and pure white color express a sense of sophistication that matches well with virtually any interior décor.
This filter incorporates nanometre-sized platinum-ceramic particles that generate stable antibacterial and deodourising effects. The size of the three-dimensional surface has been increased as well, enlarging the filter capture area. These features give the Nano Platinum Filter of the MSZ-GE60/71 models better dust collection performance than conventional filters. The superior air-cleaning effectiveness raises room comfort yet another level.
Fits neatly above 800mm-wide doors.
MSZ-GE25/35/50VA
Slim Body
Access door not required
800mm
Only 798mm
Nano Platinum
25
35
50
Standard
2.4m
2.4m
2.4m
High ceiling
2.7m
2.7m
2.7m
Left and Right Up and Down
Easy Installation
In the case of MSZ-GE25-50 It is okay to wash the filter with water (air-cleaning effect is maintained)
3D surface (Waved surface)
“i save” Mode
A built-in drain pump (500mm lift) and flexible drain ts make attaching the drain hose in the ceiling cavity easy, resulting in simple and fast installation. Tight yet flexible fittings eliminate the need of wrapping with heat-insulation tape, and ensure that pipe and drain cover connections are free of condensation. ● Drain
“i save” is a simplified setting function that recalls the preferred (preset) temperature by pressing a single button on the remote controller. Press the same button twice in repetition to immediately return to the previous temperature setting. Using this function contributes to comfortable, waste-free operation, realizing the most suitable air conditioning settings and saving on power consumption when, for example, leaving the room or going to bed.
Heating
Heating
18 c
22 c
o
o
Installation Example
Piping ers Easy t connections!
Built-in drain pump secures drainage water lift of 500mm
Flexible drain ts
Refrigerant pipe
Insulating material wrapping only required from this point Insulation material pretreatment eliminates need for wrapping.
Flexible drain ts simplify drain piping work in narrow ceiling areas
The newly adopted insulation-free cover eliminates the need for wrapping pipes with insulation tape and prevents the forming of condensation.
Drain cover 25 - 50
60/71
25 - 50
60/71
60/71
60/71
Optional
Weight Ext.Piping Diameter *SHi : Super High
29
Liquid/Gas
4C/5C/6C
Secure one side
Push the unit to the other side Secure the opposite side
Move unit to the centre
4C/5C/6C
Optional
Type Model Name Power Supply (V/Phase/Hz) Air Silent-LoVolume Cooling Mid-Hi-SHi* SPL Air Silent-LoVolume Heating Mid-Hi-Shi* SPL Operating Current (max.) Demensions H×W×D
Mounting Plate
Suspension work simplified with well-designed mounting plates
Optional 4C/5C/6C
Optional
● Easy
Nano Platinum
Electrostatic Anti-allergy Optional
60/71
m3/min dB(A) m3/min dB(A) mm kg mm
MSZ-GE25VA
MSZ-GE35VA
Inverter Heat Pump MSZ-GE50VA Outdoor (230/Single/50)
MSZ-GE60VA
MSZ-GE71VA
4.1 - 4.8 - 6.7 - 9.1 - 11.3
4.1 - 4.8 - 6.7 - 9.1 - 12.7
6.5 - 7.8 - 9.6 - 11.9 - 15.1
9.8 - 11.3 - 13.4 - 15.6 - 18.3
9.7 - 11.5 - 13.3 - 15.4 - 17.8
19 - 21 - 29 - 36 - 42
19 - 22 - 30 - 36 - 43
28 - 33 - 38 - 44 - 49
29 - 37 - 41 - 45 - 49
30 - 37 - 41 - 45 - 49
4.1 - 4.8 - 6.6 - 9.1 - 11.5
4.1 - 4.8 - 6.7 - 9.1 - 11.5
6.5 - 7.9 - 9.6 - 12.2 - 14.5
9.8 - 11.3 - 13.4 - 15.6 - 18.3
10.2 - 11.5 - 13.3 - 15.4 - 17.8
19 - 21 - 29 - 36 - 42 0.4 295 - 798 - 232 10 6.35/9.52
19 - 22 - 30 - 36 - 42 0.4 295 - 798 - 232 10 6.35/9.52
28 - 33 - 37 - 43 - 48 0.5 295 - 798 - 232 10 6.35/12.7
29 - 37 - 41 - 45 - 49 0.5 325 - 1100 - 238 16 6.35/15.88
30 - 37 - 41 - 45 - 49 0.5 325 - 1100 - 238 16 9.52/15.88
Optional
Optional
Optional
Optional
Optional
4C/5C/6C
Type Model Name Power Supply (V/Phase/Hz) Air Volume Lo-Mid-Hi Cooling SPL Air Volume Lo-Mid-Hi Heating SPL Operating Current (max.) Demensions H×W×D
Weight Ext.Piping
Diameter
3
m /min dB(A) m3/min dB(A)
mm kg Liquid/Gas mm
MLZ-KA25VA
Inverter Heat Pump MLZ-KA35VA Outdoor (230/Single/50)
MLZ-KA50VA
7.2 - 8.0 - 8.8 29 - 32 - 35 7.0 - 8.2 - 9.2 28 - 32 - 36 0.4 175 - 1102 - 360 15 6.35/9.52
7.3 - 8.4 - 9.4 31 - 34 - 37 7.7 - 8.8 - 9.9 31 - 35 - 38 0.4 175 - 1102 - 360 15 6.35/9.52
8.3 - 9.8 - 11.4 34 - 38 - 43 8.8 - 10.3 - 11.8 34 - 39 - 43 0.4 175 - 1102 - 360 15 6.35/12.7
30
PLA-RP50/60/71 MLZ-KA25/35/50VA
SEZ
PLA MLZ
SERIES SERIES
Slim Body
Access door not required
Installing the ceiling-mounted MLZ Series unit in a room creates a more spacious feel that enhances room comfort. This overhead format is also an excellent solution when lighting equipment is installed at the centre of the room and fixtures such as book shelves are mounted on wall surfaces. Vane Settings Individual
The new units are designed with a slim body (only 175mm high), ensuring easy installation even when low ceiling cavities limit installation space. The need for ceiling cavity service space is also eliminated, further reducing the dimensions required for installation.
