Introduction
4
Industry leading energy saving
7
New intelligent VRF control
12
Industry leading pipe length for greater flexibility
15
Other features Outdoor units
17
Outdoor units line-up
19
Outdoor units specifications
21
Indoor units Indoor units line-up
27
4-way Air Discharge Cassette Type
28
Compact 4-way Cassette (600x600) Type
30
2-way Air Discharge Cassette Type
32
1-way Air Discharge Cassette Type
34
Concealed Duct Type Concealed Duct High Static Pressure Type
36 38
Slim Duct Type
40
Ceiling Type
42
High-wall Type (3 series) Floor Standing Concealed Type
44 45
Floor Standing Cabinet Type
46
BI-flow Console Type
47
Floor Standing Type AHU DX Connectivity Kit
48 49
Air to Air Heat Exchanger Air to Air Heat Exchanger with DX-coil & Humidifier Fresh Air Intake Indoor Unit Type
50 52 54
Mini-SMMS
56
Super Heat Recovery Multi System-i (SHRM-i)
58
SHRM-i Outdoor units lineup
60
Outdoor Units Specifications Refrigerant piping design
61 65
Indoor Units Accessories
68
Remote Controller
70
Central Controller
72
Advance Controller systems
74
Open Network systems
76
Application Controls
78
SMMS-i selection Tools
83
Conversion Table
85
3
44
5
Advancing the eco-evolution As relative newcomers in the evolution of the Earth, it’s undeniable that humankind has had a greater impact on our planet’s eco-system than any other life form. All organisms to some extent affect change on our global environment, but none quite as quickly and drastically as humans. Many scientists agree that human activity has accelerated pollution and climatic changes beyond the natural evolutionary process. Globally, levels of carbon dioxide and average regional temperatures rise at alarming rates, impacting nature and civilization. And the quality of air we breathe continues to deteriorate in the cities we live in. Whatever the causes, the message is clear: the future is up to us all, and we can do more to make things better. The core of Toshiba Air Conditioning’s philosophy is a profound respect for our global environment and the ionate pursuit toward improving the quality of life for our customers worldwide. As part of that global commitment, we develop cutting-edge technologies and advancements that serve the benefit of people everywhere, by offering an ideal balance of comfort and ecologically superior products. We advance R&D in the field of super energy-efficient, cleaner technologies and innovative products that not only use significantly less energy but help maintain air quality through state-of-the-art air purification systems for the home and business. We endeavour to lead by example by delivering the highest quality environmental systems that give added value, and contribute responsibly to the advancement of humankind. We call this vision, “Advancing the eco-evolution.”
Toshiba solutions Toshiba offers a solution for all applications: residential, light commercial and larger commercial buildings. Residential indoor units are designed to blend perfectly with all interiors and incorporate advanced filtration systems to deliver optimum indoor air quality. For small commercial premises, products are designed to deliver top performance combined with energy efficiency. For larger applications, VRF systems combine flexibility, energy efficiency and respect for the environment, with a wide choice of stylish indoor units.
Absolute comfort Toshiba’s commitment to society drives a company-wide focus on attention to the details through every stage of the development process, from design to field tests. Installations using our products and systems therefore feature a higher standard of indoor air quality, sound levels, energy savings, and environmental awareness.
55
66
5
Innovation The new SMMS-i offers innovations in every savings with highly efficient DC twin rotary compressors and advanced vector-controlled inverters boasting COP of 6.41* at 50% partial Load.
*8HP outdoor unit Calculated based on JRA4048:2006 specification.
Intelligence The intelligent VRF ensures precise control over cooling on a room by room basis, delivering consistent temperature to even the furthest room from the unit.
Imagination With flexible layout variations beyond imagination, this extremely versatile system can accomodate up to an impressive 235 metres in length and maximum height of 40 metres between indoor units.
7
6
Industry leading energy savings Energy-effient performance for greater eco-consciousness Adopting the highly efficient new DC twin-rotary compressors and advanced vectorcontrolled inverters realizes a COP of 6.41 (under 50% partial load). Greater operating performance is now possible when operating under a constant load.
2
3
4
5
6
7
6.41
4.52 COP 5.50 3.52
6.26 4.15 EER 5.60 3.28
DC Twin Rotary Compressor : Toshiba has continuously improved its compressor technology, arriving at a solution called DC Twin Rotary Compressor. It is a double cam rotary compressor which has several features which increases its performance and reliability. The opposed double blade design yields mechanical stability and less vibration that could cause stress on other components. In fact being able to reduce the rpm without causing instability enables improved temperature control when less capacity is required. An added benefit offered by the DC Twin rotary compressors, and with refrigerant R410a, is that it is more efficient than scroll compresors.
Twin Rotary Compressor Operation : • The compression ratio in the cylinder is variable • A change of the driving compression ratio of the outer refrigerant cycle • The compression ratio in the cylinder accords with driving compression ratio • Over compression and lack of compression are very small in the cylindersmall in the cylinder Thus resulting into Higher Efficiency.
New DC Twin-Rotary Compressor Three new DC Twin-Rotary compressors that feature outstanding capacity under partial load drive for 14HP and 16HP outdoor unit models, while two are used by other outdoor unit models ( 8HP-12HP).
8
refrigerant cycle • The compression ratio in the cylinder accords with driving compression ratio • Over compression and lack of compression are very small in the cylindersmall in the cylinder
5
Thus resulting into Higher Efficiency.
New DC Twin-Rotary Compressor Three new DC Twin-Rotary compressors that feature outstanding capacity under partial load drive for 14HP and 16HP outdoor unit models, while two are used by other outdoor unit models ( 8HP-12HP).
Industry leading energy savings Industry leading energy savings 7
Introducing high-performance outdoor units with 3 compressors and 3 inverters*1
2
1
(14HP, 16HP)
• Improved Motor Efficiency : Surface area of the rotor magnet (magnetic material Neodymium, Iron and Boron increased and the slits aded, resulting higher effiency.
Increase of magnetic flux densit
• Newly Designed Compression Path : The optimization of discharge port positioning reduces compression loss and dead volume, resulting into higher energy efficiency as well as comfort levels.
• More Precise Components :
• The Blade thickness is reduced. • The Back side are of blade is reduced. Which reduces the pressing load and friction resistance and helps to achieve bettor motor efficiency and higher product efficiency.
Fast-calculating vector-controlled inverter control over operation to match the
7
8
9
Variable compression ratio Toshiba twin rotary compressor have variable discharge pressure which minimising energy loss as compared to other compression tecnology e.g in below figure, Toshiba compressor deliver the capacity at that level where ever it is required.
0 degree opening
270 degree opening (Rated condition)
90 degree opening (Part load condition)
180 degree opening (Part load condition)
Fast-calculating vector-controlled inverter All-inverter control realizes finer control over operation to match the load on the system Toshiba SMMS-i leads the industry in controlling *1 all 3 compressors with a dedicated inverter board that taps the compressor’s full potential to provide smoother operation.
*1 14,16HP models
Smooth sine curve
Circuit board
The fast calculating vector controlled inverter produces a smooth sine curve that improves operating efficiency.
The vector controlled inverter quickly converts current into a smooth sine curve to achieve smoother operation of the compressor’s DC motor.
8
59
High-efficiency DC twin-rotary compressors Every outdoor unit incorporates three new DC twin-rotary compressors* and three inverter drives — this is unique to Toshiba and the air conditioning industry.
Vector-controlled inverter DC fan motor
Outdoor units are fitted with three DC twin-rotary compressors* (switch to all-inverter models)
* 14,16 HP Outdoor units
Reliability
Rotation between outdoor units
5
Compressor
Compressor
6
7
8
9
Compressor
4
C
Compressor
3
Compressor
As the compressors are all inverter driven, power surges are eliminated. Over or under-utilisation of power, typical for non-inverter compressors is eliminated, and there is no on/off power surge as the system adjusts to the demand required by the occupant or system. The use of inverter compressors reduces the risk of compressor failure, more common in standard non-inverter systems.
2
Compressor
1
B
Compressor
A (Header unit)
Compressor
With dual-rotation, the load is distributed more evenly — this means that the operating sequence of the outdoor units and the individual compressors is rotated to spread the operating hours more evenly.
Compressor
Sequencing of individual compressors
System with controlled reliability and savings Operate Operate
Conventional system
Operate
Stop
Energy savings During operation the system determines which heat exchanger can be used most efficiently and selects the compressor to deliver the power required. Inverter systems save energy as continuous operation offers the same capacity with lower power consumption. This benefits all occupants by maintaining even room temperatures, as well as the environment by reducing energy consumption.
ON
ON
1
2
Inverter Fixed-speed compressor compressor
OFF OFF 3
4
Fixed-speed Fixed-speed compressor compressor
ON
OFF
ON
OFF
1
2
3
4
Inverter Inverter compressor compressor
Inverter Inverter compressor compressor
Using greater heat exchanger volume is more efficient
Backup operation Incase of 1 system, 1 compressor broken, SMMSi can output 67% of capacity.
NO.1
NO.2
NO.3
heat exchangers
10
10
11
DC twin-rotary compressor advantage Each SMMS-i uses twin-rotary inverter compressors that feature more stable energy efficiency through their full range of compressor rotation than do scroll type compressors. Scroll compressors can achieve high- efficiency operation, but only within in a narrow range. As VRF systems require a wide range of capacity, the twin-rotary compressor is best suited for use. Run Time Equalization for compressors : The SMMS-i system’s operation combines a highly efficient running speed and highly efficient compressors. The operating time of the compressors is equalized. Under low-load conditions, there is the advantage of the system running at low capacity and yielding stable operation even under low temperature conditions. Inverter + Fixed Speed
All Inverter twin - rotary
Efficiency
Low efficiency in operation with FIX compressors.
System operates in high efficient compressor combination and rpm.
Reliability
Inverter compressor has to run all the time. Limited condition in compressor backup operation.
System operates in high efficient compressor combination and rpm.
Comfort
Output capacity fluctuation by fixed compressor ON/OFF operation.
Min. output can meet Min. capacity indoor units demand Stable operation in low temperature condition.
Active Oil Management system : As a system, it has more than 1 compressor. This running compressor can get oil and refrigerant from other compressor or modular quickly without any additional power consumption. Discharge
RUN Comp.1
Oil Flow
Comp.2
Discharge
Oil from other two compressors Oil Balance circuit
Comp.3
Stop Stop Oil tank
64 steps for condenser fan : reduced noise level : By making it possible to control the fan inverter in 64 steps, all the compressors can be run at low speeds, and the overall level of noise from the outdoor units is reduced approx by 10dB(A).
Outdoor noise (dB)
Time (h/year) 300 250 200
55 Auto silent operation
50
150 45
100
40
50
35
0 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38
Outdoor temperature °C
Approx. 10 dB (A)
10 12
5 Oversupplied
New intelligent VRF control Differing pipe lengths result in inconsistent performance levels when several indoor units are connected to a system. This imbalance is caused by pressure loss and thermal leaks that inhibit the supply of the right amount of refrigerant to each indoor unit.
Undersupplied Without intelligent VRF control
Total system control and consistent room-to-room temperature Intelligent VRF control provides precise control over each indoor unit. For example, the upper floor indoor units of VRF systems without intelligent of refrigerant, causing a delay before indoor units on lower floors would reach efficient operating levels. Toshiba’s SMMS-i monitors the flow of refrigerant to each indoor unit, while also tracking the model of the indoor unit, the pipe length between it and the outdoor unit, as well as data on operating conditions. The system computers the amount of refrigerant required by each indoor unit and controls the unit’s pulse motor valve to ensure optiomal supply across the system. Can be adjusted to maintain consistent temperature With intelligent VRF control
12
11 13
Infinity variable control Ultra-precise 0.1 Hz control over compressor rotation speed
Infinity variable control adjusts compressor rotation speed in near-seamless 0.1 Hz steps. Responding precisely to the capacity needs of the moment, this fine control minimizes energy loss when changing frequencies, and also creates a comfortable environment subject to minimal temperature variations.
d ’s W orl in* bestlass its c
SMMS-i Current-SMMS
New-SMMSi
Compressor Hz
0.1Hz
y
Capacit
*As of december 2009 (according to independent Toshiba testing)
Advanced “I/F” Technology : Microprocessor has been improved by replacing conventional single MCU with dual MCU system consisting of a main and a sub MCU, which significantly enhanced the capacity of the interface PC board (I/F). The dual MCU system enables high-speed operation by parallel processing and fast handling of a wide variety of capacity requirements from each indoor unit.
High speed data transmission - Operated control data in I/F is transmitted to four IPDUs at high speed so that excellent load following capability with finer capacity control is provided in no time. Ultra Precise “IPDU” technology - The intelligent power The intelligent power drive unit (IPDU) receives instructions from I/F and executes appropriate and precise control over all compressors and fans. RISC (a reduced instruction set computer which adopts simplified instructions to provide high-speed performance, for short, RISC) type 32bit U processor is introduced which enables amazing ultra precise drive control of 0.1 Hz per one step and realize stable temperature environment.
5
12 14
Optimal refrigerant control – When a multiple number of indoor units are connected, an insuficient or excess amount of refrigerant may be supplied to indoor units depending on the difference in length of the connection pipe from the outdoor unit. – This is caused by pressure loss and heat leaks as the refrigerant travels through the pipes, resulting in incorrect amounts of refrigerant being supplied to the indoor units. – Optimal refrigerant flow control featuring intelligent control over the refrigerant sensors and opening rate of individual pulse motor valves realizes stable indoor temperatures throughout a building with height differences of up to 40m between indoor units.
Outdoor unit
Pulse motor valve
D
Heat exchanger B
A
TC2 TCJ
C
Indoor unit
Refrigerant sensor (In)
Capacity
The surplus represented by (B) is diminished and the deficiency represented by (C) is compensated for.
TC1 Refrigerant sensor (Out)
The surplus represented by (A) is diminished and the deficiency represented by (D) is compensated for. Target capacity
(A)
(B)
(C)
(D)
14
13 15
Industry leading pipe length for greater flexibility Layout flexibility with few design limitations
System layouts can use a maximum equivalent distance of up to 235 metres. This makes
System layouts can use a maximumnyequivalent distance of up to 235 metres. This makes it much it much easier to design f small rooms, or for tenants who often easier to design for floors with many small rooms, or for tenants who often rearrange their floor rear ayouts. layouts.
175m
Current SMMS
coverage requires two systems
60 m
Conventional VRF
Farthest equivalent length
235m
d’s Wortl in * bes lass its c
*
Main piping length
120 m
SMMS-i coverage achieved by a single system
1st branching piping length
90 m
*As of December 2009 (According to independent TOSHIBA testing)
1416 16
5
Greater for height differences Toshiba SMMS-i leads the industry with for height differences of up to 40 meters between indoor units on a single system. For instance, in an 11-story building, this is enough height to fully cover the entire floor as well as the elevator halls.
----------------------- -------11F
10F 9F 8F Height between outdoor & indoor units *2
70m
Height between indoor units *1
40m
Single system
7F 6F 5F 4F 3F 2F
1F ----------------------
*1 Calculated at 3.5 meters per floor *2 40 meters incase of Indoor unit above outdoor unit
Piping
A change from T-shape to Y-shape branching ts on the gas pipes between SMMS-i outdoor units results in equalized flow to each branch that enables more reliable operation. To indoor units
Liquid piping To indoor units Gas piping Modification point
Outdoor unit connection piping kit (RBM-BT14E, RBM-BT24E)
1715
18
Other Features Outdoor unit
Refrigerant flow Gas refrigerant
Toshiba’s own PMV (pulse motor valve) control prevents unneeded refrigerant from flowing to indoor units that are not operating at any given time. Benefits include the prevention of by- loss and finer control over the compressor capacity of the outdoor unit.
Indoor unit
Heat exchanger
Max
Mid
Liquid refrigerant
Mini
Stop
PMV Temprerature sensor
Operating temperature range SMMS-i extends the high end of its cooling function’s outdoor temperature operating range up to 43°C. This enables wider applications and use of the system in hot regions.
SMMS-i Outdoor temp. range when cooling*
-5°C to 43°C
Outdoor temp. range when heating*
-20°C to 15°C
*Cooling: °CDB, Heating: °CWB
SMMS-i
-20°C
-15°C
0°C
15°C
Other features 519
16 18
Inverter box inspection window The SMMS-i inverter box window enables easier maintenance. The window opens quickly to allow inspection of the PCB, test run operations, repairs, and control over address settings.
