Space Input Data koushari @ MOQ bp
09/01/2016 06:23PM
SHOP AREA 1. General Details: 50.0 Floor Area 6.0 Avg. Ceiling Height 341.8 Building Weight 1.1. OA Ventilation Requirements: -Defined Space Usage 0.0 OA Requirement 1 0.00 OA Requirement 2 ASHRAE Std 62.1-2007 Space Usage Defaults 2. Internals: 2.1. Overhead Lighting: Fixture Type Wattage Ballast Multiplier Schedule
m² m kg/m² L/s L/(s-m²)
Recessed (Unvented) 25.00 W/m² 1.25 project 1
2.2. Task Lighting: Wattage Schedule
0.00 W/m² project 1
2.3. Electrical Equipment: Wattage Schedule
25.00 W/m² project 1
2.4. People: Occupancy Activity Level Sensible Latent Schedule 2.5. Miscellaneous Loads: Sensible Schedule Latent Schedule
2.00 m²/person Medium Work 86.5 W/person 133.3 W/person project 1
0 W project 1 0 W project 1
3. Walls, Windows, Doors: (No Wall, Window, Door data). 4. Roofs, Skylights: (No Roof or Skylight data). 5. Infiltration: Design Cooling Design Heating Energy Analysis Infiltration occurs at all hours.
0.00 ACH 0.00 L/s 0.00 ACH
6. Floors: Floor Above Unconditioned Space Type 50.0 Floor Area 5.000 Total Floor U-Value 46.0 Unconditioned Space Max Temp. 23.0 Ambient at Space Max Temp. 46.0 Unconditioned Space Min Temp. 22.0 Ambient at Space Min Temp.
m² W/(m²-°K) °C °C °C °C
7. Partitions: (No partition data).
Hourly Analysis Program v4.61
Page 1 of 1
Air System Sizing Summary for TOTAL LOAD Project Name: koushari @ MOQ Prepared by: bp
09/01/2016 06:23PM
Air System Information Air System Name Equipment Class Air System Type
TOTAL LOAD TERM 2P-FC
Number of zones Floor Area Location
1 50.0 m² Doha, Qatar
Sizing Calculation Information Zone and Space Sizing Method: Sum of space airflow rates Zone L/s Individual peak space loads Space L/s
Hourly Analysis Program v4.61
Calculation Months Sizing Data
Jan to Dec Calculated
Page 1 of 5
Zone Sizing Summary for TOTAL LOAD Project Name: koushari @ MOQ Prepared by: bp
09/01/2016 06:23PM
Air System Information Air System Name Equipment Class Air System Type
Number of zones Floor Area Location
TOTAL LOAD TERM 2P-FC
1 50.0 m² Doha, Qatar
Sizing Calculation Information Zone and Space Sizing Method: Zone L/s Space L/s
Calculation Months Sizing Data
Sum of space airflow rates Individual peak space loads
Jan to Dec Calculated
Zone Sizing Data
Zone Name Zone 1
Maximum Cooling Sensible (kW) 12.1
Design Air Flow (L/s) 1178
Minimum Air Flow (L/s) 1178
Time of Peak Load Jan 2300
Maximum Heating Load (kW) 0.0
Total Coil Load (kW) 15.7
Sens Coil Load (kW) 12.1
Coil Entering DB / WB (°C) 23.1 / 18.1
Coil Leaving DB / WB (°C) 14.6 / 14.1
Water Flow @ 8.9 °K (L/s) 0.42
Heating Heating Coil Coil Ent/Lvg Load DB (kW) (°C) 0.0 -17.8 / -17.8
Htg Coil Water Flow @11.1 °K (L/s) 0.00
Fan Design AirFlow (L/s) 1178
Fan Motor (BHP) 0.294
Zone Floor Area (m²) 50.0
Zone L/(s-m²) 23.57
Terminal Unit Sizing Data - Cooling
Zone Name Zone 1
Time of Peak Load Jan 2300
Terminal Unit Sizing Data - Heating, Fan, Ventilation
Zone Name Zone 1
Fan Motor (kW) 0.233
OA Vent Design AirFlow (L/s) 0
Space Loads and Airflows Zone Name / Space Name Zone 1 SHOP AREA
Hourly Analysis Program v4.61
Mult.