175mm
Optimum Airflow
Wide Airflow Wide-angle outlets distribute airflow to all corners of the room.
Optimum airflow settings provide maximum comfort throughout the room.
Air Volume Settings by Ceiling Height
Auto Vane Control
ceiling heights. This is a key feature for adjusting airflow effectively when it isairflow either too strong or too weak due to being mismatched 2-, 3-, 4-way patternthe selection with height of the ceiling.
moved left and right, and up and down using the remote controller. This improved airflow Previous control feature solves themodel problem of drafts.
Standard AirflowHigh direction at ceiling each vane can be set using the wired remote controller.
25
35
50
2.4m
2.4m
2.4m
2.7m
2.7m
2.7m
Horizontal
Adjustable
Easy Installation
New 4-Way Ceiling Cassette
Setting
Wide Airflow
The setting, which enables the optimal outlet setting for each room layout, and the wide airflow function works to ensure even temperature distribution throughout each room. The result is uniformly comfortable air conditioning.
72 airflow patterns
Wave Airflow – Thoroughly Warming All Corners of the Room!
Refrigerant pipe
Downward
Horizontal Airflow Wave Airflow Insulation material pretreatment eliminates need for wrapping.
Indoor Unit
Indoor Unit
Downward
Temperature gap Uneven temperature distribution
Drain cover
Downward Downward
✽ Wave Airflow is possible only when using the heating mode
SEZ-KD35VAL
Wide Selection of Fan Speed and Static Pressure Level Three fan speeds (Low - Mid - High) and four static pressure levels (5 - 15 - 35 - 50Pa) are available by using the DC fan motor to meet various needs.
Drain Pump (Optional) The PAC-KE07DM-E drain pump is now available as an option. With the pump, a drain hose length of up to 550mm can be used, leading to increased installation possibilities.
Flexible drain ts simplify drain piping work in narrow ceiling areas
The newly adopted insulation-free cover eliminates the need for wrapping pipes with insulation tape and prevents the forming of condensation.
● Easy
Installation Example
Piping ers
only required from this point
Air inlet Air outlet Access door Ceiling surface Canvas duct Air filter Inlet grille
Up and Down combination of individual vane
Downward
Thermograph of Wave Control Effect
A B C D E F G
200
A built-in drain pump (500mm lift) and flexible drain ts make attaching the drain hose in the ceiling cavity easy, resulting in simple and fast installation. Tight yet flexible fittings eliminate the need of wrapping with heat-insulation tape, and ensure that pipe and drain cover connections are free of condensation.
● Drain
990
Dimension
Individual Vane Left and Right
Fixed
Wave Airflow Operation “Wave Airflow” is essentially the advanced control of the vanes Easy t drain ts directing the airflow from theconnections! unit. Blown-air is repeatedFlexible dispersed Built-in drain pump from the unit in horizontal and downward directions at time-lagged secures drainage intervals uniform heating throughout theInsulating room. material wrapping waterto liftprovide of 500mm
Compact Ceiling-concealed Units Only the intake-air grille and outlet vents are visible when using this ceiling-concealed indoor unit. The rest of the unit is conveniently hidden in the ceiling cavity, essentially leaving the ceiling and walls free of bulky looking devices and maintaining a high-class interior décor. The compact units require minimal space and can be installed in buildings with lowered ceilings, where exposed units were the rule in the past.
Image of multi-directional air conditioning
In addition to the selection of variable airflow patterns (i.e., 2-, The outlets are larger than those of previous 3- or 4-way), this function allows the independent selection of models and the shape has been improved for vertical airflow levels for selection each vane, thereby maintaining combetter wide-angle ventilation. Dual-level airflow is engineered toa accommodate specific Outlet vanes can be fortable room environment with even temperature distribution.
* Optional shuffle placement is required for 2- and 3-way patterns.
SEZ-KD25-71VAL
This concealed ceiling-mounted indoor unit series is compact, and fits easily into rooms with lowered ceilings. Highly reliable energy-saving performance makes it a best match choice for concealed unit installations.
The Introducing incorporation a new of wide type air-outlet of ceilingand cassette the “i-see for Sensor” the Multi-Split enhances Series airflow with distribution streamed control, interiorachieving dimensions an enhanced and a sharp, levelsleek of comfort appearance. throughout the room. The synergy of higher energy efficiency and more comfortable room environment results in the utmost satisfaction.
Ceiling Mounted
SERIES
Minimized temperature gap Warm air is supplied throughout the room, minimizing uneven temperature distribution.
Temperature distribution comparison approximately 20min after turning on a PLA-RP71BA 4-Way ceiling cassette. The measurement point for comparison is a plane 1.2m above the floor.