Square carrying holes Square holes added to the lower corners of the SMMS-i outdoor units facilitate safer and surer lifting by a crane. Belts ed through the dedicated corner holes maintain their position and the balance of the load throughout the lifting operation.
17 19 20
Outdoor units Standard model
Capacity
5HP
6HP
8HP
10HP
M odel Name (M M Y-)
M AP0501HT8P-E
M AP0601HT8-PE
Cooling capacity (kW)
14.0
16.0
22.4
28.0
33.5
40.0
45.0
Heating capacity (kW)
16.0
18.0
25.0
31.5
37.5
45.0
50.0
14HP
M AP0804HT8P-E M AP1004HT8P-E M AP1204HT8P-E M AP1404HT8P-E
Capacity
18HP
20HP
22HP
24HP
M odel Name (M MY-)
AP1814HT8P-E
AP2014HT8P-E
AP2214HT8P-E
AP2414HT8P-E
Units in combination (M MY-)
12HP
26HP AP2614HT8P-E
16HP M AP1604HT8P-E
28HP
30HP
32HP
AP2814HT8P-E
AP3014HT8P-E
AP3214HT8P-E
M AP1004HT8P-E M AP1004HT8P-E M AP1204HT8P-E M AP1204HT8P-E M AP1604HT8P-E M AP1604HT8P-E M AP1604HT8P-E M AP1604HT8P-E M AP0804HT8P-E M AP1004HT8P-E M AP1004HT8P-E M AP1204HT8P-E M AP1004HT8P-E M AP1204HT8P-E M AP1404HT8P-E M AP1604HT8P-E
Cooling capacity (kW)
50.4
56.0
61.5
68.0
73.0
78.5
85.0
90.0
Heating capacity (kW)
56.5
63.0
69.0
76.5
81.5
88.0
95.0
100.0
Capacity
34HP
36HP
38HP
40HP
42HP
44HP
46HP
48HP
M odel Name (M MY-)
AP3414HT8P-E
AP3614HT8P-E
AP3814HT8P-E
AP4014HT8P-E
AP4214HT8P-E
AP4414HT8P-E
AP4614HT8P-E
Units in combination (M MY-)
AP4814HT8P-E
M AP1204HT8P-E M AP1204HT8P-E M AP1604HT8P-E M AP1604HT8P-E M AP1604HT8P-E M AP1604HT8P-E M AP1604HT8P-E M AP1604HT8P-E M AP1204HT8P-E M AP1204HT8P-E M AP1204HT8P-E M AP1204HT8P-E M AP1404HT8P-E M AP1604HT8P-E M AP1604HT8P-E M AP1604HT8P-E M AP1004HT8P-E M AP1204HT8P-E M AP1004HT8P-E M AP1204HT8P-E M AP1204HT8P-E M AP1204HT8P-E M AP1404HT8P-E M AP1604HT8P-E
Cooling capacity (kW)
96.0
101.0
106.5
112.0
118.0
123.5
130.0
135.0
Heating capacity (kW)
108.0
113.0
119.5
127.0
132.0
138.0
145.0
150.0
* Power: 3-phase 50 Hz 400V (380 - 415V) * The source voltage must not uctuate more than ±10% . * Rated conditions Cooling: Indoor air temperature 27°C DB/19°C WB, outdoor air temperature 35°C DB Heating: Indoor air temperature 20°C DB, outdoor air temperature 7°C DB/6°C WB
21
18 20
5
High efficiency model
Capacity
16HP
24HP
26HP
28HP
30HP
M odel Name (M MY-)
AP1624HT8P-E
AP2424HT8P-E
AP2624HT8P-E
AP2824HT8P-E
AP3024HT8P-E
Units in combination (M MY-)
M AP0804HT8P-E M AP0804HT8P-E
M AP0804HT8P-E M AP0804HT8P-E M AP0804HT8P-E
M AP1004HT8P-E M AP0804HT8P-E M AP0804HT8P-E
M AP1004HT8P-E M AP1004HT8P-E M AP0804HT8P-E
M AP1004HT8P-E M AP1004HT8P-E M AP1004HT8P-E
Cooling capacity (kW)
45.0
68.0
73.0
78.5
85.0
Heating capacity (kW)
50.0
76.5
81.5
88.0
95.0
Capacity
32HP
34HP
36HP
38HP
40HP
42HP
44HP
46HP
48HP
M odel Name (M MY-)
AP3224HT8P-E AP3424HT8P-E AP3624HT8P-E AP3824HT8P-E AP4024HT8P-E AP4224HT8P-E AP4424HT8P-E AP4624HT8P-E AP4824HT8P-E
Units in combination (M MY-)
MAP0804HT8P-E MAP0804HT8P-E MAP0804HT8P-E MAP0804HT8P-E
MAP1004HT8P-E MAP0804HT8P-E MAP0804HT8P-E MAP0804HT8P-E
MAP1004HT8P-E MAP1004HT8P-E MAP0804HT8P-E MAP0804HT8P-E
MAP1004HT8P-E MAP1004HT8P-E MAP1004HT8P-E MAP0804HT8P-E
MAP1004HT8P-E MAP1004HT8P-E MAP1004HT8P-E MAP1004HT8P-E
MAP1204HT8P-E MAP1004HT8P-E MAP1004HT8P-E MAP1004HT8P-E
MAP1204HT8P-E MAP1204HT8P-E MAP1004HT8P-E MAP1004HT8P-E
MAP1204HT8P-E MAP1204HT8P-E MAP1204HT8P-E MAP1004HT8P-E
MAP1204HT8P-E MAP1204HT8P-E MAP1204HT8P-E MAP1204HT8P-E
Cooling capacity (kW)
90.0
96.0
101.0
106.5
112.0
118.0
123.5
130.0
135.0
Heating capacity (kW)
100.0
108.0
113.0
119.5
127.0
132.0
138.0
145.0
150.0
Y-shape branching t
Branch headers
Outdoor unit connection piping kit
Appearance
(4-branch headers)
M odel name
RBM-BY55E RBM-BY105E RBM-BY205E RBM-BY305E RBM-HY1043E RBM-HY2043E RBM-HY1083E RBM-HY2083E
Max.4 branches Max.8 branches Total 14.2 Total 6.4 or Total below or more Total 25.2 Total 14.2 more and (Classi cation according to 6.4 and below or more Total below Total 14.2 or Total below or more indoor unit capacity code ) below 14.2 more and 25.2 14.2 and below 14.2 below 25.2 25.2 Usage
RBM -BT14E
RBM -BT24E
Total below 26.0
Total 26.0 or more
19 21
22
Outdoor unit specifications Standard model (Single unit)
Technical specifications
Equivalent HP Heat Pump Cooling Only
5HP 6HP 8HP 10HP 12HP 14HP 16HP (M MY-) MAP0501HT8P-E MAP0601HT8P-E MAP0804HT8P-E MAP1004HT8P-E MAP1204HT8P-E MAP1404HT8P-E MAP1604HT8P-E M odel name (M MY-) MAP0501T8P-E MAP0601T8P-E MAP0804T8P-E MAP1004T8P-E MAP1204T8P-E MAP1404T8P-E MAP1604T8P-E Outdoor unit type Inverter Cooling capacity (* 1) (kW) 14.0 16.0 22.4 28.0 33.5 40.0 45.0 Heating capacity (* 1) (kW) 16.0 18.0 25.0 31.5 37.5 45.0 50.0 2 Power supply (* ) 3phase 4wires 50Hz 400V (380-415V) 3.65 4.64 5.40 7.41 9.55 11.50 13.70 Power consumption (kW) Cooling 3.84 3.45 4.15 3.78 3.51 3.48 3.28 EER (Energy E ciency Ratio) Electrical characteristics Power consumption (kW) 3.84 4.56 5.53 7.50 10.20 11.20 14.20 Heating 1 (* ) 4.17 3.95 4.52 4.20 3.68 4.02 3.52 COP (Coe cient of Performance) External dimensions (Height /Width /Depth) (mm) 1,800 /990 /750 1,800 /990 /750 1,830 /990 /780 1,830 /990 /780 1,830 /990 /780 1,830 /1,210 /780 1,830 /1,210 /780 228 228 242 242 242 330 330 Heat Pump (kg) Total weight Cooling only (kg) 227 227 241 241 241 329 329 Compressor M otor output (kW) 1.1 x 2 1.4 x 2 2.3 x 2 3.1 x 2 4.2 x 2 3.0 x 3 3.6 x 3 M otor output (kW) 0.6 0.6 1.0 1.0 1.0 1.0 1.0 Fan unit Air volume (m3/h) 9,000 9,000 9,900 10,500 11,600 12,000 13,000 Gas side (mm) ø 15.9 ø 19.1 ø 22.2 ø 22.2 ø 28.6 ø 28.6 ø 28.6 M ain Refrigerant piping pipe Liquid side (mm) ø 9.5 ø 9.5 ø 12.7 ø 12.7 ø 12.7 ø 15.9 ø 15.9 diameter Balance pipe (mm) ø 9.5 ø 9.5 ø 9.5 ø 9.5 ø 9.5 ø 9.5 ø 9.5 Sound pressure level (Cooling/Heating) (dB(A)) 55 /55 56 /56 55 /56 57 /58 59 /62 60 /62 62 /64 Sound power level (Cooling/Heating) (dB(A)) — — 77 / 78 78 /79 82 /83 82 /83 83 /84
Standard model (Combination) M odel name
Equivalent HP Heat Pump Cooling Only
Technical specifications M MYM MY-
Outdoor unit type Heat Pump M MYOutdoor unit model Cooling Only M MY1 Cooling capacity (* ) (kW) (kW) Heating capacity (* 1) 2 Power supply (* ) Power consumption (kW) Cooling EER (Energy E ciency Ratio) Electrical 1 characteristics (* ) Power consumption (kW) Heating COP (Coe cient of Performance) Heat Pump (kg) Total weight Cooling only (kg) Compressor M otor output (kW) M otor output (kW) Fan unit Air volume (m3/h) Gas side (mm) Refrigerant piping M ain pipe diameter Liquid side (mm) Balance pipe (mm) Sound pressure level (Cooling/Heating) (dB(A))
18HP AP1814HT8P-E AP1814T8P-E MAP1004HT8P-E MAP0804HT8P-E MAP1004T8P-E MAP0804T8P-E 50.4 56.5
242 241 3.1 x 2 1.0 10,500
12.81 3.93 13.03 4.34
242 241 2.3 x 2 1.0 9,900
ø 28.6 ø 15.9 ø 9.5 59.5 /60.5
20HP AP2014HT8P-E AP2014T8P-E
22HP AP2214HT8P-E AP2214T8P-E
Inverter MAP1004HT8P-E MAP1004HT8P-E MAP1204HT8P-E MAP1004HT8P-E MAP1004T8P-E MAP1004T8P-E MAP1204T8P-E MAP1004T8P-E 56.0 61.5 63.0 69.0 3phase 4wires 50Hz 400V (380-415V) 14.82 16.96 3.78 3.63 15.00 17.70 4.20 3.90 242 242 242 242 241 241 241 241 3.1 x 2 3.1 x 2 4.2 x 2 3.1 x 2 1.0 1.0 1.0 1.0 10,500 10,500 11,600 10,500 ø 28.6 ø 34.9 ø 15.9 ø 19.1 ø 9.5 ø 9.5 60.0 /61.0 61.5 / 63.5
Standard model (Combination) M odel name
Equivalent HP Heat Pump Cooling Only
24HP AP2414HT8P-E AP2414T8P-E MAP1204HT8P-E MAP1204HT8P-E MAP1204T8P-E MAP1204T8P-E 68.0 76.5 19.66 3.46 21.13 3.62
242 242 241 241 4.2 x 2 4.2 x 2 1.0 1.0 11,600 11,600 ø 34.9 ø 19.1 ø 9.5 62.0 /65.0
Technical specifications M MYM MY-
Outdoor unit type Heat Pump M MYOutdoor unit model Cooling Only M MYCooling capacity (* 1) (kW) (kW) Heating capacity (* 1) Power supply (* 2) Power consumption (kW) Cooling EER (Energy E ciency Ratio) Electrical characteristics (* 1) Power consumption (kW) Heating COP (Coe cient of Performance) Heat Pump (kg) Total weight Cooling only (kg) Compressor M otor output (kW) M otor output (kW) Fan unit Air volume (m3/h) Gas side (mm) Refrigerant piping M ain pipe diameter Liquid side (mm) Balance pipe (mm) Sound pressure level (Cooling/Heating) (dB(A))
26HP AP2614HT8P-E AP2614T8P-E
28HP AP2814HT8P-E AP2814T8P-E Inverter MAP1604HT8P-E MAP1004HT8P-E MAP1604HT8P-E MAP1204HT8P-E MAP1604T8P-E MAP1004T8P-E MAP1604T8P-E MAP1204T8P-E 73.0 78.5 81.5 88.0 3phase 4wires 50Hz 400V (380-415V) 21.11 23.25 3.46 3.38 21.70 24.65 3.76 3.57 330 242 330 242 329 241 329 241 3.6 x 3 3.1 x 2 3.6 x 3 4.2 x 2 1.0 1.0 1.0 1.0 13,000 11,500 13,000 11,600 ø 34.9 ø 34.9 ø 19.1 ø 19.1 ø 9.5 ø 9.5 63.5 /65.0 64 /66.5
30HP AP3014HT8P-E AP3014T8P-E MAP1604HT8P-E MAP1404HT8P-E MAP1604T8P-E MAP1404T8P-E 85.0 95.0
330 329 3.6 x 3 1.0 13,000
25.20 3.37 25.40 3.74
ø 34.9 ø 19.1 ø 9.5 64.5 /66.5
330 329 3.0 x 3 1.0 12,000
20 22
23
Standard model M odel name
Equivalent HP Heat Pump Cooling Only
Technical specifications M MYM MY-
Outdoor unit type Heat Pump M MYOutdoor unit model Cooling Only M MY1 Cooling capacity (* ) (kW) 1 Heating capacity (* ) (kW) 2 Power supply (* ) Power consumption (kW) Cooling EER (Energy E ciency Ratio) Electrical 1 characteristics (* ) Power consumption (kW) Heating COP (Coe cient of Performance) Heat Pump (kg) Total weight Cooling only (kg) Compressor M otor output (kW) M otor output (kW) Fan unit Air volume (m3/h) Gas side (mm) Refrigerant piping M ain pipe diameter Liquid side (mm) Balance pipe (mm) Sound pressure level (Cooling/Heating) (dB(A))
32HP AP3214HT8P-E AP3214T8P-E
34HP 36HP AP3414HT8P-E AP3614HT8P-E AP3414T8P-E AP3614T8P-E Inverter MAP1604HT8P-E MAP1604HT8P-E MAP1204HT8P-E MAP1204HT8P-E MAP1004HT8P-E MAP1204HT8P-E MAP1204HT8P-E MAP1204HT8P-E MAP1604T8P-E MAP1604T8P-E MAP1204T8P-E MAP1204T8P-E MAP1004T8P-E MAP1204T8P-E MAP1204T8P-E MAP1204T8P-E 90.0 96.0 101.0 100.0 108.0 113.0 3phase 4wires 50Hz 400V (380-415V) 27.40 27.06 28.93 3.28 3.55 3.49 28.40 28.60 30.84 3.52 3.78 3.66 330 330 242 242 242 242 242 242 329 329 241 241 241 241 241 241 3.6 x 3 3.6 x 3 4.2 x 2 4.2 x 2 3.1 x 2 4.2 x 2 4.2 x 2 4.2 x 2 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 13,000 13,000 11,600 11,600 10,500 11,600 11,600 11,600 ø 34.9 ø 34.9 ø 41.3 ø 19.1 ø 19.1 ø 22.2 ø 9.5 ø 9.5 ø 9.5 65.0 /67.0 63.5 /66.0 64.0 /67.0
Standard model
Technical specifications
Equivalent HP Heat Pump Cooling Only
38HP AP3814HT8P-E AP3814T8P-E
40HP 42HP AP4014HT8P-E AP4214HT8P-E M MYM odel name M MYAP4014T8P-E AP4214T8P-E Outdoor unit type Inverter Heat Pump M MY- MAP1604HT8P-E MAP1204HT8P-E MAP1004HT8P-E MAP1604HT8P-E MAP1204HT8P-E MAP1204HT8P-E MAP1604HT8P-E MAP1404HT8P-E MAP1204HT8P-E Outdoor unit model Cooling Only M MY- MAP1604T8P-E MAP1204T8P-E MAP1004T8P-E MAP1604T8P-E MAP1204T8P-E MAP1204T8P-E MAP1604T8P-E MAP1404T8P-E MAP1204T8P-E 1 Cooling capacity (* ) (kW) 106.5 112.0 118.0 1 (kW) 119.5 127.0 132.0 Heating capacity (* ) 3phase 4wires 50Hz 400V (380-415V) Power supply (* 2) Power consumption (kW) 30.66 32.80 34.47 Cooling EER (Energy E ciency Ratio) 3.47 3.41 3.42 Electrical 1 characteristics (* ) Power consumption (kW) 32.14 35.29 35.46 Heating COP (Coe cient of Performance) 3.72 3.60 3.72 Heat Pump (kg) 330 242 242 330 242 242 330 330 242 Total weight Cooling only (kg) 329 241 241 329 241 241 329 329 241 Compressor M otor output (kW) 3.6 x 3 4.2 x 2 3.1 x 2 3.6 x 3 4.2 x 2 4.2 x 2 3.6 x 3 3.0 x 3 4.2 x 2 M otor output (kW) 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 Fan unit Air volume (m3/h) 13,000 11,600 10,500 13,000 11,600 11,600 13,000 12,000 11,600 Gas side (mm) ø 41.3 ø 41.3 ø 41.3 Refrigerant piping M ain pipe diameter Liquid side (mm) ø 22.2 ø 22.2 ø 22.2 Balance pipe (mm) ø 9.5 ø 9.5 ø 9.5 Sound pressure level (Cooling/Heating) (dB(A)) 65.0 /67.0 65.0 /67.5 65.5 /67.5
Standard model M odel name
Equivalent HP Heat Pump Cooling Only
Technical specifications M MYM MY-
Outdoor unit type Heat Pump M MYOutdoor unit model Cooling Only M MY1 Cooling capacity (* ) (kW) 1 (kW) Heating capacity (* ) 2 Power supply (* ) Power consumption (kW) Cooling EER (Energy E ciency Ratio) Electrical 1 characteristics (* ) Power consumption (kW) Heating COP (Coe cient of Performance) Heat Pump (kg) Total weight Cooling only (kg) Compressor M otor output (kW) M otor output (kW) Fan unit Air volume (m3/h) Gas side (mm) Refrigerant piping M ain pipe diameter Liquid side (mm) Balance pipe (mm) Sound pressure level (Cooling/Heating) (dB(A))
44HP AP4414HT8P-E AP4414T8P-E
46HP AP4614HT8P-E AP4614T8P-E Inverter MAP1604HT8P-E MAP1604HT8P-E MAP1204HT8P-E MAP1604HT8P-E MAP1604HT8P-E MAP1404HT8P-E MAP1604HT8P-E MAP1604T8P-E MAP1604T8P-E MAP1204T8P-E MAP1604T8P-E MAP1604T8P-E MAP1404T8P-E MAP1604T8P-E 123.5 130.0 138.0 145.0 3phase 4wires 50Hz 400V (380-415V) 36.95 38.90 3.34 3.34 38.85 39.60 3.55 3.66 330 330 242 330 330 330 330 329 329 241 329 329 329 329 3.6 x 3 3.6 x 3 4.2 x 2 3.6 x 3 3.6 x 3 3.0 x 3 3.6 x 3 1.0 1.0 1.0 1.0 1.0 1.0 1.0 13,000 13,000 11,600 13,000 13,000 12,000 13,000 ø 41.3 ø 41.3 ø 22.2 ø 22.2 ø 9.5 ø 9.5 66.0 /68.5 66.5 /68.5
*1 Rated conditions Cooling :Indoor air temperature 27°C DB/19°C WB, Outdoor air temperature 35°C DB Heating :Indoor air temperature 20°C DB, Outdoor air temperature 7°C DB/6°C WB The standard piping means that main pipe length is 5m, branching pipe length is 2.5m of branch piping connected with a 0meter height. *2 The source voltage must not ucture more than ±10% .