Cooling Sensible (kW)
Time of Load
Air Flow (L/s)
Heating Load (kW)
Floor Area (m²)
Space L/(s-m²)
1
12.1
Jan 2300
1178
0.0
50.0
23.57
Page 2 of 5
Air System Design Load Summary for TOTAL LOAD Project Name: koushari @ MOQ Prepared by: bp
ZONE LOADS Window & Skylight Solar Loads Wall Transmission Roof Transmission Window Transmission Skylight Transmission Door Loads Floor Transmission Partitions Ceiling Overhead Lighting Task Lighting Electric Equipment People Infiltration Miscellaneous Safety Factor >> Total Zone Loads Zone Conditioning Plenum Wall Load Plenum Roof Load Plenum Lighting Load Exhaust Fan Load Ventilation Load Ventilation Fan Load Space Fan Coil Fans Duct Heat Gain / Loss >> Total System Loads Terminal Unit Cooling Terminal Unit Heating >> Total Conditioning Key:
Hourly Analysis Program v4.61
09/01/2016 06:23PM
DESIGN COOLING DESIGN HEATING COOLING DATA AT Jan 2300 HEATING DATA AT DES HTG COOLING OA DB / WB 27.6 °C / 21.0 °C HEATING OA DB / WB 10.0 °C / 6.0 °C Sensible Latent Sensible Latent Details (W) (W) Details (W) (W) 0 m² 0 0 m² 0 m² 0 0 m² 0 0 m² 0 0 m² 0 0 m² 0 0 m² 0 0 m² 0 0 m² 0 0 m² 0 0 m² 0 50 m² 6000 50 m² 0 0 m² 0 0 m² 0 0 m² 0 0 m² 0 1563 W 1562 0 0 0W 0 0 0 1250 W 1250 0 0 25 2162 3333 0 0 0 0 0 0 0 0 0 0 0 10% / 10% 1097 333 10% 0 0 12072 3666 0 0 11843 3666 0 0 0% 0 0 0 0% 0 0 0 0% 0 0 0 0 L/s 0 0 L/s 0 0 L/s 0 0 0 L/s 0 0 0 L/s 0 0 L/s 0 233 -233 0% 0 0% 0 12077 3666 -233 0 12077 3666 -233 0 0 0 12077 3666 -233 0 Positive values are clg loads Positive values are htg loads Negative values are htg loads Negative values are clg loads
Page 3 of 5
System Psychrometrics for TOTAL LOAD Project Name: koushari @ MOQ Prepared by: bp
09/01/2016 06:23PM
January DESIGN COOLING DAY, 2300 TABLE 1:
SYSTEM DATA
Component Ventilation Air Vent - Return Mixing Ventilation Fan Zone Air Return Plenum
Location Inlet Outlet Outlet Outlet
Dry-Bulb Temp (°C) 27.6 -17.8 -17.8 22.9 -17.8
Specific Humidity (kg/kg) 0.01288 0.00000 0.00000 0.01092 0.01092
Airflow (L/s) 0 0 0 1178 1178
CO2 Level (ppm) 400 0 0 200 200
Sensible Heat (W) 0 0 11843 0
Latent Heat (W) 0 3666 -
Air Density x Heat Capacity x Conversion Factor: At sea level = 1.207; At site altitude = 1.205 W/(L/s-K) Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947.6; At site altitude = 2942.8 W/(L/s) Site Altitude = 13.5 m
TABLE 2:
ZONE DATA
Component Zone 1 ( Cooling ) Ventilation Air Cooling Coil Inlet Cooling Coil Outlet Heating Coil Inlet Heating Coil Outlet Zone Air
Hourly Analysis Program v4.61
Location
Dry-Bulb Temp (°C)
Specific Humidity (kg/kg)
Airflow (L/s)
CO2 Level (ppm)
Sensible Heat (W)
Latent Heat (W)
-
23.1 14.6 14.6 14.6 22.9
0.01092 0.00986 0.00986 0.00986 0.01092
0 1178 1178 1178 1178 1178
0 0 0 0 0
12077 0 11843
3666 -
Page 4 of 5
System Psychrometrics for TOTAL LOAD Project Name: koushari @ MOQ Prepared by: bp
09/01/2016 06:23PM
WINTER DESIGN HEATING TABLE 1:
SYSTEM DATA
Component Ventilation Air Vent - Return Mixing Ventilation Fan Zone Air Return Plenum
Location Inlet Outlet Outlet Outlet
Dry-Bulb Temp (°C) 10.0 -17.8 -17.8 21.1 -17.8
Specific Humidity (kg/kg) 0.00417 0.00000 0.00000 0.01092 0.01092
Airflow (L/s) 0 0 0 1178 1178
CO2 Level (ppm) 400 0 0 0 0
Sensible Heat (W) 0 0 0 0
Latent Heat (W) 0 0 -
Air Density x Heat Capacity x Conversion Factor: At sea level = 1.207; At site altitude = 1.205 W/(L/s-K) Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947.6; At site altitude = 2942.8 W/(L/s) Site Altitude = 13.5 m
TABLE 2:
ZONE DATA
Component Zone 1 ( Deadband ) Ventilation Air Cooling Coil Inlet Cooling Coil Outlet Heating Coil Inlet Heating Coil Outlet Zone Air
Hourly Analysis Program v4.61
Location
Dry-Bulb Temp (°C)
Specific Humidity (kg/kg)
Airflow (L/s)
CO2 Level (ppm)
Sensible Heat (W)
Latent Heat (W)
-
21.3 21.1 21.1 21.1 21.1
0.01092 0.01092 0.01092 0.01092 0.01092
0 1178 1178 1178 1178 1178
0 0 0 0 0
233 0 0
0 -
Page 5 of 5