Mounting Plate
Suspension work simplified with well-designed mounting plates
Secure one side
Push the unit to the other side Secure the opposite side
Move unit to the centre
Optional 4C/5C/6C
4C/5C/6C
Optional
Optional
Type Model Name Power Supply (V/Phase/Hz) Heating and Air Volume Lo-Mid2-Mid1-Hi Cooling SPL Operating Current (max.) H×W×D Demensions Weight Diameter Liquid/Gas Ext.Piping
31
4C/5C/6C
Optional
m3/min dB(A) mm kg mm
PLA-RP50BA
Inverter Heat Pump PLA-RP60BA Outdoor (230/Single/150)
PLA-RP71BA
12.0 - 14.0 - 16.0 - 18.0 28 - 29 - 31 - 32 0.36 258 - 840 - 840 22 6.35/12.7
12.0 - 14.0 - 16.0 - 18.0 28 - 29 - 31 - 32 0.36 258 - 840 - 840 23 6.35·9.52/15.88
14.0 - 16.0 - 18.0 - 21.0 28 - 30 - 32 - 34 0.51 258 - 840 - 840 23 9.52/15.88
Type Model Name Power Supply (V/Phase/Hz) Heating and Air Volume Lo-Mid-Hi Cooling SPL Operating Current (max.) H×W×D Demensions Weight Diameter Ext.Piping External Static Pressure
Liquid/Gas
m3/min dB(A) mm kg mm
Optional
4C/5C/6C
Optional
SEZ-KD25VAL
SEZ-KD35VAL
Inverter Heat Pump SEZ-KD50VAL Outdoor (230/Single/50)
SEZ-KD60VAL
SEZ-KD71VAL
5.5 - 7.0 - 9.0 23 - 26 - 30 0.39 200 - 790 - 700 18 6.35/9.52 5/15/35/50
7.0 - 9.0 - 11.0 23 - 28 - 33 0.46 200 - 990 - 700 21 6.35/9.52 5/15/35/50
10.0 - 12.5 - 15.0 30 - 34 - 37 0.63 200 - 990 - 700 23 6.35/12.7 5/15/35/50
12.0 - 15.0 - 18.0 30 - 34 - 38 0.63 200 - 1190 - 700 27 6.35/15.88 5/15/35/50
12.0 - 16.0 - 20.0 30 - 35 - 40 0.84 200 - 1190 - 700 27 9.52/15.88 5/15/35/50
32
Indoor Unit Compatibility Table Possible combinations of outdoor units and indoor units are shown below. Outdoor Unit Indoor Unit MSZ-EF25VE
Wall-mounted
MSZ-EF35VE
MSZ-EF50VE MSZ-EF
MSZ-GE25VA
MSZ-GE35VA MSZ-GE(25/35/50)
MSZ-GE50VA
MSZ-GE60VA MSZ-GE(60/71)
MSZ-GE71VA
1-way cassette
MLZ-KA25VA
MLZ-KA35VA
MLZ Series
4-way cassette
MLZ-KA50VA
PLA-RP50BA
PLA-RP60BA
PLA Series
Ceiling-concealed
PLA-RP71BA
SEZ-KD25VAL
SEZ-KD35VAL
SEZ-KD50VAL
SEZ Series
SEZ-KD60VAL
SEZ-KD71VAL
33
MXZ2C52VA
3C68VA
4C71VA
4C80VA
5C100VA
6C120VA
External Dimensions Wall-Mounted MSY-EF10VA MSY-EF13VA MSY-EF18VA MSZ-EF25VE MSZ-EF35VE MSZ-EF50VE
Unit : mm
MSY-GE10VA MSY-GE13VA MSY-GE18VA MSZ-GE25VA MSZ-GE35VA MSZ-GE50VA INDOOR UNIT
INDOOR UNIT 895 875
798 785
10
6.5
Air in Installation plate
Air in 232
299
Piping
5
Air out
50
619
42
130
Drain hose
107
Air out
112
19
159
58
56 69
18
193
60
Drain hose
8
94 110
(80)
100
158
295
678
58
7
Piping
47
100
59
Installation plate
MSY-GE24VA MSY-GE26VA MSZ-GE60VA MSZ-GE71VA INDOOR UNIT
1100 1090
5
238 Air in Installation plate Piping
843
181
Air out
125 160 184
Drain hose
18
193
60
65 ( 70 )
3
76
100
12
67
325
5
34
Light weight
By the entrance
Easy to transport and install at site.
On the balcony
Light and easy to carry Welc om
e
Easy to transport by elevator
SERIES
Flexible choice and suitable for the limited outdoor space.
Smaller footprint 8HP
New S series
8HP Extended residence space.
Advanced Energy-saving Technologies
S series
PUMY-P VKM PUMY-P YKM
Highly efficient fan and grille for outdoor unit The shapes of the fan and grille of the outdoor unit have been redesigned, realising an increase in blowing capacity and more efficient heat exchange while maintaining the same operating noise level.
Outdoor unit fan opening increased 4HP x 2units
8HP x 1units
New S series can maximize residential area.
The two-pipe zoned system designed for Heat Pump Operation The CITY MULTI S series make use of a two-pipe refrigerant system, which allows for system changeover from cooling to heating, ensuring that a constant indoor climate is maintained in all zones. The compact outdoor unit utilizes R410A refrigerant and an INVERTER-driven compressor to use energy effectively. With a wide range of indoor unit line-up in connection with a flexible piping system, the CITY MULTI series can be configured for all applications. Up to 12 indoor units can be connected with up to 130% connected capacity to maximize engineer's design options. This feature allows easy air conditioning in each area with convenient individual controllers.
The diameter of the opening for the fan in the outdoor unit has been increased from 490 to 550mm. Blowing capacity has been increased while maintaining the same fan rotation speed.
Opening increased from 490 to 550mm in diameter
Grille shape changed
Inflexed fan
The shape of the air outlet grille has been c h a n g e d to r e d u c e pressure l o s s. T h i s has helped to improve heat exchange performance.
Adoption of a fan with improved ventilation characteristics and a newly designed rear edge that suppresses wind turbulence raises fan operation efficiency.
PUMY-P V/YHMB
Fan rear edge
PUMY-P V/YKM
Highly efficient heat exchanger A high density and increase in surface area have improved the heat-exchange efficiency of the heat exchanger. Outdoor unit
[P112~140(V/YKM)]
Residence
Refrigerant Piping Lengths
Maximum meters
Total length Maximum allowable length Farthest indoor from first branch
300 150 (175 equivalent) 30
Vertical differentials between units
Maximum meters
Indoor/outdoor (outdoor higher) Indoor/outdoor (outdoor lower) Indoor/indoor
50 40 15
Furthest piping length 175m (equivalent length) (actual length 150m)
Top-bottom differential 50m
Between indoor units top-bottom differential 15m
High-density heat exchanger
Outdoor unit
Outdoor unit
Silent mode can reduce sound pressure level by 3dB(A)
Maximum meters
Total length Maximum allowable length Farthest indoor from first branch
150 80 (90 equivalent) 30
Vertical differentials between units
Maximum meters
Indoor/outdoor (outdoor higher) Indoor/outdoor (outdoor lower) Indoor/indoor
50 40 15
Furthest piping length 90m (equivalent length) (actual length 80m)
Top-bottom differential 50m
Between indoor units top-bottom differential 15m
Indoor unit
Heat exchanger
A HIC circuit has been added to improve energy efficiency during cooling operation. Liquid refrigerant is rerouted, transformed into a gas state and injected back into the system to increase overall pressure of the refrigerant being sent to the compressor, thereby reducing the load on the compressor and raising efficiency.