48HP AP4814HT8P-E AP4814T8P-E MAP1604HT8P-E MAP1604T8P-E 135.0 150.0 41.10 3.28 42.60 3.52 330 329 3.6 x 3 1.0 13,000 ø 41.3 ø 22.2 ø 9.5 67.0 /69.0
MAP1604HT8P-E MAP1604T8P-E
330 329 3.6 x 3 1.0 13,000
5
21 23
24 High efficiency model (Combination) M odel name
Equivalent HP Heat Pump Cooling Only
Technical specifications M MYM MY-
Outdoor unit type Heat Pump M MYOutdoor unit model Cooling Only M MY1 Cooling capacity (* ) (kW) (kW) Heating capacity (* 1) Power supply (* 2) Power consumption (kW) Cooling EER (Energy E ciency Ratio) Electrical characteristics (* 1) Power consumption (kW) Heating COP (Coe cient of Performance) Heat Pump (kg) Total weight Cooling only (kg) Compressor M otor output (kW) M otor output (kW) Fan unit Air volume (m3/h) Gas side (mm) Refrigerant piping M ain pipe diameter Liquid side (mm) Balance pipe (mm) Sound pressure level (Cooling/Heating) (dB(A))
16HP AP1624HT8P-E AP1624T8P-E
24HP 26HP AP2424HT8P-E AP2624HT8P-E AP2424T8P-E AP2624T8P-E Inverter M AP0804HT8P-E MAP0804HT8P-E MAP0804HT8P-E MAP0804HT8P-E MAP0804HT8P-E MAP1004HT8P-E MAP0804HT8P-E MAP0804HT8P-E MAP0804T8P-E MAP1004T8P-E MAP0804T8P-E MAP0804T8P-E MAP0804T8P-E MAP0804T8P-E MAP0804T8P-E MAP0804T8P-E 45.0 68.0 73.0 50.0 76.5 81.5 3phase 4wires 50Hz 400V (380-415V) 10.89 16.58 18.31 4.13 4.10 3.99 11.06 17.18 18.56 4.52 4.45 4.39 242 242 242 242 242 242 242 242 241 241 241 241 241 241 241 241 2.3 x 2 2.3 x 2 2.3 x 2 2.3 x 2 2.3 x 2 3.1 x 2 2.3 x 2 2.3 x 2 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 9,900 9,900 9,900 9,900 9,900 10,500 9,900 9,900 ø 28.6 ø 34.9 ø 34.9 ø 15.9 ø 19.1 ø 19.1 ø 9.5 ø 9.5 ø 9.5 58.0 /59.0 60.0 /61.0 60.5 /61.5
High efficiency model (Combination) M odel name
Equivalent HP Heat Pump Cooling Only
Technical specifications M MYM MY-
Outdoor unit type Heat Pump M MYOutdoor unit model Cooling Only M MY1 Cooling capacity (* ) (kW) (kW) Heating capacity (* 1) 2 Power supply (* ) Power consumption (kW) Cooling EER (Energy E ciency Ratio) Electrical 1 characteristics (* ) Power consumption (kW) Heating COP (Coe cient of Performance) Heat Pump (kg) Total weight Cooling only (kg) Compressor M otor output (kW) M otor output (kW) Fan unit Air volume (m3/h) Gas side (mm) Refrigerant piping M ain pipe diameter Liquid side (mm) Balance pipe (mm) Sound pressure level (Cooling/Heating) (dB(A))
28HP AP2824HT8P-E AP2824T8P-E
30HP 32HP AP3024HT8P-E AP3224HT8P-E AP3024T8P-E AP3224T8P-E Inverter MAP1004HT8P-E MAP1004HT8P-E MAP0804HT8P-E MAP1004HT8P-E MAP1004HT8P-E MAP1004HT8P-E MAP0804HT8P-E MAP0804HT8P-E MAP0804HT8P-E MAP1004T8P-E MAP1004T8P-E MAP0804T8P-E MAP1004T8P-E MAP1004T8P-E MAP1004T8P-E MAP0804T8P-E MAP0804T8P-E MAP0804T8P-E 78.5 85.0 90.0 88.0 95.0 100.0 3phase 4wires 50Hz 400V (380-415V) 20.27 22.75 21.79 3.87 3.74 4.13 20.53 22.71 22.12 4.29 4.18 4.52 242 242 242 242 242 242 242 242 242 241 241 241 241 241 241 241 241 241 3.1 x 2 3.1 x 2 2.3 x 2 3.1 x 2 3.1 x 2 3.1 x 2 2.3 x 2 2.3 x 2 2.3 x 2 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 10,500 10,500 9,900 10,500 10,500 10,500 9,900 9,900 9,900 ø 34.9 ø 34.9 ø 34.9 ø 19.1 ø 19.1 ø 19.1 ø 9.5 ø 9.5 ø 9.5 61.5 /62.5 62.0 / 63.0 61.0 /62.0
High efficiency model (Combination) M odel name
Equivalent HP Heat Pump Cooling Only
MAP0804HT8P-E MAP0804T8P-E
242 241 2.3 x 2 1.0 9,900
Technical specifications M MYM MY-
34HP AP3424HT8P-E AP3424T8P-E
36HP AP3624HT8P-E AP3624T8P-E
Outdoor unit type Inverter Heat Pump M MY- MAP1004HT8P-E MAP0804HT8P-E MAP0804HT8P-E MAP0804HT8P-E MAP1004HT8P-E MAP1004HT8P-E MAP0804HT8P-E MAP0804HT8P-E Outdoor unit model Cooling Only M MY- MAP1004T8P-E MAP0804T8P-E MAP0804T8P-E MAP0804T8P-E MAP1004T8P-E MAP1004T8P-E MAP0804T8P-E MAP0804T8P-E Cooling capacity (* 1) (kW) 96.0 101.0 1 (kW) 108.0 113.0 Heating capacity (* ) 2 3phase 4wires 50Hz 400V (380-415V) Power supply (* ) Power consumption (kW) 24.00 25.72 Cooling EER (Energy E ciency Ratio) 4.00 3.93 Electrical 1 characteristics (* ) Power consumption (kW) 24.70 26.06 Heating COP (Coe cient of Performance) 4.37 4.34 Heat Pump (kg) 242 242 242 242 242 242 242 242 Total weight Cooling only (kg) 241 241 241 241 241 241 241 241 Compressor M otor output (kW) 3.1 x 2 2.3 x 2 2.3 x 2 2.3 x 2 3.1 x 2 3.1 x 2 2.3 x 2 2.3 x 2 M otor output (kW) 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 Fan unit Air volume (m3/h) 10,500 9,900 9,900 9,900 10,500 10,500 9,900 9,900 Gas side (mm) ø 34.9 ø 41.3 Refrigerant piping M ain pipe diameter Liquid side (mm) ø 19.1 ø 22.2 Balance pipe (mm) ø 9.5 ø 9.5 Sound pressure level (Cooling/Heating) (dB(A)) 62.0 / 63.0 62.5 /63.5
22 24
25
High efficiency model (Combination) M odel name
Equivalent HP Heat Pump Cooling Only
Technical specifications M MYM MY-
38HP AP3824HT8P-E AP3824T8P-E
40HP AP4024HT8P-E AP4024T8P-E
Outdoor unit type Inverter Heat Pump M MY- MAP1004HT8P-E MAP1004HT8P-E MAP1004HT8P-E MAP0804HT8P-E MAP1004HT8P-E MAP1004HT8P-E MAP1004HT8P-E MAP1004HT8P-E Outdoor unit model Cooling Only M MY- MAP1004T8P-E MAP1004T8P-E MAP1004T8P-E MAP0804T8P-E MAP1004T8P-E MAP1004T8P-E MAP1004T8P-E MAP1004T8P-E Cooling capacity (* 1) (kW) 106.5 112.0 (kW) 119.5 127.0 Heating capacity (* 1) 3phase 4wires 50Hz 400V (380-415V) Power supply (* 2) Power consumption (kW) 27.68 29.64 Cooling EER (Energy E ciency Ratio) 3.85 3.78 Electrical characteristics (* 1) Power consumption (kW) 28.03 30.42 Heating COP (Coe cient of Performance) 4.26 4.17 Heat Pump (kg) 242 242 242 242 242 242 242 242 Total weight Cooling only (kg) 241 241 241 241 241 241 241 241 Compressor M otor output (kW) 3.1 x 2 3.1 x 2 3.1 x 2 2.3 x 2 3.1 x 2 3.1 x 2 3.1 x 2 3.1 x 2 M otor output (kW) 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 Fan unit 10,500 10,500 10,500 9,900 10,500 10,500 10,500 10,500 Air volume (m3/h) Gas side (mm) ø 41.3 ø 41.3 Refrigerant piping M ain pipe diameter Liquid side (mm) ø 22.2 ø 22.2 Balance pipe (mm) ø 9.5 ø 9.5 (dB(A)) 63.0 /64.0 63.0 /64.0 Sound pressure level (Cooling/Heating)
High efficiency model (Combination) M odel name
Equivalent HP Heat Pump Cooling Only
Technical specifications M MYM MY-
42HP AP4224HT8P-E AP4224T8P-E
M MYM MY-
46HP AP4624HT8P-E AP4624T8P-E
44HP AP4424HT8P-E AP4424T8P-E
Outdoor unit type Inverter Heat Pump M MY- MAP1204HT8P-E MAP1004HT8P-E MAP1004HT8P-E MAP1004HT8P-E MAP1204HT8P-E MAP1204HT8P-E MAP1004HT8P-E MAP1004HT8P-E Outdoor unit model Cooling Only M MY- MAP1204T8P-E MAP1004T8P-E MAP1004T8P-E MAP1004T8P-E MAP1204T8P-E MAP1204T8P-E MAP1004T8P-E MAP1004T8P-E Cooling capacity (* 1) (kW) 118.0 123.5 (kW) 132.0 138.0 Heating capacity (* 1) 3phase 4wires 50Hz 400V (380-415V) Power supply (* 2) Power consumption (kW) 32.04 34.19 Cooling EER (Energy E ciency Ratio) 3.68 3.61 Electrical characteristics (* 1) Power consumption (kW) 32.70 35.40 Heating COP (Coe cient of Performance) 4.04 3.90 Heat Pump (kg) 242 242 242 242 242 242 242 242 Total weight Cooling only (kg) 241 241 241 241 241 241 241 241 Compressor M otor output (kW) 4.2 x 2 3.1 x 2 3.1 x 2 3.1 x 2 4.2 x 2 4.2 x 2 3.1 x 2 3.1 x 2 M otor output (kW) 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 Fan unit Air volume (m3/h) 11,600 10,500 10,500 10,500 11,600 11,600 10,500 10,500 Gas side (mm) ø 41.3 ø 41.3 Refrigerant piping M ain pipe diameter Liquid side (mm) ø 22.2 ø 22.2 Balance pipe (mm) ø 9.5 ø 9.5 Sound pressure level (Cooling/Heating) (dB(A)) 64.0 /65.5 64.5 /66.5
High efficiency model (Combination) M odel name
Equivalent HP Heat Pump Cooling Only
Technical specifications 48HP AP4824HT8P-E AP4824T8P-E
Outdoor unit type Inverter Heat Pump M MY- MAP1204HT8P-E MAP1204HT8P-E MAP1204HT8P-E MAP1004HT8P-E MAP1204HT8P-E MAP1204HT8P-E MAP1204HT8P-E MAP1204HT8P-E Outdoor unit model Cooling Only M MY- MAP1204T8P-E MAP1204T8P-E MAP1204T8P-E MAP1004T8P-E MAP1204T8P-E MAP1204T8P-E MAP1204T8P-E MAP1204T8P-E Cooling capacity (* 1) (kW) 130.0 135.0 1 Heating capacity (* ) (kW) 145.0 150.0 2 3phase 4wires 50Hz 400V (380-415V) Power supply (* ) Power consumption (kW) 36.88 38.76 Cooling EER (Energy E ciency Ratio) 3.52 3.48 Electrical 1 characteristics (* ) Power consumption (kW) 38.57 40.80 Heating COP (Coe cient of Performance) 3.76 3.68 Heat Pump (kg) 242 242 242 242 242 242 242 242 Total weight Cooling only (kg) 241 241 241 241 241 241 241 241 Compressor M otor output (kW) 4.2 x 2 4.2 x 2 4.2 x 2 3.1 x 2 4.2 x 2 4.2 x 2 4.2 x 2 4.2 x 2 M otor output (kW) 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 Fan unit Air volume (m3/h) 11,600 11,600 11,600 10,500 11,600 11,600 11,600 11,600 Gas side (mm) ø 41.3 ø 41.3 Refrigerant piping M ain pipe diameter Liquid side (mm) ø 22.2 ø 22.2 Balance pipe (mm) ø 9.5 ø 9.5 Sound pressure level (Cooling/Heating) (dB(A)) 65.0 /67.5 65.0 /68.0
*1 Rated conditions Cooling :Indoor air temperature 27°C DB/19°C WB, Outdoor air temperature 35°C DB Heating :Indoor air temperature 20°C DB, Outdoor air temperature 7°C DB/6°C WB The standard piping means that main pipe length is 5m, branching pipe length is 2.5m of branch piping connected with a 0meter height. *2 The source voltage must not ucture more than ±10% .