Heat exchanger
PUMY-P V/YHMB
Heat Interchanger (HIC)
PUMY-P V/YKM
Cooling operation
Indoor HEX
A
Outdoor HEX
Accumulator LEV B
A
Compressor
LEV C
LEV A Heat interchanger(HIC)
w/ HIC circuit w/o HIC circuit I_current I_new
43
Increase in heat-exchanger surface area
(image)
Heat-exchange surface area increased Heat exchanger size extended horizontally, increasing the surface area.
Indoor unit
[P175~225(YKM)]
2 lines, 64 columns
The pipe diameter has been changed from 9.52 to 7.94mm, resulting in a high-density heat exchanger.
Heat Interchanger (HIC) Added Refrigerant Piping Lengths
2 lines, 52 columns
HIC without to increase the heat exchange volume with increasing
I.
44
Advanced Energy-saving Technologies
System Controller
OUTDOOR UNIT S Series Specifications
MITSUBISHI ELECTRIC's Air-conditioner Network System (MELANS) leads air conditioner management a PC browser and Network era.
Model
Power source
Cooling capacity (Nominal)
12.5
14.0
15.5
12.5
14.0
42,700
47,800
52,900
42,700
47,800 3.46 5.53-5.26-5.07
Indoor temp.
8HP Extended residence space.
4.46-4.24-4.09
3.43
4.48
4.05
W.B.
15.0~24.0°C
15.0~24.0°C
15.0~24.0°C
15.0~24.0°C
15.0~24.0°C -5.0~46.0°C
D.B.
-5.0~46.0°C
-5.0~46.0°C
-5.0~46.0°C
-5.0~46.0°C
kW
14.0
16.0
18.0
14.0
16.0
*2
BTU / h
47,800
54,600
61,400
47,800
54,600 3.74 5.98-5.68-5.48
Power input
kW
3.04
3.74
4.47
3.04
Current input
A
14.03-13.42-12.86
17.26-16.51-15.82
20.63-19.73-18.91
4.86-4.62-4.45
4.61
4.28
4.03
4.61
D.B.
15.0~27.0°C
15.0~27.0°C
15.0~27.0°C
15.0~27.0°C
Outdoor temp.
W.B.
Indoor unit connectable
Total capacity
-20.0~15.0°C
-20.0~15.0°C
-20.0~15.0°C
-20.0~15.0°C
50~130 % of outdoor unit capacity
50~130 % of outdoor unit capacity
50~130 % of outdoor unit capacity
50~130 % of outdoor unit capacity
P15~P140 / 9
P15~P140 / 10
P15~P140 / 12
P15~P140 / 9
P15~P140 / 10
49 / 51
50 / 52
51 / 53
49 / 51
50 / 52
9.52 Flare
9.52 Flare
15.88 Flare
15.88 Flare
Model / Quantity dB
Highly efficient fan outdoor unit 15.88 Flare and grille for 15.88 Flare 15.88 Flare mm
Refrigerant piping diameter
Liquid pipe
FAN
Air flow rate
New S series can maximize residential area.
9.52 Flare
9.52 Flare
9.52 Flare
m3 /min
110
110
110
110
110
L/s
1,833
1,833
1,833
1,833
1,833
Gas pipe
kg
Power source
123
123
The two-pipe zoned system designed for Heat Pump Operation
Heating capacity (Nominal)
The CITY MULTI S series make use of a two-pipe refrigerant system, which allows for system changeover from cooling to heating, ensuring that a constant indoor climate is maintained in all zones. The compact outdoor unit utilizes R410A refrigerant and an INVERTER-driven compressor to use energy effectively. With a wide range of indoor unit line-up in connection with a flexible piping system, the CITY MULTI series can be configured for all applications. Up to 12 indoor units can be connected with up to 130% connected capacity to maximize engineer's design options. This feature allows easy air conditioning in each area with convenient individual controllers.
Temp. range of heating Indoor unit connectable
R410A 4.8kg
125
125
Outdoor unit
[P112~140(V/YKM)] Refrigerant Piping Lengths
Maximum meters
Total length Maximum allowable length Farthest indoor from first branch
300 150 (175 equivalent) 30
Vertical differentials between units
Maximum meters
Indoor/outdoor (outdoor higher) Indoor/outdoor (outdoor lower) Indoor/indoor
50 40 15
Furthest piping length 175m (equivalent length) (actual length 150m)
Top-bottom differential 50m
Between indoor units top-bottom differential 15m
6.91
9.62
11.29-10.72-10.34
15.72-14.93-14.39
3.65
3.24
2.60
Indoor temp.
W.B.
15.0~24.0°C
15.0~24.0°C
15.0~24.0°C
15.0~24.0°C
-5.0~46.0°C
-5.0~46.0°C
FAN
Air flow rate
Gas pipe
22.4 5.73 9.36-8.89-8.57
11.37-10.80-10.41
3.91
3.59
3.57
15.0~27.0°C
15.0~27.0°C
15.0~27.0°C
-20.0~15.0°C
-20.0~15.0°C
50~130 % of outdoor unit capacity
50~130 % of outdoor unit capacity
P15~P224 / 12
P15~P250 / 12
P15~P250 / 12
56/ 61 PUMY-P V/YKM
9.52 Flare *3
9.52 Flare *3
mm
15.88 Flare
22.2 Brazed
22.2 Brazed
22.2 Brazed
m3 /min
110
134
134
143.8
2,233
2,397
L/s 1,833 2,233 Highly efficient heat exchanger cfm
3,884
4,732
4,732
5,078
1,338 x 1,050 x 330 (+25)
1,338 x 1,050 x 330 (+25)
1,338 x 1,050 x 330 (+25)
1,338 x 1,050 x 330 (+25)
High-density heat exchanger
Indoor unit
7.5m
0m
2 lines, 52 columns
ExternalTheDimensions pipe diameter has been changed from 9.52 to 7.94mm, resulting
Unit : mm
2 lines, 64 columns
PUMY-P112V(Y)KM PUMY-P125V(Y)KM PUMY-P140V(Y)KM in a high-density heat exchanger. PUMY-P175YKM PUMY-P200YKM PUMY-P225YKM
Increase in heat-exchanger surface area
(image)
Heat-exchange surface area increased OUTDOOR UNIT 1050
Between indoor units top-bottom differential 15m
7ºC DB/6ºC WB
Level difference
A high density and increase in surface area have improved the heat-exchange efficiency Type x original charge R410A 4.8kg R410A 7.3kg R410A 7.3kg R410A 7.3kg of the heat exchanger. kg 125 138 138 138
600
362
Terminal connection From left to right
Heat exchanger For the *1 branch box power supply
For the power supply
Ground for the power supply ("GR"marking position)
For the transmission line
Heat exchanger
For concentration control
PUMY-P V/YHMB
225
19
PUMY-P V/YKM
Ground for the transmission line Ground for concentration control
417
370
330
Maximum meters 50 40 15
20ºC DB
Pipe length
Fan rear edge
mm
56 33 0 53
70(75*)
632
56(60*)
1338
28
42
25
Vertical differentials between units Indoor/outdoor (outdoor higher) Indoor/outdoor (outdoor lower) Indoor/indoor
58 / 63
9.52 Flare *3
2-U Shaped notched holes (Foundation Bolt M10)
Handle for moving
Air Discharge A HIC circuit has been added to improve energy efficiency during cooling operation. Liquid refrigerant is PUMY-P175/200/225YKM rerouted, *transformed into a gas state and injected back into the system to increase overall pressure of the refrigerant being sent to the compressor, thereby reducing the load on the compressor and raising efficiency.
1 Refrigerant GAS pipe connection PUMY-P112/125/140V(Y)KM:(Flare) 15.88
Ground for *1 the branch box
power supply Heat Interchanger Service (HIC)
Cooling operation PUMY-P175/200/225YKM:(attached T) 22.2
2 Refrigerant LIQUID pipe connection :(Flare) 9.52
Handle for moving
A
Air Intake
Indoor HEX
LEV B
1 2
*1 PUMY-P112/125/140V(Y)KM only. Outdoor Accumulator *2 Indication of STOP VALVE connection location. HEX *3 PUMY-P175/200/225YKM:(Flare) 19.05(3/4F)
A
Compressor
Model
A
PUMY-P112/125/140VKM
LEV1062 A Heat interchanger(HIC) PUMY-P112/125/140YKM 909
26
2-12×36 Oval holes (Foundation Bolt M10)
369
Furthest piping length 90m (equivalent length) (actual length 80m)
Top-bottom differential 50m
56 / 61
9.52 Flare
Heat Interchanger (HIC) Added
150 80 (90 equivalent) 30
35ºC DB
*3 Liquid pipe diameter:12.7mm in case of farthest piping length is longer than 60m.
-20.0~15.0°C
mm
Installation Feet
Total length Maximum allowable length Farthest indoor from first branch
12.50-11.87-11.44
50~130 % of outdoor unit capacity
Side Air Intake
Maximum meters
Cooling
Outdoor
Adoption of a fan-5.0~46.0°C with improved ventilation characterisHeating 7.5m 0m 25.0 27.3 tics and a newly designed rear *Nominal edgecondition that*1,*2suppresses 85,300 93,200 are subject to ISO 15042. 6.96 7.65 fan operation *Due to continuing improvement, above specification wind turbulence raises efficiency. may be subject to change without notice.
76,400
51 / 53 PUMY-P V/YHMB
dB
Inflexed fan
*1,*2 Nominal conditions
Indoor Opening increased fromCooling 490 27ºC to 550mm DB/19ºCWB in diameter Heating
5.48 8.95-8.51-8.20
225
Refrigerant Piping Lengths
85,300
4.52
Heat exchanger size extended horizontally, increasing the Rear Air Intake surface area.
Outdoor unit
25.0
7.23-6.87-6.62
Liquid pipe
Indoor unit
[P175~225(YKM)]
3-phase 380-415V 50Hz
A
Outdoor temp. The shape of D.B. the air -5.0~46.0°C 18.0 *2 kW outlet grille*2has 61,400 BTU /been h 4.47 c h Power a n ginput e d to r ekWd u c e 7.15-6.79-6.55 Current input A pressure l o skWs./ kWT h i s 4.03 COP 15.0~27.0°C temp. to improve D.B. hasIndoor helped -20.0~15.0°C Outdoor temp. heat exchange W.B. perfor50~130 % of outdoor unit capacity Total capacity mance. P15~P140 / 12 Model / Quantity
Notes:
PUMY-P225YKM
kW
Refrigerant piping diameter
Refrigerant
LEV C
Front piping cover Rear piping cover
w/ HIC circuit w/o HIC circuit
I_current I_new
45
R410A 4.8kg
123
Current input
Sound pressure level (measured in anechoic room)
Net weight
Silent mode can reduce sound pressure level by 3dB(A)
3,884 1,338 x 1,050 x 330 (+25)
Power input
External dimension HxWxD
Outdoor unit
3,884 1,338 x 1,050 x 330 (+25)
PUMY-P140YKM PUMY-P200YKM The diameter of the opening for the fan in thePUMY-P175YKM outdoor unit has been in380-415VBlowing 50Hz 3-phase 380-415V 3-phase 380-415V 50Hz creased from 490 to 3-phase 550mm. capacity has50Hz been increased 15.5 20.0 22.4 *1 kW while maintaining the same52,900 fan rotation speed. 68,200 *1 BTU / h 76,400
Grille shape changed 3.43 EER kW / kW Temp. range of cooling
-20.0~15.0°C
mm
The shapes ofcfm the fan and3,884 grille of the outdoor unit have been rede3,884 3,884 External dimension HxWxD signed, realising an increase in blowing capacity and more efficient heat mm 1,338 x 1,050 x 330 (+25) 1,338 x 1,050 x 330 (+25) 1,338 x 1,050 x 330 (+25) exchange while maintaining the same operating noise level. Refrigerant Type x original charge R410A 4.8kg R410A 4.8kg R410A 4.8kg
Cooling capacity (Nominal)
PUMY-P VKM 4.28 15.0~27.0°C PUMY-P YKM
50~130 % of outdoor unit capacity
Outdoor unit fan opening increased 8HP x 1units
S series
kW / kW
Indoor temp.
Net weight
4HP x 2units
Residence
20.86-19.95-19.12
4.05
Temp. range of heating
Model
e
15.97-15.27-14.64
4.48
A
Welc om
New S series
4.52
12.87-12.32-11.80
B *2
Light and easy to carry
8HP
3.46
A
kW / kW
C *2*3
On the balcony
Easy to transport by elevator
By the entrance
Smaller footprint
2.79
2.79
kW
*2
Outdoor temp.