5
23 25
26 Model : MMY-MAP0501, MAP0601 (SMMS) Mounting surface of bottom plate
990
755 (Anchor bolt pitch)
630 80
610
4-15x20 (Long hole)
100
700 (Anchor bolt hole pitch)
Foundation
80
100
B ø9.5 ø9.5
790 (Including steady leg)
A ø15.9 ø15.9
750 755 (Anchor bolt pitch)
Applied model MMY-MAP0501 MMY-MAP0601
Foundation
165
700 (Anchor bolt hole pitch)
1800
1640
280
Refrigerant pipe connecting port (Gas side) A
280
88
*1 241
700
Refrigerant pipe connecting port (Liquid side)B
Balance pipe connecting port
2-60x150 square hole (for freight handling)
500
9.5
*1 Cutting position of L-shape pipe when pipe at gas side is connected (Recommended pipe connecting position)
(Note) 1. If there is an obstacle at the upper side of the outdoor unit, set the top end of the outdoor unit 2000mm apart from the obstacle. 2. Limit the height of the obstacle surrounding the outdoor unit to 800mm or less from the bottom end of the outdoor unit. 3. Draw out the pipe procured locally to the front of the outdoor unit horizontally and keep 500mm or more between the outdoor unit and traversing pipe if placing pipe transversely.
(Unit: mm)
Model: MMY-MAP0804, MAP1004, MAP1204
100
Foundation
50
700 (Anchor bolt hole pitch)
Foundation
755 (Anchor bolt pitch)
60 670
100 610
4-15x20 (Long hole)
990
60
700
(Anchor bolt hole pitch)
790 (Including steady leg)
755 (Anchor bolt pitch)
C 1,830 1,800
780
Mounting surface of bottom plate
B ø12.7 ø12.7 ø12.7
1595
(75)*1
2-60x200 square hole (for freight handling )
500 Balance pipe connecting port 9.5
(220)*1
273 284
687
Applied model MMY-MAP ∗∗∗-E Other models
A ø22.2 ø22.2 ø28.6
C
Applied model MMY-MAP0804 MMY-MAP1004 MMY-MAP1204
L-shape pipe Refrigerant pipe connecting port (Gas side)A Refrigerant pipe connecting port (Liquid side) B
(Note) 1. If there is an obstacle at the upper side of the outdoor unit, *1 Recommended cutting set the top end of the outdoor unit 2000mm apart from the obstacle. position of L-shape pipe 2. Limit the height of the obstacle surrounding the outdoor unit to 800mm or less from the bottom end of the outdoor unit. 3. Draw out the pipe procured locally to the front of the outdoor unit horizontally and keep 500mm or more between the outdoor unit and traversing pipe if placing pipe transversely.
(Unit: mm)
24
275
26
Model: MMY-MAP1404, MAP1604
100
1210
Foundation
1595
50
920 (Anchor bolt hole pitch)
Foundation
755 (Anchor bolt pitch)
60 670
610
920 (Anchor bolt hole pitch)
60
4-15x20 (Long hole)
780 790 (Including steady leg)
755 (Anchor bolt pitch)
C 1,830 1,800
100
Mounting surface of bottom plate
B ø15.9 ø15.9
2-60x200 square hole (for freight handling)
620 Balance pipe connecting port 9.5
284
(220)*1
221
687
(75)*1
85
Applied model MMY-MAP ∗∗∗-E Other models
A ø28.6 ø28.6
C
Applied model MMY-MAP1404 MMY-MAP1604
L-shape pipe Refrigerant pipe connecting port (Gas side) 28.6 Refrigerant pipe connecting port
(Liquid side) 15.9 (Note) 1. If there is an obstacle at the upper side of the outdoor unit, set the top end of the outdoor unit 2000mm apart from the obstacle. *1 Recommended cutting 2. Limit the height of the obstacle surrounding the outdoor unit to position of L-shape pipe 800mm or less from the bottom end of the outdoor unit. 3. Draw out the pipe procured locally to the front of the outdoor unit horizontally and keep 500mm or more between the outdoor unit and traversing pipe if placing pipe transversely.
(Unit: mm)
27 29
VRF Indoor Units Range Type
4-way air discharge cassette type
Compact 4-way cassette (600 x 600) type
2-way air discharge cassette type
1-way air discharge cassette type
Concealed duct type
Concealed duct high static pressure type
Slim duct type
Ceiling type - 7 series
Model Name
Equivalent HP
Cooling Heating capacity (kW) capacity (kW)
MMU-AP0094HP-E MMU-AP0124HP-E MMU-AP0154HP-E MMU-AP0184HP-E MMU-AP0244HP-E MMU-AP0274HP-E MMU-AP0304HP-E MMU-AP0364HP-E MMU-AP0484HP-E MMU-AP0564HP-E
1.00 1.25 1.70 2.00 2.50 3.00 3.20 4.00 5.00 6.00
2.80 3.60 4.50 5.60 7.10 8.00 9.00 11.20 14.00 16.00
3.20 4.00 5.00 6.30 8.00 9.00 10.00 12.50 16.00 18.00
MMU-AP0074MH-E MMU-AP0094MH-E MMU-AP0124MH-E MMU-AP0154MH-E MMU-AP0184MH-E
0.80 1.00 1.25 1.70 2.00
2.20 2.80 3.60 4.50 5.60
2.50 3.20 4.00 5.00 6.30
MMU- AP0072WH MMU-AP0092WH MMU-AP0122WH MMU-AP0152WH MMU-AP0182WH MMU-AP0242WH MMU-AP0272WH MMU-AP0302WH MMU-AP0362WH MMU-AP0482WH MMU-AP0562WH
0.80 1.00 1.25 1.70 2.00 2.50 3.00 3.20 4.00 5.00 6.00
2.20 2.80 3.60 4.50 5.60 7.10 8.00 9.00 11.20 14.00 16.00
2.50 3.20 4.00 5.00 6.30 8.00 9.00 10.00 12.50 16.00 18.00
MMU-AP0074YH-E MMU-AP0094YH-E MMU-AP0124YH-E
0.80 1.00 1.25
2.20 2.80 3.60
2.50 3.20 4.00
MMU-AP0154SH-E MMU-AP0184SH-E MMU-AP0244SH-E
1.70 2.00 1.25
4.50 5.60 7.10
5.00 6.30 8.00
Air-to-Air Heat Exchangers
MMD-AP0076BHP-E MMD-AP0096BHP-E MMD-AP0126BHP-E MMD-AP0156BHP-E MMD-AP0186BHP-E MMD-AP0246BHP-E MMD-AP0276BHP-E MMD-AP0306BHP-E MMD-AP0366BHP-E MMD-AP0486BHP-E MMD-AP0566BHP-E
0.80 1.00 1.25 1.70 2.00 2.50 3.00 3.20 4.00 5.00 6.00
2.20 2.80 3.60 4.50 5.60 7.10 8.00 9.00 11.20 14.00 16.00
2.50 3.20 4.00 5.00 6.30 8.00 9.00 10.00 12.50 16.00 18.00
Air-to-Air Heat Exchangers with DX-coil + Humidifier
MMD-AP0184H-E MMD-AP0244H-E MMD-AP0274H-E MMD-AP0364H-E MMD-AP0484H-E MMD-AP0724H-E MMD-AP0964H-E
2.00 2.50 3.00 4.00 5.00 8.00 1.000
5.60 7.10 8.00 11.20 14.00 22.40 28.00
6.30 8.00 9.00 12.50 16.00 25.00 31.50
MMD-AP0054SPH-E MMD-AP0074SPH-E MMD-AP0094SPH-E MMD-AP0124SPH-E MMD-AP0154SPH-E MMD-AP0184SPH-E MMD-AP0244SPH-E MMD-AP0274SPH-E
0.6 0.80 1.00 1.25 1.70 2.00 2.50 3.00
2.20 2.20 2.80 3.60 4.50 5.60 7.10 8.00
2.50 2.50 3.20 4.00 5.00 6.30 8.00 9.00
MMC-AP0157HP-E MMC-AP0187HP-E MMC-AP0247HP-E MMC-AP0277HP-E MMC-AP0367HP-E MMC-AP0487HP-E MMC-AP0567HP-E
1.70 2.00 2.50 3.00 4.00 5.00 6.00
4.50 5.60 7.10 8.00 11.20 14.00 16.00
5.00 6.30 8.00 9.00 12.50 16.00 18.00
Model Name
Equivalent HP
MMK-AP0073H MMK-AP0093H MMK-AP0123H MMK-AP0153H MMK-AP0183H MMK-AP0243H
0.80 1.00 1.25 1.70 2.00 2.50
2.20 2.80 3.60 4.50 5.60 7.10
2.50 3.20 4.00 5.00 6.30 8.00
MML-AP0074H-E MML-AP0094H-E MML-AP0124H-E MML-AP0154H-E MML-AP0184H-E MML-AP0244H-E
0.80 1.00 1.25 1.70 2.00 2.50
2.20 2.80 3.60 4.50 5.60 7.10
2.50 3.20 4.00 5.00 6.30 8.00
Bi Flow Console type
MML-AP0074NH-E MML-AP0094NH-E MML-AP0124NH-E MML-AP0154NH-E MML-AP0184NH-E
0.80 1.00 1.25 1.70 2.00
2.20 2.80 3.60 4.50 5.60
2.50 3.20 4.00 5.00 6.30
Floor standing concealed type
MML-AP0074BH-E MML-AP0094BH-E MML-AP0124BH-E MML-AP0154BH-E MML-AP0184BH-E MML-AP0244BH-E
0.80 1.00 1.25 1.70 2.00 2.50
2.20 2.80 3.60 4.50 5.60 7.10
2.50 3.20 4.00 5.00 6.30 8.00
Floor standing type
MMF-AP0154H-E MMF-AP0184H-E MMF-AP0244H-E MMF-AP0274H-E MMF-AP0364H-E MMF-AP0484H-E MMF-AP0564H-E
1.70 2.00 2.50 3.00 4.00 5.00 6.00
4.50 5.60 7.10 8.00 11.20 14.00 16.00
5.00 6.30 8.00 9.00 12.50 16.00 18.00
Type
High wall type 3 series
Floor standing cabinet type
VN-M150HE VN-M250HE VN-M350HE VN-M500HE VN-M650HE VN-M800HE VN-M1000HE VN-M1500HE VN-M2000HE
Air Flow in CMH 150 250 350 500 650 800 1000 1500 2000
MMD-VN(K)502HEXE MMD-VN(K)802HEXE MMD-VN(K)1002HEXE
Air Flow in CMH 500 800 950
New AHU DX Coil Interface
MM-DXC010 MM-DXC012
AHU DX Valve Kit
MM-DXV080 MM-DXV140 MM-DXV280
Fresh air intake indoor unit type
Cooling Heating capacity (kW) capacity (kW)
MMD-AP0481HFE MMD-AP0721HFE MMD-AP0961HFE
5.00 8.00 10.00
14.20 22.40 28.00
8.90 13.90 17.40
5
30 28
4-way Air Discharge Cassette Type Individual louver control The angles of each of the four louver can be set individually * Enables airflow to be adapted to preferences. Condensate drain pump included. (1) Standard swing
(2) Diagonally opposite swing
(3) Turn-around swing
Easy installation
MMU-AP*** 4HP
The is attached using the bolt already installed on the indoor unit.
REMOTE CONTROLS
RBC-U31PGP(W)-E RBC-AX32U(W)-E RBC-AX32U(WS)-E
RBC-AMS41E
RBC-AMS51E
Technical specifications Model name
MMU
Cooling/Heating capacity*1
(kW)
Electrical characteristics
3.6/4.0
External dimensions: Width Main unit (Ceiling )* Depth
Total weight: Main unit (Ceiling )* Standard air flow (High/Mid/Low) Motor output Gas side
0.021/0.021
5.6/6.3
0.023/0.023 0.026/0.026
Model
7.1/8.0
8.0/9.0
9.0/10.0
11.2/12.5
14.0/16.0
16.0/18.0
0.036/0.036
319 (30)*
256 (30)*
(mm)
840 (950)*
(mm)
840 (950)*
(kg)
18 (4)*
(m3/h)
800/730/680
(W) (mm) (mm)
Drain port
(nominal dia.) (dB(A))
0.043/0.043 0.088/0.088 0.112/0.112 0.112/0.112
RBC-U31PGP(W)-E/RBC-U31PGSP(W)-E*/RBC-U31PGSP(WS)-E* (Thailand)
(mm)
Liquid side
Sound pressure level*2 (High/Mid/Low)
4.5/5.0
1-phase 50 Hz 230 V (220–240 V)/1-phase 60 Hz 220 V (Separate power supply for indoor units required.)
Power consumption 50 Hz/60 Hz (kW)
Height
Connecting pipe
2.8/3.2
Power requirements
Appearance (Ceiling )
Fan unit
AP0094HP-E AP0124HP-E AP0154HP-E AP0184HP-E AP0244HP-E AP0274HP-E AP0304HP-E AP0364HP-E AP0484HP-E AP0564HP-E
25 (4)*
20 (4)* 930/830/790 1050/920/800
1290/920/800
14 ø9.5
1320/1110/850 1970/1430/1070 2130/1430/1130 2130/1520/1230
20
68
ø12.7
72
ø15.9
ø6.4
ø9.5 25 (Polyvinyl chloride tube)
30/29/27
31/29/27
32/29/27
35/31/28
38/33/30
* Preliminary *Figures in parentheses are for ceiling s. *1 This reference piping consists of 5 m of main piping and 2.5 m of branch piping connected at the same height level. *2 The actual values in an external operating environment are generally higher than the indicated values due to the contribution from ambient noise.
43/38/32
46/38/33
46/40/33
29
MMU-AP0094HP to MMU-AP0564HP Wireless sensor mounting section (RBC-AX31U can be connected four corners)
323
269
Knockout for fresh air intake ф100 416.5 ° 45 690± 20 Hanging bolt pitch
860 to 910 ceiling open dimension For branch duct knockout square hole ф150 (Also located on the back)
Bottom face of ceiling
129
16.5
Drain pipe connecting port
Ceiling (Sold separately)
41.5
105
106.5 Refrigerant pipe connecting port (Liquid side)
157 397.5
112
189
337.5
Refrigerant pipe connecting port (Gas side)
72
263
*(319) 256
*(137)
351
77 105 74
35
105
101 120 30
Stand-up 850 or less
Stand-up 661 or less
*(183)
300 or less
384
163.5 256.5
223.5
132
480
196.5
Hanging bolt M10 or W3/8 procured locally
172
950 external dimension
*( ): AP0364 to AP0564
Check port ( 450)
44
Z Z View
200
860 to 910 ceiling open dimension
64
15 5
Bottom face of ceiling
950 external dimension
57
18 7
.5 28
32
780 Hanging bolt pitch
61
Air outlet 518
Electric parts box
408
30
Wiring connection port
For branch duct knockout square hole ф150
Bottom face of ceiling Drain standing-up size
*The figure shows the RBC-U31PG(W)-E
(Unit: mm)
Options Air discharge direction kit
Auxiliary fresh air flange TCB-FF101URE2
Fresh air filter chamber TCB-BC1602UE
TCB-GFC1602E
Fresh air inlet box TCB-GB1602UE2
Ceiling RBC-U31PG(W)-E RBC-U31PGS(W)-E* RBC-U31PGS(WS)-E*
Spacer for height adjustment TCB-SP1602UE
Air inlet grill
5
32 30
Compact 4-way Cassette (600 x 600) Type Perfect for grid system ceiling
Designed for simple & easy installation and maintenance
This compact unit (575 × 575 mm) fits perfectly into ceilings and matches standard architectural modules, without the need to cut ceiling tiles.