Sound pressure level (measured in anechoic room)
Light weight
PUMY-P125YKM 3-phase 380-415V 50Hz
kW
COP
Flexible choice and suitable for the limited outdoor space.
PUMY-P112YKM 3-phase 380-415V 50Hz
BTU / h
Current input
Easy to transport and install at site.
PUMY-P140VKM
1-phase 220-240V 50Hz
*1
EER
Heating capacity (Nominal)
PUMY-P125VKM
1-phase 220-240V 50Hz
*1
Power input
Temp. range of cooling
PUMY-P112VKM
1-phase 220-240V 50Hz
PUMY-P175/200/225YKM
HIC without to increase the heat exchange volume with increasing
986
B
C
510
426
510
426
450
393
I.
46
Wide Selection of Indoor Units Model name
Ceiling Cassette
4-way air flow
Model name
Model
P15
P20
P25
P32
P40
P50
P63
P71
P80
P100
P125
P140
P200
P250
PLFY-P VBM-E
PLFY-P VCM-E2
2-way air flow
PLFY-P VLMD-E
1-way air flow
PMFY-P VBM-E
Ceiling Concealed
PEFY-P VMR-E-L/R
PEFY-P VMS1(L)-E
PEFY-P VMA(L)-E
PEFY-P VMA3-E
PEFY-P VMH(S)-E
Fresh Air Intake
PEFY-P VMH-E-F
Ceiling Suspended
PCFY-P VKM-E
Wall Mounted
PKFY-P VBM-E
PKFY-P VHM-E
PKFY-P VKM-E
Floor Standing/ Floor Mounted Concealed
PFFY-P VKM-E2
PFFY-P VLEM-E
PFFY-P VLRM-E PFFY-P VLRMM-E
47
48
System SystemController Controller
The System New Structure Cooling-only Models
Mitsubishi MITSUBISHI Electric's ELECTRIC's Air-conditioner Air-conditioner NetworkNetwork System (MELANS) System (MELANS) introduces leads an era airofconditioner air conditioner management management a PC via browser PC browsers and Network connected era. to a Network.
Mitsubishi In an easyElectric and flexible offersmanner a wide with lineup our ofnew newCentralized cooling-only Controller models with AE-200E, themaximum an optimum capacity system of 54 canHP*. be Different patterns established of combinations according toof the basic scale modules of facilities. provide either standard or high COP. *Applicable to standard model combinations only
MELANS MELANS
Requires t work
Single module up 20 HP
Use Useofofour ourMELANS MELANSproducts productsenhances enhancesEFFICIENCY EFFICIENCYand andQUALITY QUALITYofofair-conditioning, air-conditioning,contributing contributingtotoENERGY ENERGYSAVING SAVINGand and reduction reduction inin running running cost. cost. We We offer offer a wide a wide variety variety ofof MELANS MELANS products products toto meet meet allall requirements requirements - from - from the the smallest smallest and and simplest simplest toto the thelargest largestand andmost mostcomplex. complex. We Wehave haveindividual individualremote remotecontrollers, controllers,various variouscentralized centralizedcontrollers, controllers,and andcentralized centralizedintegrated integratedsoftware, software,asaswell wellasasBMS BMS interface interface hardware hardwareand andsoftware softwareetc. etc.Above Aboveall,all,with withAE-200E/AE-50E/AG-150A/EB-50GU-J/GB-50ADA-J, AE-200E/AE-50E/AG-150A/EB-50GU-J/GB-50ADA-J,PC PCbrowser browserand andlong longdistance distance remote remotecontrol control(monitoring (monitoringand andoperating) operating)viaviacommunication communicationNetwork Networkis ispossible possibleand andeasy. easy.
ndividual Remote Controller
Remote Controller
Simple Remote Controller
Wireless Remote Controller
C entralized Remote Controller Advanced Touch Controller
Field-installed
HUB BACnet®
NEW
AE-200E/AE-50E
Field-installed
Tablet
All modules feature inverter-driven compressors. Maximum combined horse power: 60 HP
52ºC
New
Current
M-NET
M-NET
LAN1
AG-150A
group 1
AT-50B
ON/OFF Remote Controller
M-NET M-NET
Capable of running cooling operations HUB of up to HUBtemperature in the outdoor 52°C*. LAN2 *Compared to 46°C of the older model
NEW
20HP
No need for t work
PC
® *1
All of the local remote controllers feature liquid crystal and LED displays and easy to operate.
10HP
Capable of management covering up to 20 HP with a single module and a single Building system BMS compressor. Reduced piping work.
To be connectable with Compatibility to outdoor temperature BACnet Router of up to 52°C*1
I
10HP
group 2
AE-200E EB-50GU-J
PAC-YG50ECA
PAR-31MAAE
M-NET
Increase in the limit of piping length LAN1 : For air conditioning systems LAN2 : For BACnet®
PAC-YT52CRA PAR-FL32MA PAR-FA32MA
GB-50ADA-J PAC-YT40ANRA
Farthest indoor from first branch: 90 m Height difference between indoor and indoor units is up to 30 m.
group 3
AHC ADAPTER
PAR-U02MEDA
First Branch *1
PAR-SA9FA-E
PAR-SL94B-E
group 4
PAC-IF01AHC-J
PI Controller
Power supply unit (PAC-SC51KUA)
Max height
30m
*2
General Equipment DIDO Controller (PAC-YG66DCA)
Max length
90m*3
Temp/Humidity sensor
Lights
Ventilation
Security card reader
AI Controller (PAC-YG63MCA)
PAC-YG60MCA
OUTDOOR UNIT S : PUMY Y : PUCY/PUHY
DIDO Controller
INDOOR UNIT PLFY PMFY PEFY
PCFY PKFY PFFY
PAC-YG66DCA
AI Controller
Watt hour meter
Standard or high COP options are available by different combinations of modules. LAN2
PI Controller (PAC-YG60MCA)
LAN1
Farthest indoor from first branch: 90 m Height difference AE-50E between indoor and indoor units is up to 30 m. PAC-YG63MCA
Interface
Interface
LAN2
S
*1. Advanced HVAC CONTROLLER
LLAN1
XL AE-50E
BAC-HD150
A ir-Conditioning
LMAP04-E
LAN2
Control System
BACnet ® *1
transmission line (Ethernet)
This is a specialized air conditioning management system, in which up to 2000 indoor units can be centrally controlled.