The slim design is only 268 mm in height even when an electrical box is located inside the unit. Easy installation is also possible using the adjust pocket. Use the “adjust pocket” function for fine adjustments after installation.
The flaps fold tightly against the ceiling when operation stops so that the ceiling is affected only slightly even if air conditioning is installed.
MMU-AP***4MH-E
Available for ceilings up to 3.5 m in height.
Condensate drain pump included.
The drain-checking hole makes it possible to check the drain pan through the side case.
RBC-UM11PG(W)E 3.5m
Drain-checking hole TCB-AX32E2
RBC-AMS41E
Maximum height
RBC-AMS51E
Technical specifications Model name
MMU
AP0074MH-E
AP0094MH-E
AP0124MH-E
AP0154MH-E
AP0184MH-E
Cooling/Heating capacity*1
(kW)
2.2/2.5
2.8/3.2
3.6/4.0
4.5/5.0
5.6/6.3
Electrical characteristics
Power consumption 50 Hz/60 Hz (kW)
Appearance (Ceiling ) Height
External dimensions: Width Main unit (Ceiling )* Depth
Total weight: Main unit (Ceiling )* Fan unit
Standard air flow (High/Mid/Low) Motor output Gas side
Connecting pipe
1-phase 50 Hz 230 V (220–240 V)/1-phase 60 Hz 220 V (Separate power supply for indoor units required.)
Power requirements
0.034/0.034
0.036/0.036
0.038/0.038
Model
RBC-UM11PG(W)-E
(mm)
268 (27)*
(mm)
575 (700)*
(mm)
575(700)*
552/462/378
570/468/378
(W)
594/504/402
762/642/522
ø9.5
ø12.7
(mm)
ø6.4
Drain port
(nominal dia.)
25 (Polyvinyl chloride tube)
(dB(A))
660/552/468
60
(mm)
Liquid side
Sound pressure level*2 (High/Mid/Low)
0.052/0.052
17 (3)*
(kg) (m3/h)
0.041/0.041
36/32/28
37/33/28
37/33/29
*Figures in parentheses are for ceiling s. *1 This reference piping consists of 5 m of main piping and 2.5 m of branch piping connected at the same height level. *2 The actual values in an external operating environment are generally higher than the indicated values due to the contribution from ambient noise.
40/35/30
44/39/34
33 31
MMU-AP0074MH-E to MMU-AP0184MH-E
235 235
207 207
575 575
Ceilingopen open dimension dimension 595 Ceiling 595toto660 660
Indoor
Indoor unit unit
Bottom of ceiling Bottomface face of ceiling
Ceiling open 595595 to 660 Ceiling opendimension dimension to 660 external external dimension 700700 dimension Hanging bolt or W3/8 procured locallylocally Hanging boltM10 M10 or W3/8 procured
For ductknockout knockout Forbranch branch duct square φ150 square hole hole ф150
158 158
120 120 142 142
268 268
63 63 21 21
Bottom of of ceiling Bottomface face ceiling 27 27
Wiring port Wiringconnection connecting port
Drain pipe pipe connecting port Drain connecting port
20.5 220.5
256 256 ф162 φ162
145.5 145.5
105 105 148 148
134 134
215 214 42 42
55 55
97.5 97.5 93 105 105 70 70 93
300 300
Ceilingopen open dimension dimension 595 Ceiling 595toto660 660
Hanging bolt 525 Hanging boltpitch pitch 525
Refrigerant pipe Refrigerant pipe connecting port connecting port (Liquid side) (Liquid side)
190.5 190.5
Checkport port Check (( 450) 450)
64 142 142 64
177 177
Refrigerant pipe Refrigerant pipe connecting port connecting port (Gas side) (Gas side)
139.5 139.5
175 175 149 149
64 64
29 29
368.5 368.5
320.5 320.5
575 575
Hanging bolt pitch 525 525 Hanging bolt pitch
Electric boxbox Electriarts parts
external 700 700 externaldimension dimension
Bottom of of ceiling Bottomface face ceiling
Ceiling open 595595 to 660 Ceiling opendimension dimension to 660
Knockout for fresh airintake intake φ100 ф100 air
Stand-up Stand-up 629.5 629.5 or or less less
105 105
235 235
Stand-up 850 less Stand-up 850oror less
ф162 φ162
200 200
For ductknockout knockout For branch branch duct square hole square holeф150 φ150
145.5 145.5
70 105 93 93 70 105
Bottom of ceiling Bottomface face of ceiling
Ceiling (sold separately) Ceiling (sold separately)
(Unit:(Unit: mm) mm)
Options
Auxiliary fresh air flange TCB-FF101URE2
Ceiling RBC-UM11PG(W)E
5
34 32
2-way Air Discharge Cassette Type Slim and compact unit
Unified the width of ceiling s, 680mm. Available for ceilings up to 3.8m in height. (in case of 0.8HP to 3.2HP) Easy installation and fine adjustment using the “Adjust-Cover” function. Condensate drain pump included.
MMU-AP***2WH
REMOTE CONTROLS
RBC-AX23UW(W)-E
RBC-AMS41E
RBC-AMS51E
Technical specifications Model name
MMU
Cooling/Heating capacity*1
(kW)
Electrical characteristics
2.2/2.5
3.6/4.0
2.8/3.2
(kW)
0.029/0.029
Model
RBC-UW283PG(W)-E
Height External dimensions: Width Main unit (Ceiling )* Depth
(mm)
295 (20)
(mm)
815 (1050)
Fan unit
Standard air flow (High/Mid/Low) Motor output Gas side
Connecting pipe
7.1/8.0
8.0/9.0
9.0/10.0
11.2/12.5
14.0/16.0
16.0/18.0
(mm)
Drain port
(nominal dia.) (dB(A))
RBC-UW1403 345 (20)
1180 (1415)
19 (10)
1600 (1835)
20
30
ø9.5
36 (14)
26 (14) 600/534/450 900/750/618
558/498/450
(W) (mm)
0.064/0.064 0.076/0.076 0.088/0.088 0.117/0.117
570 (680)
(kg) (m3/h)
0.054/0.054 RBC-UW803PG(W)-E
(mm)
Liquid side
Sound pressure level*2 (High/Mid/Low)
5.6/6.3
0.030/0.030 0.044/0.044
Appearance (Ceiling )
Total weight: Main unit (Ceiling )*
4.5/5.0
1-phase 50Hz 230V (220-240V)/1-phase 60Hz 220V (Separate power supply for indoor units required)
Power requirements Power consumption 50 Hz/60 Hz
AP0072WH AP0092WH AP0122WH AP0152WH AP0182WH AP0242WH AP0272WH AP0302WH AP0362WH AP0482WH AP0562WH
1050/840/738
1260/900/780 1740/1434/1182 1800/1482/1230 2040/1578/1320
40
50
ø12.7
70 ø15.9
ø6.4
ø9.5 25 (Polyvinyl chloride tube)
34/32/30
35/33/30
38/35/33
*Figures in parentheses are for ceiling s. *1 This reference piping consists of 5 m of main piping and 2.5 m of branch piping connected at the same height level. *2 The actual values in an external operating environment are generally higher than the indicated values due to the contribution from ambient noise.
40/37/34
42/39/36
43/40/37
46/42/39
33
MMU-AP0072WH to AP0152WH Hanging bolt 4-M10 procured locally
Adjust cover
Wireless sensor mounting section
295
151
20
77 Bottom face Ceiling (sold separetely) of ceiling
880 Hanging bolt pitch 1000~1010 Ceiling open dimension 1050 external dimension
Refrigerant pipe connecting port (Liquid side) Refrigerant pipe connecting port (Gas side)
185
570 137.5 147.5 95 190 80 20
189
850 or less
609 or less
300 or less
Drain pipe connecting port 241
380 Hanging bolt pitch
680 ceiling open dimension
680 external dimension
815
103
Electric parts box
Power supply Knockout hole for auxiliary connecting port fresh air intake flange (only at reverse side)
ceiling Drain standing-up size
(Unit: mm)
MMU-AP0182WH to AP0302WH Adjust cover
345
570 137.5 147.5 95 190 185 80 20
Refrigerant pipe connecting port (Liquid side) Refrigerant pipe connecting port (Gas side)
Drain pipe connecting port
242
850 or less
559 or less
300 or less
ceiling
Knockout hole for auxiliary fresh air intake flange (Only at reverse side)
Drain standing-up size
291
Ceiling (sold separetely)
103
Bottom face of ceiling
20
151
77 1245 Hanging bolt pitch 1365~1357 Ceiling open dimension 1415 external dimension
Wireless sensor mounting section
Hanging bolt 4-M10 procured locally
1180
380 Hanging bolt pitch
620 Ceiling open dimension
680 external dimension
Electric parts box
Power supply connecting port
(Unit: mm)
MMU-AP0362WH to AP0562WH Adjust cover
Wireless sensor mounting section
Electric parts box
20 ceiling Drain standing-up size
570 137.5 147.5 95 190 185 80 20
Drain pipe connecting port
Refrigerant pipe connecting port (Gas side)
Knockout hole for auxiliary fresh air intake flange (Only at reverse side)
291
Refrigerant pipe connecting port (Liquid side)
103
300 or less
242
Ceiling (sold separetely)
850 or less
Bottom face of ceiling
559 or less
1835 external dimension
255
151
77 1665 Hanging bolt pitch 1785~1795 Ceiling open dimension
345
Hanging bolt 4-M10 procured locally
120 120
380 Hanging bolt pitch
620 Ceiling open dimension
680 external dimension
1600
Power supply connecting port
(Unit: mm)
Options
Ceiling RBC-UW283PG(W)-E RBC-UW803PG(W)-E RBC-UW1403PG(W)-E
Filter chamber TCB-FC283UW-E TCB-FC803UW-E TCB-FC1403UW-E Super long life filter TCB-LF283UW-E TCB-LF803UW-E TCB-LF1403UW-E
Auxiliary fresh air flange TCB-FF151US-E
5
36 34
1-way Air Discharge Cassette Type The perfect choice for hotels and reception areas
Fresh air intake is possible
Silent sound design ensures the quiet required for the office.
Preparations/connection possible with a circle duct flange.
Ideal for smaller rooms where one-way air distribution is required. Able to blow air straight out. MMU-AP***4YH-E MMU-AP***4SH-E
Condensate drain pump included. Long-life filters fitted as standard.
* The photo shows the MMU-AP***4SH-E Series.
REMOTE CONTROLS
RBC-AX32CE2
RBC-AMS41E
RBC-AMS51E Technical specifications
Model name
MMU
AP0074YH-E
AP0094YH-E
AP0124YH-E
AP0154SH-E
AP0184SH-E
AP0244SH-E
Cooling/Heating capacity*1
(kW)
2.2/2.5
2.8/3.2
3.6/4.0
4.5/5.0
5.6/6.3
7.1/8.0
Electrical characteristics
Power requirements Power consumption 50 Hz/60 Hz
1-phase 50 Hz 230 V (220–240 V)/1-phase 60 Hz 220 V (Separate power supply for indoor units required.) 0.042/0.041
5.6/6.3
(kW)
0.053/0.056
Appearance (Ceiling )
Model
RBC-UY136PG
Height External dimensions: Width Main unit (Ceiling )* Depth
(mm)
235 (18)*
200 (20)*
(mm)
850 (1050)*
1000 (1230)*
(mm)
850 (1050)*
710 (800)*
(kg)
22 (3.5)*
(m3/h)
540/480/420
(W)
22
Gas side
(mm)
ø9.5
Liquid side
(mm)
Drain port
(nominal dia.)
Total weight: Main unit (Ceiling )* Fan unit
Standard air flow (High/Mid/Low) Motor output
Connecting pipe
Sound pressure level*2 (High/Mid/Low)
(dB(A))
7.1/8.0
RBC-US21PGE
21 (5.5)* 750/690/630
22 (5.5)*
780/720/660
1140/960/810
30 ø12.7
ø15.9
ø6.4
ø6.4
25 (Polyvinyl chloride tube) 42/39/34
37/35/32
*Figures in parentheses are for ceiling s. *1 This reference piping consists of 5 m of main piping and 2.5 m of branch piping connected at the same height level. *2 The actual values in an external operating environment are generally higher than the indicated values due to the contribution from ambient noise.
38/36/34
45/41/37
35
MMU-AP0074YH-E to AP0124YH-E external dimension 1050 Ceiling open dimension 1010
20
455
Hanging bolt 4-M10 procured locally
140
120
Ceiling (Sold separately)
100 or less Bottom face of ceiling
Air outlet
1050
metal
Stand-up 150 or less
Discharge louver
400
18
85
200
850
Refrigerant pipe connecting port (Gas side)
20
50
Center of
100
235
395
110
150 225
470
Refrigerant pipe connecting port (Liquid side) mounting hole 5 positions
Stand-up 350 or less
Drain pipe connecting port
external dimension 470
Power supply connecting port
400
Hanging bolt pitch 330
20
Hanging bolt pitch 890
Ceiling open dimension 430
20
Bottom face of ceiling Air inlet
Drain standing-up size
(Unit: mm)
MMU-AP0154SH-E to AP0244SH-E Wiring connection port Drain pipe connecting port
20
72
Refrigerant pipe connecting port (Gas side)
Ceiling (Sold separately)
800
60
43
1230
80
710
20
135
220
122
233
Hanging bolt pitch 475 100
ф112
20
Hanging bolt pitch 1060
216
Ceiling open dimension 1190
externaldimension 800
20
112
94
Wireless sensor mounting section
154 140 or less
1000
Hanging bolt M10 or W3/8 local arrange
73.4
93
20
200
76
706
Stand-up 696 or less
Refrigerant pipe connecting port (Liquid side)
Bottom face of ceiling
Stand-up 850 or less
external dimension 1230
Ceiling open dimension 760
Fresh air intake (ф92 knockout hole)
Bottom face of ceiling
Knockout hole for front blow out
Drain standing-up size
(Unit: mm)
Options AP0074YH-E/AP0094YH-E/AP0124YH-E
Front air discharge unit TCB-BUS21HWE
Ceiling RBC-UY136PG
Auxiliary fresh air flange TCB-FF101URE2 Ceiling
AP0154SH-E/AP014SH-E/AP0244SH-E
RBC-US21PGE
5
38 36
Concealed Duct Type Compact size, wider range of installation opportunities
275mm giving a wider range of installation opportunities Especially in height as new model has a slimmer chassis Improved external static pressure (max 120Pa)
With a new DC Fan Motor provides a wider range of installation opportunities. New Design for safety and easy maintenance
The new model has adopted new features for safety and easy approach during installation Pre-installed drain pump
Gives a wider scope for installation as it is able to pump water 850mm up from the drain pan.
MMD-AP***6BHP-E
REMOTE CONTROLS
TCB-AX32E2
RBC-AMS41E
RBC-AMS51E
Technical specifications Model name
MMD
Cooling/Heating capacity (Note 1)
(kW)
2.2/2.5
(A)
0.26 / 0.27
AP0076BHP-E AP0096BHP-E AP0126BHP-E AP0156BHP-E AP0186BHP-E AP0246BHP-E AP0276BHP-E AP0306BHP-E AP0366BHP-E AP0486BHP-E
2.8/3.2
4.5/5.0
Running current Power consumption Starting current
0.29/ 0.31
9.0/10.0
11.2/12.5
14.0/16.0
16.0/18.0
0.52 /0.55
0.61 / 0.64
1.07 / 1.12
1.23 / 1.29
0.038
0.043
0.062
0.077
0.094
0.172
0.198
(A)
0.45 /0.47
0.5 /0.54
0.73 / 0.76
0.9 /0.95
1.06 /1.11
1.85 / 1.94
2.13 / 2.23
Zinc hot dipping steel plate (mm)
Width
(mm)
Depth
(mm)
275 700
1,000
1,400
30
40
750 23
(kg)
Heat exchanger
Finned tube
Soundproof / Heat-insulating meterial
Polyethlene foam
Fan Standard air flow (Mid/Low)
Centrifugal fan (m3/h)
Motor output
540 (420/360*)
5 7 0 ( 4 5 0 /390*)
8 0 0 ( 6 3 0 /540*)
1 , 2 0 0 ( 9 3 0 /870*)
1,260 (960/930*) 1,920 (1,500/1380*)
150
(W)
External static pressure (Pa)(factory setting)
2100 (1,650/1500*)
250
30
40
50
30 - 40 - 50 - 65 - 80 - 100 - 120 (7steps)
External static pressure (Pa)
Standard filter (Long life filter)
Air filter
Remote controller
Controller
Connecting pipe
8.0/9.0
(kW)
Height
Total weight
Fan unit
7.1/8.0
0.42 /0.44
Appearance
Dimension
5.6/6.3
1phase 50Hz 230V(220V-240V),1phase 60Hz 220V (Sepatate power supploy for indoor unit is required.)
Power supply Electrical characteristics (50Hz / 60 Hz)
3.6/4.0
AP0566BHP-E
Gas side
(mm)
Liquid side
(mm)
Drain port
(mm)
Sound pressure level (Note 2) (Hi/Med./Low)
ø 9.5
ø 12.7
ø 15.9
ø 6.4
ø 9.5 25 (Polyvinyl chloride tube)
29/26/23
30/26/23
33/29/25
36/31/27
40/36/33
Note 1: The cooling capacities and electrical characteristics are measured under the conditions specified by JIS B 8615 base on the reference piping. The reference piping consists of 5 m of main piping and 2.5 m of branch piping connected with 0 meter height. Note 2: The sound levels are measured in an anechoic chamber in accordance with JIS B8616. Normally, the values measured in the actual operating environment become larger than the indicated values due to the effects of external sound. Note: Rated conditions Cooling : Indoor air temperature 27°C DB/19°C WB, Outdoor air temperature 35°C DB. Heating : Indoor air temperature 20°C DB, Outdoor air temperature 7°C DB/6°C WB.
37
MMD-AP0076BHP-E to AP0566BHP-E Flexible drain hose (Accessory)
Hanging bolt pitch A
Space required for installation and servicing 5 or more
Unit external dimension B
Refrigerant pipe connecting port ф 6.4
25 700 or more Service door (Ceiling opening) 700 or more
2500 or more
25 100 or more
275
Air outlet
Ceiling
1/100 or more downward At the time of natural drainage
750
Floor surface
(Liquid side) Refrigerant pipe connecting port ф 9.5
108
(Gas side)
650
Electrical control box Air filter
(For air taking-in air)
20 37
233 232
20
345
50 ф 125 knockout hole
18
136
233 117.5
570 355
Hanging bolt pitch 650
Drain pipe connecting port
170
Unit external dimension 750
50
22
64 180 (Outside)
Unit external dimension 275
C (outside)
18
Wires drawing-out port
229
Model MMD-
(Unit: mm) D
Options
Spigot shaped flange TCB-SF56C6BE TCB-SF80C6BE TCB-SF160C6BE
A
B
C
D
AP0076BH-E, AP0096BH-E, AP0126BH-E
765
700
640
654
AP0156BH-E, AP0186BH-E
765
700
640
654
1000
940
953.5
1500
1340
1349
1065 AP0246BH-E, AP0276BH-E, AP0306BH-E Under air intake type 1465 AP0366BH-E, AP0486BH-E, AP0566BH-E Model MMD- (Thailand)
A
B
C
D
AP0076BHP-E, AP0096BHP-E, AP0126BHP-E
765
700
640
654
AP0156BHP-E, AP0186BHP-E
765
700
640
654
AP0246BHP-E, AP0276BHP-E, AP0306BHP-E
1065
1000
940
953.5
AP0366BHP-E, AP0486BHP-E, AP0566BHP-E
1465
1500
1340
1349
5
42 38
Concealed Duct High Static Pressure type Design flexibility
Construction characteristics
Satisfies all your design needs.
Three-phase-switchable static pressure.
Compatible with external static pressures up to 196 Pa.
The flexible duct is accessible.
Inspection inlet enables easy access and maintenance.
Easy service and installation.
• high-efficiency filter (65%, 90% efficiency) • Filter/Drain pump optional
MMD-AP***4H-E
Inspection hole enables easy access and maintenance.
REMOTE CONTROLS
RBC-AMS41E
RBC-AMS51E
Technical specifications Model name
MMD
AP0184H-E
AP0244H-E
AP0274H-E
AP0364H-E
AP0484H-E
AP0724H-E
AP0964H-E
Cooling/Heating capacity*1
(kW)
5.6/6.3
7.1/8.0
8.0/9.0
11.2/12.5
14.0/16.0
22.4/25.0
28.0/31.5
Power consumption 50 Hz/60 Hz
(kW)
0.184/0.198
Height
(mm)
Width
(mm)
850
Depth
(mm)
660
Electrical characteristics
External dimensions
Total weight Standard air flow (High/Mid/Low) Fan unit
Connecting pipe
1-phase 50 Hz 230 V (220–240 V)/1-phase 60 Hz 220 V (Separate power supply for indoor units required.)
Power requirements
0.299/0.385
0.368/0.450
0.414/0.490
1.200/1.540
380
1.260/1.610 470
1,200
1,380 1,250
(kg)
50
52
56
67
150
(m3/h)
900
1,320
1,600
2,100
3,600
160
260
Motor output
(W)
External static pressure (factory setting)
(Pa)
137
External static pressure
(Pa)
68.6 – 137 – 196
4,200 370x3
Gas side
(mm)
ø12.7
ø15.9
ø22.2
Liquid side
(mm)
ø6.4
ø9.5
ø12.7
Drain port
(nominal dia.)
Sound pressure level*2 (High/Mid/Low)
(dB(A))
25 (male screw) 37
40
*1 This reference piping consists of 5 m of main piping and 2.5 m of branch piping connected at the same height level. *2 The actual values in an external operating environment are generally higher than the indicated values due to the contribution from ambient noise.
49
50
39
MMD-AP0484H-E
MMD-AP0724H-E, AP0964H-E 70
70
MMD-AP0184H-E to AP0364H-E
Z
Air inlet
Refrigerant pipe connecting port (Liquid side)
Refrigerant pipe connecting port (Liquid side) 1250
13
316
164
470 31
Drain pipe connecting port 190
1200 (202)
624 698
250
250
250
250
316
348
(141) 226
13
348
77 Left side
(141) 226
406
850 Left side AP0361H
Left side Air outlet
Air outlet
275
275
(150)
150
300
300
300
250
(150)
250
250
250 190
Z view
(Unit: mm)
Screw hole for duct mounting (8-M6)
(47)
Screw hole for duct mounting (6-M6)
65
85
(47)
30
70
(Unit: mm)
Filter chamber TCB-FCY21DE, TCB-FCY31DE TCB-FCY51DE, TCB-FCY100DE
Long life prefilter TCB-PF1D-1E TCB-PF2D-1E TCB-PF3DE
High-efficiency filter 65 TCB-UFM1D-1E, TCB-UFM2D-1E, TCB-UFM3DE High-efficiency filter 90 TCB-UFH5D-1E, TCB-UFH6D-1E, TCB-UFM7DE
TCB-DP31DE TCB-DP32DE
Screw hole for duct mounting (10-M6)
(Unit: mm)
Options
Drain pump kit
370
Z view
35
Z view
316
316
17
150
Screw hole for duct mounting (10-M6)
Screw hole for duct mounting (8-M6)
Screw hole for duct mounting (6-M6) 17
Air outlet
29
Air outlet
110
45
90 30
Drain pipe connecting port
Screw hole for duct mounting (4-M6)
200 150
40
60
35
(141)226
242
380
105
426
Refrigerant pipe connecting port (Gas side)
Electric parts box
660
35
(182)
100
70 Refrigerant pipe connecting port (Gas side)
850 13
Air inlet
1328 Hole for hanging bolt (4-ф12x92)
Hanging bolt pitch 700 740
35
30
35
60
110
Hanging bolt pitch 1288
35
660 105
Left side AP0181H to AP0271H
Air outlet
70 Refrigerant pipe connecting port (Liquid side)
Power supply/communication piping port (ф26) (bottom side of electric parts box)
380
Refrigerant pipe connecting port (Gas side)
Drain pipe connecting port
Air inlet
Electric parts box Hanging bolt pitch 700 740
90 40
Power supply/communication piping port (ф26) (bottom side of electric parts box)
1060
Air outlet
Electric parts box
Z 1380
710
Air outlet
Hole for hanging bolt (4-ф12x72)
Hanging bolt pitch 1260
Z
5
44 40
Slim Duct Type Slim & Quite
Functional design
Only 210 mm in height for greater application flexibility.
Perfect comfort throughout the room.
4 step static pressure setup.
Can be used with any style of air diff.
Concealed installation within a ceiling void.
Quiet, powerful operation.
Fresh air intake available. MMD-AP***4SPH-E
Condensate drain pump included.
REMOTE CONTROLS
TCB-AX32E2
RBC-AMS41E
RBC-AMS51E
Technical specifications Model name
MMD
AP0074SPH-E
AP0094SPH-E
AP0124SPH-E
AP0154SPH-E
AP0184SPH-E
AP0244SPH-E
AP0274SPH-E
Cooling/Heating capacity*1
(kW)
2.2/2.5
2.8/3.2
3.6/4.0
4.5/5.0
5.6/6.3
7.1/8.0
8.0/9.0
Electrical characteristics 50 Hz/60 Hz
Power consumption
(kW)
Height
(mm)
210
210
Width
(mm)
845
1,140
Depth
(mm)
645
645
1-phase 50 Hz 230 V (220–240 V)/1-phase 60 Hz 220 V (Separate power supply for indoor units required.)
Power requirements
0.039
0.043
Appearance
0.045
(kg)
Total weight
22
23
Heat exchanger
Fan unit
Motor output External static pressure Gas side
Connecting pipe Sound pressure level (note 2) (Hi/Mi/Lo) (dB(A)
Note:
29
Fined tube Standard air flow (Mid/Low)
Note 2:
0.105
Zinc hot dipping steel plate
External dimensions
Note 1:
0.054
(m3/h)
540/470/400
600/520/450
(W) (Pa)
06/16/31/46
(mm)
Liquid side
(mm)
Drain port
(nominal dia.)
690/600/520
780/680/580
60
1,080/1,000/900 120
05/15/30/45
04/14/29/44
ø9.5
ø12.7
02/12/22/42 ø15.9
ø6.4
ø9.4
25 (polyvinyl chloride tube)
Under air inlet
36/33/30
38/35/32
39/36/33
40/38/36
49/47/44
Back air inlet
28/26/24
29/27/25
32/30/28
33/31/29
38/36/33
The cooling capacities and electrical characteristics and measured under the conditions specified by JIS B 8615 based on the reference piping. The reference piping consists of 5 m of main piping and 2.5 m of branch piping connected with 0 meter height. The sound levels are measured in an anechoic chamber in accordance with JIS B 8615. Normally, the values measured in the actual operating environment become larger than the indicated values due to the effects of external sound. Rated conditions cooling: Indoor air temperature 27°C DB / 19°C WB, Outdoor air temperature 35°C DB. Heating: Indoor air temperature 20°C DB, outdoor air temperature 7°C DB/6°C WB.
41
MMD-AP0074SPH-E to AP0184SPH-E
210
Refrigerant pipe connecting port (Liquid side)
21
803 (inside)
21
Refrigerant pipe connecting port (Gas side)
103
Air filter
31 359 372 422 502
168
40
67
120
80
ф9 2
511 645
19
4-ф4
67
20 21
168 (Inside)
57
21
845
805 80
59
33 163
910
Fresh air intake (knock-out hole)
Drain pipe connecting port
Hanger plate
(Unit: mm)
MMD-AP0244SPH-E & AP0274SPH-E Hanging bolt pitch 1205
Unit external dimension 210 Hung-up plate 103
Refrigerant pipe connecting port ф9.5 (Liquid side) Refrigerant pipe connecting port ф15.9 (Gas side)
1100
98 ф 92 knockout hole (For air taking-in-air)
Air filter
Electrical control box
Unit external dimension 645 120 166
67
372 422 502
359
31
40
120
185
168
Hanging bolt pitch 511
67
20
21 168 (inside)
Unit external dimention 1140 1100 (inside)
15 33 163
Drain pipe connecting port for vinyl chloride pipe (Inner dia. ф32. VP25)
(Unit: mm)
Options
Auxiliary fresh air flange TCB-FF101URE2
5
48 42
Ceiling Type Equipped with self-clean operation. Improved air flow angel by new designed wide flap. Reduces noise level to half that of conventional The unit can be suspended from the ceiling with free access hangers: Fix the hanging plate on the ceiling firstly. Next, hang the indoor unit on that plate. Drain pump kit (Optional) To restrict the bacterial growth, anti-bacterial glass is built into new drain pump kit.
MMC-AP***7HP-E
REMOTE CONTROLS
RBC-AX32CE2
RBC-AMS41E
RBC-AMS51E
Technical specifications Model name
MMC
AP0157HP-E
AP0187HP-E
AP0247HP-E
AP0277HP-E
AP0367HP-E
AP0487HP-E
AP0567HP-E
Cooling/Heating capacity*1
(kW)
4.5/5.0
5.6/6.3
7.1/8.0
8.0/9.0
11.2/12.5
14.0/16.0
16.0/18.0
Power consumption 50 Hz/60 Hz
(kW)
0.033/0.033
Height
(mm)
Width
(mm)
Depth
(mm)
Electrical characteristics
External dimensions
Standard air flow (High/Mid/Low)
0.830/0.830
1,270
23 840/690/540
0.111/0.111
1,586
29 900/720/540
(mm)
ø12.7
Liquid side
(mm)
ø6.4
Drain port
(nominal dia.) (dB(A))
0.083/0.083
690
30
Sound pressure level*2 (High/Mid/Low)
0.067/0.067 235
(W)
Motor output Gas side
Connecting pipe
(m3/h)
0.034/0.034
950
(kg)
Total weight Fan unit
1-phase 50 Hz 230 V (220–240 V)/1-phase 60 Hz 220 V (Separate power supply for indoor units required.)
Power requirements
35
1410/1020/750
1860/1350/1020
2040/1650/1260
40
80
80
ø15.9 ø9.5 20 (Polyvinyl chloride tube)
36/34/28
37/35/28
41/36/29
0.083/0.083
*1 This reference piping consists of 5 m of main piping and 2.5 m of branch piping connected at the same height level. *2 The actual values in an external operating environment are generally higher than the indicated values due to the contribution from ambient noise.
44/41/35
46/42/36
43
MMC-AP0157HP-E to AP0567HP-E
Upper piping drawing-out port (Knockout)
235
Piping drawing-out port (Knockout)
176 205 244
145 Hanging position
98
690
320
Z 40
218 109 66
170
48
Power supply cable taking-in port (Knockout) Drain left pipe 87 connecting port
158
102
Drain pipe connection port
132 192
A (Hanging position) Refrigerant pipe connecting port D (Liquid side) Refrigerant pipe connecting port C (Gas side)
353 Wireless sensor mounting section
158
125
33
33 85
351 270
B
Remote controller cable taking-in port Power supply taking-in port (Knocking) Remote controller cable taking-in port (Knockout) 87
Air taking-in port (Duct sold separately) (Knockout hole ф 92) Z view
Drain left piping drawing-out port (Knockout)
Space requirement for installation and servicing
A
B
C
D
MMC-AP0157HP-E / 0187HP-E
906
950
ф 12.7
ф 6.4
MMC-AP0247HP-E / 0277HP-E
1223
1269
ф 15.9
ф 9.5
MMC-AP0367HP-E / 0487HP-E / 0567HP-E
1540
1586
ф 15.9
ф 9.5
Ceiling surface Unit 250 or more
250 or more
500 or more
MMC-
Within 50
Hanging bolt
Model
(Front side to be positioned horizontally)
(Unit:mm)
Options TCB-KP13CE, TCB-KP23CE Elbow piping RBC-AX33CE Wireless remote controller
TCB-DP31CE Drain pump kit
TCB-PCUC1E Optional connecting kit
5
50 44
High-wall Type (3 series) Elegant and slim
This classic high wall is elegant and slim; it can easily blend in with any room. Total comfort is granted, thanks also to the 70°directional auto swing louver that provide uniform air distribution.