LONWORKS ® *2
transmission line
Mitsubishi Electric's CITY MULTI can be easily connected to the building management system through BACnet .
LAN1
HP example : 30HP
8 10 12
+
S
L
COP
Integrated centralized control software TG-2000A
+
S
+
S
L
COP
3.33
3.88
Standard model
HighCOP model
12
Ethernet
AE-50E 20
14 16 18
+
18
=
30
*1. Please your local distributor for when the feature is ed.
8
+
8
+
14
=
30
Integrated centralized control software TG-2000A
49
*Some controllers cannot be used in combination with certain models of devices. *1 BACnet ® is a ed trademark of ASHRAE. *2 LonWorks® is a trademark of Echelon Corporation ed in the United States and other countries.
*1 : Any continuous operation over 46ºC may require an increased frequency of maintenance. *2 : When the height difference is 15m or greater, use the one size larger liquid pipe between the indoor unit and the indoor unit. *3 : When the piping length is 40m or longer, use the one size larger liquid pipe between the indoor unit and the first branch. 50
1-way cassette
Unit : mm
MLZ-KA25VA MLZ-KA35VA MLZ-KA50VA INDOOR UNIT (Top)
35
466.5
0 10
20~45 860~910
605 +35 -5
D
74
241 258
85 77
20~45
Detail connecting of branch duct 90
100
Cut out hole
90
Power supply wire, Indoor unit/Outdoor unit connecting wire entry
Ceiling Grille
155
Keep approximately 10 to 15mm space between unit ceiling and ceiling slab.
175
Burring hole pitch
350
150
167
B
70
Control wire entry
35
Suspension bolt lower edge
100
130
Drain pipe
100
377
A
Hole position for the installation of grille
284
17 +50
6
R6
466.5
166.5 173
60
Refrigerant pipe (gas) 170
0
160
105
CL
414
81.8
PLA-RP60BA
840
Suspension bolt M10 or W3/8
50~70
R6
C
80
PLA-RP71BA
Refrigerant pipe (liquid)
172.4 166.5
B
(7.5)
Ceiling surface
24
Grille
160
Ceiling surface
140
CL
A
PLA-RP50BA
190
34
1200
Receiving section
Models
Branch duct hole
87
187.5
Grille (MLP-440W)
Suspension bolt pitch
Suspension bolt M10
Ceiling hole
(7.5)
160 840
Indoor power supply terminal block(optional part)
D
Ceiling surface Display and receiving section
(Front)
Remote controller terminal block Indoor unit/Outdoor unit connecting terminal block
156
58 No gaps between the ceiling surface and grille
0.04m2
Branch duct hole 950
112 60
25
48
Gas pipe Liquid pipe
31
110
116 Pipe cover Drain pan
Outlet opening area
20
C
110 Drain pipe
Electrical box
54.5
90
78
Suspension bolt pitch
175
170
180 or more
960
1160 Ceiling opening
244
Drain hose
160
Outlet
1051 Suspension bolt pitch
360
175
1102
Air outlet
1200 Outer side of grille
(Right side) Drain hose
20~45
860~910 810
620
38
15
54.5 20
(Front)
Ceiling hole
20~45
Fresh air intake hole
150
20
950 Center of ceiling opening, suspension bolt pitch and grille are located in one position.
308 Suspension bolt pitch
158
15
180
230 15
1051 Suspension bolt pitch
18
26
Drain hose connecting part
Air outlet
58
414 Outer side of grille
26
Pipe cover
Electrical box
20
308 Suspension bolt pitch
2 2
Wireless remote controller
384 Ceiling opening
Center of ceiling opening, suspension bolt pitch and grille are located in one position.
38
13.5
58
49.7
Unit : mm
PLA-RP50BA PLA-RP60BA PLA-RP71BA INDOOR UNIT
(Top)
(51.6)
4 -way cassette
14- 2.8
Burring hole
Cut out hole
36
Ceiling-concealed
Unit : mm
SEZ-KD25VAL SEZ-KD35VAL SEZ-KD50VAL SEZ-KD60VAL SEZ-KD71VAL
OUTDOOR UNIT
37 400
169
Drain hole
63.2
Air in
18.3
344.5
16.8
171
288
12.3
Air in
Air out
Air out
Drain holes
2-10x21 Oval hole 22.3
23
285
17.7
H 100XJ=K
Air inlet
500 233.1
40
C
A
Air outlet
B (Suspension bolt pitch)
D (Duct)
100X(E-1)=F
17.5
Air in
304 325
44
88
Air in
396
37 100
OUTDOOR UNIT
17.7
12
15
157.5
MXY-3A28VA MXZ-3C68VA
360.6 (Bolt Pitch)
20
Unit : mm
MXY-2E20VA MXZ-2C52VA
31.3
INDOOR UNIT
MXY SERIES MXZ SERIES
4-10 x 21 Oval hole (Base bolt M10)
13
840
30
200
30
330
13
240
66.3
170.4
800
69
440
C unit connection
500
225
150
Gas pipe
710
251.1
302.5
Knockout hole 27 (Indoor/outdoor connecting line)
Control box
B unit connection A unit connection
299
Notes:
7
700
20
9
900
24
MXY-4A28VA MXZ-4C71VA
MXY-4A38VA MXZ-4C80VA MXZ-5C100VA
OUTDOOR UNIT
OUTDOOR UNIT
169
500 233.1
31.3
200
171
288
35
Air in
18.3
16.8
63.2
12.3
Air in Drain holes
500
Air in
Air out
Air in Drain holes
4-10 x 21 Oval hole (Base bolt M10)
30
30
27.1 Indoor and outdoor connect wiring 39 x 27 hole
2-12 x 36 Oval hole (Base bolt M10)
30
330
13
Handle
Handle
84
Gas pipe
B
132 317
10
88
A
B unit connection A unit connection
299
45
C unit connection
440
45
360
315
710
D unit connection
460
Gas pipe
320
Indoor and outdoor connect wiring (35 x 53) hole
66.3
405
200
2 U-shaped notched hole (Base bolt M10)
900
240
840
200
270
17.7
Air out
250
900
860
(Bolt pitch) 387
800
1000 1060
597
9 11
1. Use M10 bolts for suspension (purchase locally). 2. Keep service space for maintenance at the bottom. 3. This chart is based on the SEZ-KD50VAL, which has three fans. SEZ-KD25VAL and SEZ-KD35VAL have two fans, and SEZ-KD60VAL and SEZ-KD71VAL have four fans. 4. If an inlet duct is used, remove the air filter supplied with the unit, and install a locally purchased filter on the suction side.
16
L 16
11
K 500
355
860
J 5
24
998
H 660
16
952
F 600
27
900
1100 1152 1198 1060
E 7
40
D 660
35
C 798
74
B 752
396
A 700
17.7
Drain pipe(Spontaneous draining)
Model SEZ-KD25VAL SEZ-KD35VAL SEZ-KD50VAL SEZ-KD60VAL SEZ-KD71VAL
Liquid pipe
23.1
200
Terminal block Terminal block (Indoor/outdoor connecting line) (Remote controller transmission line)
70 270
360.6 (Bolt Pitch)
116
170
102
2X2- 2.9 Refrigerant piping flare connection (gas)
Knockout hole 27 (Remote controller transmission line)
Indoor and outdoor connect wiring 39 x 27 hole
A unit connection
45
Air filter
27.1
B unit connection
84
23 10
100
150 (Duct)
23 25
Refrigerant piping flare connection (liquid)
700 677
51 51 51
L- 2.9
Suspension bolt hole 4-14X30 Slot
Liquid pipe Gas pipe Liquid pipe Gas pipe
360
625 (Suspension bolt pitch)
49
10
23
10
280
20 12
57
2XE- 2.9
90
25
20 30
88
550
100
100
handle
E unit connection (MXZ-5C100VA) D unit connection C unit connection B unit connection A unit connection
23 Liquid pipe
23.1 Liquid pipe
37
38
Piping Installation MXZ-6C120VA
MXY SERIES MXZ SERIES
OUTDOOR UNIT
MXY-2E20VA MXZ-2C52VA
Unit : mm
Maximum Piping Length 450
200
(Foundation Bolt M10)
16
42 Drain Hole
Air Discharge
Outdoor unit - Indoor unit (a,b)
20m
Total length (a+b)
30m
Maximum height difference
a
Outdoor unit
Maximum Number of Bends
40
24
Side Air Intake
387
355 (Bolt Pitch)
11
48
Rear Air Intake
2-U Shaped Notched Hole
27
500
16
200
Indoor units
2-12 x 36 Oval Hole
Outdoor unit - Indoor unit (a,b)
20
Total number (a+b)
30
Outdoor unit |
Indoor unit
15m
*Outdoor unit installed lower
21
320
|
15m
(Foundation Bolt M10)
900
Indoor unit Indoor unit
5
Outdoor unit |
Indoor unit
b Connecting Wire Hole (36 x 96)
10m
*Outdoor unit installed higher
Handle 70
515
LIQ GAS LIQ GAS LIQ GAS LIQ GAS LIQ GAS LIQ GAS
Unit F Unit E Unit D Unit C
LIQ 6.35(1/4")FLARE GAS 9.52(3/8")FLARE
Unit B Unit A
LIQ 6.35(1/4")FLARE GAS 12.7(1/2")FLARE
125
45
548
730
65
1070
Handle
340
34
MXY-3A28VA MXZ-3C68VA
Indoor units
Maximum Piping Length Outdoor unit - Indoor unit (a,b,c)
25m
Total length (a+b+c)
60m
Highest
Outdoor unit
b
Maximum Number of Bends Outdoor unit - Indoor unit (a,b,c)
25
Total number (a+b+c)
60
Maximum height difference
a
Outdoor unit |
Indoor unit
15m
*Outdoor unit installed lower Indoor unit |
Indoor unit
15m
Lowest
Outdoor unit
c
|
Indoor unit
10m
*Outdoor unit installed higher
39
40
MXY-4A28VA MXZ-4C71VA
Indoor units
Maximum Piping Length Outdoor unit - Indoor unit (a,b,c,d)
25m
Total length (a+b+c+d)
60m
Highest
Outdoor unit
b
Maximum Number of Bends Outdoor unit - Indoor unit (a,b,c,d)
25
Total number (a+b+c+d)
60
Maximum height difference
a
Outdoor unit |
Indoor unit
15m
*Outdoor unit installed lower Indoor unit |
c
MXY-4A38VA MXZ-4C80VA
Indoor unit
15m
Lowest
Maximum Piping Length Outdoor unit - Indoor unit (a,b,c,d)
25m
Total length (a+b+c+d)
70m
Outdoor unit
d
|
Indoor unit
10m
*Outdoor unit installed higher
Maximum Number of Bends Outdoor unit - Indoor unit (a,b,c,d)
25
Total number (a+b+c+d)
70
Indoor units
MXZ-5C100VA
Maximum Piping Length Outdoor unit - Indoor unit (a,b,c,d,e)
25m
Total length (a+b+c+d+e)
80m
Highest
Maximum height difference
a Outdoor unit
b
Outdoor unit |
Indoor unit
Maximum Number of Bends
15m
c
Outdoor unit - Indoor unit (a,b,c,d,e)
25
Total number (a+b+c+d+e)
80
*Outdoor unit installed lower Indoor unit |
Indoor unit
15m
Outdoor unit |
Lowest
Indoor unit
10m
d e
*Outdoor unit installed higher
Highest Indoor units
MXZ-6C120VA
Maximum Piping Length Outdoor unit - Indoor unit (a,b,c,d,e,f)
25m
Total length (a+b+c+d+e+f)
80m
e
Maximum height difference
a Outdoor unit
b
Outdoor unit |
Indoor unit
Maximum Number of Bends
15m
c
Outdoor unit - Indoor unit (a,b,c,d,e,f)
25
Total number (a+b+c+d+e+f)
80
*Outdoor unit installed lower Indoor unit |
Indoor unit
15m
Outdoor unit |
Lowest
Indoor unit
d f
41
10m
*Outdoor unit installed higher
42