REMOTE CONTROLS
MMK-AP***3H
Standard
RBC-AMS41E
RBC-AMS51E
MMK-AP0073H to AP0243H 1050
Air Filter
228
50
Air outlet
Heat exchanger
50 Knockout
7
7
73.5
73.5
320
Air inlet
50
Knockout
72 78
Tab for installation plate 132
568
Tab for installation plate
200
Drain connecting pipe
Refrigerant connecting pipe (Gas side)
150
Refrigerant connecting pipe (Liquid side)
(Unit: mm)
Technical specifications Model name
MMK
AP0073H
AP0093H
AP0123H
AP0153H
AP0183H
AP0243H
Cooling/Heating capacity*1
(kW)
2.2/2.5
2.8/3.2
3.6/4.0
4.5/5.0
5.6/6.3
7.1/8.0
Power consumption 50 Hz/60 Hz
(kW)
0.018
Height
(mm)
320
Width
(mm)
1,050
Depth
(mm)
228
(kg)
15
Electrical characteristics
External dimensions
Total weight Fan unit
Connecting pipe
1-phase 50 Hz 230 V (220–240 V)/1-phase 60 Hz 220 V (Separate power supply for indoor units required.)
Power requirements
Standard air flow (High/Mid/Low) Motor output
(m3/h)
570/450/390
600/480/390
(mm)
Liquid side
(mm)
Drain port
(nominal dia.) (dB(A))
0.043
0.050
840/660/540
1,020/750/570
ø12.7
ø15.9
30
(W)
Gas side
Sound pressure level*2 (High/Mid/Low)
0.021
ø9.5
ø9.5
ø6.4 16 (Polyvinyl chloride tube) 35/31/28
37/32/28
*1 The cooling capacities and electrical characteristics are measured under the conditions specified by JIS B 8615 based on the reference piping. The reference piping consists of 5 m of main piping and 2.5 m of branch piping connected with 0 meter height. *2 The sound level are measured in an anechoic chamber in accordance with JIS B 8616. Normally the values measured in the actual operating environment become larger than the indicated values due to the effects of external sound.
41/36/33
46/39/34
51 45
Floor Standing Concealed Type Cool air makes for a pleasant indoor environment
Easy maintenance
Install it under a window and aircondition any room effectively.
Simplified design of fan and drainage pipe eases maintenance.
REMOTE CONTROLS
MML-AP***4BH-E
TCB-AX32E2
RBC-AMS41E
RBC-AMS51E
MML-AP0074BH-E to AP0244BH-E Hole for floor mounting
(Air discharge port size in flange) Ceiling board section
25
145
145
50
5
B
C
85
100
(Air discharge port size in flange) 10
123
2- ф 4.7 hole (left/right side each)
10
65
10
20
A D X 100
135
Drain pipe connecting port
B
C
D
E
AP0074BH-E to AP0124BH-E
610
580
550
4
5
AP0154BH-E to AP0244BH-E
910
880
850
7
8
104
274
A
140
80
129
Model MML-
Air filter
2-12 X 18 long hole (Hole for floor mounting)
224
315
Refrigerant pipe connecting port (Gas side)
436
Refrigerant pipe connecting port (Liquid side)
4-ф15 hole (for mounting rear side)
Electric parts box (earth terminal is provided in inner side)
170
394
402
600
Expansion valve box E -ф4.7 hole (front side and rear side)
B
110 85
55
155 220
(Unit: mm)
Technical specifications Model name
MML
AP0074BH-E
AP0094BH-E
AP0124BH-E
AP0154BH-E
AP0184BH-E
AP0244BH-E
Cooling/Heating capacity*1
(kW)
2.2/2.5
2.8/3.2
3.6/4.0
4.5/5.0
5.6/6.3
7.1/8.0
Electrical characteristics
External dimensions
Power consumption 50 Hz/60 Hz
(kW)
Height
(mm)
Width
(mm)
Depth
(mm)
Total weight Fan unit
Standard air flow (High/Mid/Low) Motor output Gas side
Connecting pipe
1-phase 50 Hz 230 V (220–240 V)/1-phase 60 Hz 220 V (Separate power supply for indoor units required.)
Power requirements
0.056/0.058
0.090/0.096
745
1,045 220
(kg)
21
(m3/h)
460/400/300
(W)
19
(mm)
ø9.5
29 740/600/490
Liquid side
(mm)
ø6.4
(nominal dia.)
20 (Polyvinyl chloride tube)
(dB(A))
950/790/640 70
ø12.7
Drain port Sound pressure level*2 (High/Mid/Low)
0.095/0.110
600
36/34/32
*1 This reference piping consists of 5 m of main piping and 2.5 m of branch piping connected at the same height level. *2 The actual values in an external operating environment are generally higher than the indicated values due to the contribution from ambient noise.
ø15.9 ø9.5
42/37/33
5
52 46
Floor Standing Cabinet Type Slim & compact design
Air exits from front or top
Under-window mounting does not black lighting.
Distribution can be reversed to suit occupant preference.
Indoor unit size of 2.2 kW to 7.1 kW is the same. Air blown from top Air blown from front (Factory default)
REMOTE CONTROLS
MML-AP***4H-E
TCB-AX32E2
RBC-AMS41E
RBC-AMS51E
150
Drain pipe connecting port
Hole for wall mounting (Knockout hole)
230
(Drain)
138
(Liquid)
(Gas)
Piping positional drawing 133
Air outlet
130 5
177
35
Refrigerant pipe connecting port (Gas side)
(Gas)
120 130
400
106
Hole for floor mounting (2-ф10)
Refrigerant pipe connecting port (Liquid side)
162
95 28 Lower refrigerant piping port (Knockout hole 50x100)
(Liquid)
MML-AP0074H-E to AP0244H-E
97
70
50
35
Long hole for wall mounting
430
630
Power supply cord hole (ф26 knockout hole)
950
120
30
Refrigerant pipe port (both sides) (knockout hole 50x100)
Earth screw (M6)
130 (100 left side)
57
Air inlet
Refrigerant pipe port (Knockout hole ф130)
(Unit: mm)
Technical specifications Model name
MML
AP0074H-E
AP0094H-E
AP0124H-E
AP0154H-E
AP0184H-E
AP0244H-E
Cooling/Heating capacity*1
(kW)
2.2/2.5
2.8/3.2
3.6/4.0
4.5/5.0
5.6/6.3
7.1/8.0
Electrical characteristics
External dimensions
Power consumption 50 Hz/60 Hz
(kW)
Height
(mm)
630
Width
(mm)
950
Depth
(mm)
Total weight Fan unit
Connecting pipe
1-phase 50 Hz 230 V (220–240 V)/1-phase 60 Hz 220 V (Separate power supply for indoor units required.)
Power requirements
0.056/0.053
230 37
(kg) Standard air flow (High/Mid/Low) Motor output
(m3/h)
(mm)
Liquid side
(mm)
Drain port
(nominal dia.)
Sound pressure level*2 (High/Mid/Low)
(dB(A))
40
480/420/360
900/780/650
1,080/930/780
45
(W)
Gas side
0.102/0.113
0.092/0.092
70
ø9.5
ø12.7
ø15.9
ø6.4
ø9.5
20 (Polyvinyl chloride tube) 39/37/35
45/41/38
*1 This reference piping consists of 5 m of main piping and 2.5 m of branch piping connected at the same height level. *2 The actual values in an external operating environment are generally higher than the indicated values due to the contribution from ambient noise.
49/44/39
53 47
Bi-Flow Console Type Compact and modern design in all three dimensions (60x70x22 cm). Bi-flow. Two outlets for complete personalized flow: flow intensity and air direction control. Toshiba new IAQ Filtration : Having anti virus, Anti bacteria and the deodorizing capabilities. Smart interface : Child lock function on the unit display . Brightness level control of the display unit to reduce the LED light glow. Automatic restart function in case of unexpected electricity supply line power cuts. Floor heating function. REMOTE CONTROLS MML-AP***4NH-E
TCB-AX32E2
RBC-AMS41E
RBC-AMS51E
MML-AP0074NH-E to MML-AP0184NH-E
(Wall installation)
230
15 288
Slit
6 screw (M4 x 25L)
4 screw (M4 x 25L)
670
15
1000 mm or less
Note
150
10
Installation on the wall 1) Fix the installation plate on the wall with 4 mounting screws. 2) Hook the indoor unit on the installation plate. 3) Fix the upper part of indoor unit on the wall with 4 mounting screws.
40
Mounting directly on the floor 1) Fix the leg of indoor unit on the floor with 2 mounting screws. 2) Fix the upper part of indoor unit on the wall with 4 mounting screws.
• In case the plinth is fi xed to the wall, please make sure to cut out the slit on the left and right side of the main part. Cut dot-line area
4 screw (M4 x 25L)
Technical specifications Indoor unit
MML
Cooling capacity Heating capacity Power consumption Running current Starting current
AP0074NH-E
AP0094NH-E
AP0124NH-E
AP0154NH-E
AP0184NH-E
(kW)
2.2
(kW)
2.5
2.8
3.6
4.5
5.6
3.2
4.0
5.0
6.3
(kW) (A)
0.021
0.021
0.025
0.034
0.052
0.20
0.20
0.23
0.29
0.42
(A)
0.26
0.26
0.30
0.38
0.55
Air flow
(m3/h)
510/282
510/282
552/324
624/384
726/426
Sound pressure level (h/l)
(dB(A))
38/26
38/26
40/29
43/31
47/34
Sound power level (h/l)
(dB(A))
53/41
53/41
55/44
58/46
62/49
Dimensions (H x W x D)
(mm)
600/700/220
600/700/220
600/700/220
600/700/220
600/700/220
Weight
(kg)
17
17
17
17
17
Connecting pipe (Gas)
(in)
3/8”
3/8”
3/8”
1/2”
1/2”
Connecting pipe (liquid)
(in)
1/4”
1/4”
1/4”
1/4”
1/4”
Drain port diameter Power Supply
(mm)
16
16
16
16
16
V-ph-Hz
220/240-1-50
220/240-1-50
220/240-1-50
220/240-1-50
220/240-1-50
54 48
5
Floor Standing Type Thin profile suits interior design
Wide outlet
Slender, space-saving (1.7-6.0HP)
Corner location is also possible, with right and left auto swing.
type
Auto swing REMOTE CONTROLS MMF-AP***4H-E TCB-AX32E2
RBC-AMS41E
RBC-AMS51E
MMF-AP0154H-E to AP0564H-E Bracket for wall mounting Pitch 30x3
Air outlet
E
20
80
Wall
Model MMD-
Pipe holes on side (both sides) (knockout hole)
50 Rear side pipe hole (ф130 knockout hole)
120
180
132 157
210
50
AP0364H-E to AP0564H-E
380
120 160
390
40
Drain pipe connecting port
A
B
125
C
D
MMF-AP0364H-E Liquid side
358
Liquid side
155
D 204
F
120
B
MMF-AP0154H-E
165
631
Air inlet
A
164 C
Floor fixing bracket Screw position 640
F
200 107
Drain pipe port (both sides) (knockout hole)
59 10
Bracket for floor mounting (both sides)
E
AP0154H-E to AP0274H-E
380
815
1750
210 25
40
600 Pitch 30x3
Gas side
165
Refrigerant pipe connecting port (Liquid side)
215 215
Gas side
Refrigerant pipe connecting port (Gas side)
Earth screw (M4)
Refrigerant piping position
(Unit: mm)
Technical specifications Model name
MMF
AP0154H-E
AP0184H-E
AP0244H-E
AP0274H-E
AP0364H-E
AP0484H-E
AP0564H-E
Cooling/Heating capacity*1
(kW)
4.5/5.0
5.6/6.3
7.1/8.0
8.0/9.0
11.2/12.5
14.0/16.0
16.0/18.0
Electrical characteristics
External dimensions
Power consumption 50 Hz/60 Hz
(kW)
Height
(mm)
1,750
Width
(mm)
600
Depth
(mm)
0.067/0.067
0.830/0.830
210
390
(kg)
48
49
900/780/660
1,200/1,020/840
1,920/1,680/1,380
2,160/1,860/1,560
(W)
37
63
110
160
(mm)
ø12.7
Liquid side
(mm)
ø6.4
Drain port
(nominal dia.)
Standard air flow (High/Mid/Low) Motor output Gas side
Connecting pipe
0.033/0.033
(m3/h)
Total weight Fan unit
1-phase 50 Hz 230 V (220–240 V)/1-phase 60 Hz 220 V (Separate power supply for indoor units required.)
Power requirements
Sound pressure level*2 (High/Mid/Low)
(dB(A))
65
ø15.9 ø9.5 20 (Polyvinyl chloride tube)
46/43/38
49/45/40
51/48/44
*1 This reference piping consists of 5 m of main piping and 2.5 m of branch piping connected at the same height level. *2 The actual values in an external operating environment are generally higher than the indicated values due to the contribution from ambient noise.
54/50/46
56
49
AHU DX Connectivity Kit - DX Controller & DX Valve Kit DX Coil Interface
Valve Kit
• DX Coil interface enables the connection of Toshiba VRF Outdoor with third party Air Handling Unit (AHU) for fresh air intake. • Control possible thru standard Toshiba Remote control (RBC-AMT32-E). • Compatible with Toshiba control accessories. • External on/off output. • Safety cut out input to detect fan failure. • Air temperature control using TA sensor positioned in supply air stream| (set with remote controller). • Diversity Ratio maximum 110 % ( when a DX interface is connected ) • Its composed of two parts : Controller & Valve Kit (3 sizes). AHU DX Controller
Controller (Field supplied)
Controller
DX Controller-MM-DXC*** DX Valve Kit - MM-DXV*** Outdoor Unit Air Handling Unit (Field Supplied)
Options :
Typical System Diagram
RBC-FDP3-PE – Monitoring & Control Interface TCB-TC21LE2 – Remote Temperature Sensor
Technical specifications Total Size (Individual) MM-DXC010 MM-DXC012 MM-DXV080 MM-DXV140 MM-DXV280 Nominal Cooling Capacity (kW) Nominal Heating Capacity (kW) Minimum Air volume flow rate (m3/hr) Standard Air volume flow rate (m3/hr) Maximum Air volume flow rate (m3/hr)
HP 2 2.5 3 4 5 6 8 10
2.0 1 1
2.5 1 -
3.0 1 -
1
1
7.1 8.0 1060 1320 1580
5.6 6.3 720 900 1080
4.0 1 -
5.0 1 -
1
8.0 9.0 1060 1320 1580
6.0 1 -
1
11.2 12.5 1280 1600 1920
8.0 1 -
1
14.0 16.0 1680 2100 2520
1
16.0 18.0 1850 2800 3740
22.4 25.0 2880 3600 4320
10 1 -
1 28.0 31.5 3360 4200 5040
Technical specifications Total Size (Individual) MM-DXC010 MM-DXC012 MM-DXV080 MM-DXV140 MM-DXV280
HP 2 2.5 3 4 5 6 8 10
Nominal Cooling Capacity (kW) Nominal Heating Capacity (kW) Minimum Air volume flow rate (m3/hr) Standard Air volume flow rate (m3/hr) Maximum Air volume flow rate (m3/hr) *In GROUP combination the Header Controller (MM-DXC010)
12.0 1 1
14.0 1 1
2
1
32.0 38.4 36.0 43.0 3700 4730 5600 6400 7480 8060 must be connected to
16.0 1 1
18.0 1 1
2
1
20.0 1 1
22.0 1 2
1* 2 44.8 50.4 56.0 50.0 56.5 63.0 5730 6240 6720 7200 7800 8400 8640 9360 10080 the largest DX Coil Valve Kit.
24.0 1 2
26.0 1 2
28.0 1 2
30.0 1 2
1 2*
3
60.8 68.0 7610 10000 12380
67.2 75.0 8640 10800 12960
2 1* 72.8 81.5 9120 11400 13680
1 2* 78.4 88.0 9600 12000 14400
3 84.0 94.5 10080 12600 15120
Technical specifications Total Size (Individual) MM-DXC010 MM-DXC012 MM-DXV280 Nominal Cooling Capacity (kW) Nominal Heating Capacity (kW) Minimum Air volume flow rate (m3/hr) Standard Air volume flow rate (m3/hr) Maximum Air volume flow rate (m3/hr)
HP 8 10
32.0 1 3 4 89.6 100.0 11520 14400 17280
34.0 1 3 3 1* 95.2 106.5 12000 15000 18000
36.0 1 3 2 2* 100.8 113.0 12480 15600 18720
38.0 1 3 1 3* 106.4 119.5 12960 16200 19440
40.0 1 3 112 126.0 13440 16800 20160
42.0 1 3 4 1* 117.6 131.5 14880 18600 22320
44.0 1 3 3 2* 123.2 138.0 15360 19200 23040
46.0 1 3 2 3* 128.8 144.5 15840 19800 23760
*In GROUP combination the Header Controller (MM-DXC010) must be connected to the largest DX Coil Valve Kit. Cooling & Heating output figures are based on calculations and ‘general’ test data. All figures are to ne taken as approximations. The properties of the DX coils (by others) will have an effect on the performance of the outdoor units. All capacity data shown in this brochure is based on the following conditions. Cooling: indoor air temperature 27◦C db/ 19◦C wb, outdoor air temperature 35◦C db Heating: indoor air temperature 20◦C db, outdoor air temperature 7◦C db / 6◦C wb ● ● ● ● ● ● ●
The DX coil must be suitable for R410A. The design should allow operation as both an Evaporator and a Condenser (Features: Multiple circuits/Liquid Capillary Distributor / Gas Header) The counter flow principle must be observed. Design target Evaporation temperature : 6.5C Design target Condensation temperature: 52C A Drain Pan must be fitted (even if only used in Heat mode) due to defrost cycles. It is recommended to fit droplet eliminator plates in the discharge air stream if used in Cool mode.
48.0 1 3 1 4* 134.4 151.0 16320 20400 24480
5
50
Air to Air Heat Exchanger • 9 models available with air flow ranges from 110 to 2000 m3/h. • Air conditioners and heat exchangers are controlled with same main bus. (Fig.1) • Automatic changeover to efficient operation mode: Units automatically switches to the heat exchange mode and normal ventilation based on operating conditions.(Fig. 2) • Free cooling -Provides fresh outdoor cool air to reduce the indoor air temperature,when the outdoor temperature is lower than the indoor air conditioned temperature. • Air balance volume rate can be varied to suit the usage environment and location . VN-M***HE
REMOTE CONTROLLER
Main bus (TCC-LINK)
1) ON/OFF
Main bus (TCC-LINK)
COOLING or HEATING
Main bus (TCC-LINK)
EXCEPT COOLING & HEATING By- flow Damper : Open
New Heat Exchange
2) Operating mode
RA
EA
Indoor
Outdoor
3) Setting temp
EA
OA
5) Ventilation mode
New Remote controller for HEX (NRC-01HE)
NRC-01HE
SMMSi
New Remote controller for HEX (NRC-01HE)
Remote controller for SMMSi
Indoor SA
OA
Central remote controller
4) Air volume
RA
Outdoor
SA
Heat exchange element
Heat exchange element
Heat exchange mode
Normal ventilation mode
(Fig. 1)
(Fig. 2)
Technical specifications VN-M150HE
VN-M250HE
VN-M350HE
VN-M500HE
VN-M650HE
VN-M800HE
VN-M1000HE
VN-M1500HE
VN-M2000HE
150/110
250/150
350/210
500/390
650/520
800/700
1,000/755
1,500/1,200
2,000/1,400
%
81.5/83
78/81.5
74.5/79.5
76.5/78
75/76.5
76.5/77
73.5/77
76.5/79
73.5/77.5
dB(A)
25.5/20
27/21
32/27
31/26
34/31
37/33.5
40.5/38.5
37.5/36
41/37
Model name Air Flow (h/l) Temperature exchange efficiency (h/l) Sound pressure level (h/l)
m3/h
Power Input (h/l) Enthalpy exchange efficiency
W
67/42
111/52
145/82
192/128
258/178
353/286
538/353
784/570
1,080/702
Heating (h/l)
%
74.5/76
70/74
65/71.5
72/73.5
69.5/71.5
71/71.5
68.5/71.5
71/73.5
68.5/72
Cooling (h/l)
%
69.5/71
65/69
60.5/67
64.5/66.5
61.5/64
64/65.5
60.5/64.5
64/67
60.5/65.5
Max. external static pressure(h/l)
Pa
8/47
65/28
83/65
99/62
82/61
132/76
122/84
124/112
116/110
Dimensions (HxWxD) Weight Duct diameter (Indoor side)
290x900x900
mm
350x1140x1140
400x1189x1189
810x1189x1189
kg
36
36
38
53
53
70
70
143
143
mm
100
150
150
200
200
250
250
250
250
49 51 MMD-VNM150HE to VNM350HE 25
1050
350
170
1140 EA(Exhaust Air)
454
RA(Return Air)
Outdoor side
Indoor side
80 Connecting Diagram
80
SA(Suppiy Air)
150~250 170
Power supply wire intake 25
200
600 or more
OA(Outdoor Air)
1197
800
1140
195 212
Earth Terminal
175 4-13 × 30 Oval hole(Hanging Bracket) Inspection Opening 450 × 450 or more Heat Exchange Element Filter Motor,Fans Maintenance Space
(Unit: mm)
Duct size (Nominal Diameter): 200
MMD-VNM500HE, VNM650HE 25
350 1140
EA(Exhaust Air)
454
RA(Return Air)
Earth Terminal
Outdoor side
Indoor side
80 Connecting Diagram
80
SA(Suppiy Air)
150~250 170
25
Power supply wire intake 200
600 or more
OA(Outdoor Air)
1197
800
1140
195 212
170
1050
175 4-13 × 30 Oval hole(Hanging Bracket) Inspection Opening 450 × 450 or more
(Unit: mm)
Heat Exchange Element Filter Motor,Fans Maintenance Space Duct size (Nominal Diameter): 200
MMD-VNM800HE, VNM1000HE 195
25
1099 EA(Exhaust Air)
400 1189 454
Earth Terminal
Outdoor side
Indoor side
1246
800
1189
245 262
RA(Return Air)
85
85
SA(Suppiy Air)
150~250 195
Power supply wire intake 25
200
600 or more
OA(Outdoor Air)
Connecting Diagram
200
4-13 × 30 Oval hole(Hanging Bracket) Inspection Opening 450 × 450 or more
(Unit: mm)
Heat Exchange Element Filter Motor,Fans Maintenance Space Duct size (Nominal Diameter):250
MMD-VNM1500HE, VNM2000HE
195
25
1099 EA(Exhaust Air)
810 50
1189 454 245 262 Connecting Diagram
410
85
Power supply wire intake
4-13 × 30 Oval hole(Hanging Bracket) Inspection Opening 450 × 450 or more Heat Exchange Element Filter Motor,Fans Maintenance Space
Duct size (Nominal Diameter): 250
245 262
SA(Suppiy Air)
200
150~250 195
600 or more
OA(Outdoor Air)
205
Indoor side
1246
Outdoor side
25
800
1189
730
RA(Return Air)
(Unit: mm)
5
52
Air to Air Heat Exchanger with DX-coil & Humidifier Greater comfort and reduced load Functionality built into the cooling system reduces load on cooling beyond that of the heat exchanger itself. This improves air quality and ensures maximum comfort throughout room being cooled. Free cooling at night When the air outdoors is cooler at night, the system expels warm air from the room. This reduces the air conditioning load the next day for improved energy efficiency. Flexible control Supply and exhaust fan speed ratios can be changed for improved air volume control that best matches the needs of the environment and location. *Limitations The total capacity of indoor units combined should be within 80 - 135% of the capacity of the outdoor unit. The capacity of the air to air heat exchanger should be no more than 30% of the capacity of the outdoor unit.
REMOTE CONTROLLER
Connectable with SMMSi Outdoor, It is not possible to connect SMMS/SHRM/MiniSMMS
(Fig.1) NRC-01HE Mo del name Fresh air conditioning load
VN(K )502HEXE
VN(K )802HEXE
VN(K )1002HEXE
Cooling (*1)
MMD (k W )
4.10 (1. 30)
6. 56 (2.06)
8. 25 (2. 32)
8. 25 (2. 32)
Heating (*1)
(k W )
5. 53 (2. 33)
8.61 (3.61)
10.92(4. 32)
10.92 (4. 32)
1-phase 50Hz 230V (220–240V) / 1-phase 60Hz 220V (Separate power supply for indoor units required.)
Power supply Temperature exchange efficiency 50Hz / 60Hz
Enthalpy exchange efficiency 50Hz / 60Hz
(%)
70. 5/70. 5
70.0/70.0
65. 5
70. 5/70. 5
70.0/70.0
65. 5
Low Cooling
Heating
High
D r ain p o r t
(%)
71. 5/72.0
72. 5/73.0
H i gh
(%)
56. 5/56. 5
56.0/56.0
Mid
(%)
56. 5/56. 5
56.0/56.0
L ow
(%)
57. 5/58.0
59.0/59. 5
High
(%)
68. 5/68. 5
70.0/70.0
M id
(%)
68. 5/68. 5
70.0/70.0
L ow
(%)
69.0/69.0
73.0/73. 5
High
(m3/h)
500/500
800/800
Mid
(m3/h)
500/500
800/800
Low
(m3/h)
4 40/410
6 40/600
820
High
(Pa)
120/200
120/190
135
195
Mid
(Pa)
105/170
100/155
120
160
L ow
67. 5
6 8 .0 52.0 52.0
54. 5
55.0 6 6.0 6 6 .0
68. 5
69.0 950 950 80 0
(Pa)
115/150
105/130
105
130
(dB)
37. 5/40.0
41.0/43.0
43.0
43. 5
Mid
(dB)
36. 5/38.0
40.0/42.0
42.0
L ow
(dB)
34. 5/36. 5
38.0/37.0
4 0. 0
H e i g ht
(mm)
W i d th
(mm)
1140
1189
D e p th
(mm)
1690
1739
G as si d e
(mm)
Total weight
(kg) Liquid side
1-phase 60Hz 220V
(Separate power supply for indoor units is required.)
(%)
External static pressure
Connecting piping
(Separate power supply for indoor units is required.)
High
Fan unit 50Hz / 60Hz
External Dimensions
1-phase 50Hz 230V (220V-240V)
Mid
Standard air flow
Sound pressure 50Hz / 60Hz
VN(K )1002HEXE2
430
84
100
101
ø9. 5
(mm) (Nominal dia .mm)
(*1) Cooling and heating capacities are based on the following conditions: Cooling capacities are based on : indoor temperature :27 °CDB/19°CWB, Outdoor temperature : 35°CDB Heating capacities are based on : indoor temperature :20 °CDB, Outdoor temperature : 7 °CDB/6°CWB Fan is based on High and Middle ( ): The figures in ( ) indicate the heat reclaimed from the heat recovery ventilator.
ø12.7 ø 6.4 25(Poly vinyl chloride tube)
103
47 53
MMD-VN(K)502HEXE 1690 1601 25
550
400
Outdoor side
Indppr Side
250
1197 1140 800
173
RA (Return Air)
EA (Exhaust Air)
SA (Supply Air)
OA (Outdoor Air) 200
152
Power supply wire intake
600
25
4-13 x 30 oval hole (Hangling bracket)
Inspection opening 600 x 600
80 Duct size (Nominal Diameter): 200
26
46
476 350 175 195 212 430
350 175
343
454
Water inlet connecting port (R1/2) 194 53
Heat exchange element Filter Motors, (Fans, ( Maintenance space Magnetic valve Decompression magnetic valve ( (
496
Drain pipe connecting port (VP25)
80 Refrigerant pipe connecting port (Liquid) 6.4 Refrigerant pipe connecting port (Gas) 9.5
(Unit: mm)
MMD-VN(K)802HEXE to VN(K)1002HEXE2
4-13 x 30 oval hole (Hangling bracket)
550
RA (Return Air)
400
EA (Exhaust Air) Outdoor side
Indppr Side
SA (Supply Air)
200
Power supply wire intake
Inspection opening 600 x 600
600
25
OA (Outdoor Air)
343 80
Duct size (Nominal Diameter): 250
Water inlet connecting port (R1/2)
46
476 350
496 Drain pipe connecting port (VP25)
Options
Drain pump kit TCB-DP31HEXE
200 245 262 430
(
454 400 200
(
26
(
Heat exchange element Filter Motors, Fans, Maintenance space Magnetic valve Decompression magnetic valve
194 53
(
250
800
1246 1189
25
1739 1650
85 Refrigerant pipe connecting port (Liquid) 6.4 Refrigerant pipe connecting port (Gas) 12.7
(Unit: mm)
57 5
54
Fresh Air Intake Indoor Unit Type Air controller for fresh-air intake
Outside static pressure maximum 230Pa (In case of 50Hz of 5Hp). Use of high-performance filter provides more comfortable room enviroment.Introduces outdoor air at atemperature close to that of the indoor air. Primary processing of fresh outdoor air. Fresh Air-intake often influences the system, rendering normal control of the air conditioner difficult or placing large loads on the system and its cooling performance. Therefore it is frequently adopted to handle the fresh air to a certain condition before the fresh air will enter in the main air conditioner. This device is known as a fresh air intake indoor unit.
MMD-AP****HFE
NOTE: The fresh air intake indoor unit is an air conditioner provided to handle the fresh air load and is not to control the room temperature. For correspondence to the load of the indoor air controller, set an air conditioner separately.
Connectable outdoor unit MMY-MAPXXXXHT8 MMY-MAPXXXXHT7
Fresh air intake indoor unit SMMS-i outdoor unit Indoor unit
Fresh air Technical specifications Model name
MMD
AP0481HFE
AP0721HFE
AP0961HFE
Cooling/Heating capacity (Note 1)
(kW)
14.0/8.9
22.4/13.9
28.0/17.4
Electrical characteristics
External dimensions: Main unit
Power supply
(kW)
Power consumption
(kW)
Height
(mm)
Width
(mm)
Depth
(mm) (kg)
Total weight Standard air flow Fan unit
Connecting pipe
Motor output External static pressure 50 Hz/60 Hz Air ow limit Lower limit/Upper limit
1-phase 50 Hz 230 V (220–240 V)/60 Hz 220 V 0.28/0.34
0.45/0.55
0.52/0.65
492 892
1392 1262
93
(m3/h)
1080
(W)
0.160
144 1680
2100 0.160×2
170-210-230 / 115-215-260
140-165-180 / 150-210-235
160-190-205 / 80-180-220
(m3/h)
756/1188
1176/1848
1470/2310
Gas side
(mm)
ø15.9
ø22.2
Liquid side
(mm)
ø9.5
ø12.7
Drain port
(nominal dia.)
Sound pressure level (Note 2) (High/Med./Low)
(dB(A))
R1 45/43/41
46/45/44
* The setting temperature is 16 – 27°C (standard FCU…18 – 29°C). * An optional humidi er is not available with fresh air intake indoor unit. * Height di erence between fresh air intake indoor units must be within 0.5 m. Height di erence between fresh air intake indoor unit and standard FCU must be within 30 m. NOTE 1:
NOTE 2: NOTE 3: NOTE 4: NOTE 5:
Rated conditions
Cooling: Outdoor air temperature 33°C DB/28°C WB setting temperature 18°C Heating: Outdoor air temperature 0°C DB/–2.9°C WB setting temperature 25°C Piping: Length 7.5 m / Height 0 m Normally, the values measured in the actual operating environment become large than the indicated values due to the e ects of external sound * When supply air temperature is “setting temperature + 3°C” or less, fresh air intake indoor unit operates as FAN mode.. * When supply air temperature is 19°C or less, Fresh Air Intake Indoor unit operates as FAN mode. * When supply air temperature is “setting temperature –3°C” or over, fresh air intake indoor unit operates as FAN mode. * For more connectivity option please supplier.
55
MMD-AP0481HFE to AP0961HFE Long hole for M10 hanging bolt Type
Hole dia.-Width x Length
0481
4-ф12 x 40
0721, 0961
4-ф12 x 92
1328 Hanging bolt pitch 1288
100
A
Hanging bolt pitch B
1262
600
600
Refrigerative piping work example at local site
Check port
Refrigerant pipe connecting port (Gas pipe M) Electric parts box (With cover)
145.5
492
370 Discharge port connecting flange (K) (Accessory for main unit of product)
23 60
35
G
H
I
J
Suction port
Suction port connecting flange (L) (Accessory for main unit of product)
1262 Drain pipe connecting port
Model MMD-
(Unit: mm)
704 850
47
81
Blow-off port Discharge temp sensor
528.5
406
F
51
E
216 150
D
41
C
Refrigerant pipe connecting port (Liquid pipe N)
A
B
C
D
E
F
G
H
I
J
K
L
M
N
AP0961HFE
1392
1260
250
250
250
250
250
250
250
250
10-M6
10-M6
ф22.2 brazing
ф12.7 flare
AP0721HFE
1392
1260
250
250
250
250
250
250
250
250
10-M6
10-M6
ф22.2 brazing
ф12.7 flare
AP0481HFE
892
810
215
107.5
107.5
215
250
250
8-M6
6-M6
ф15.9 flare
ф9.5 flare
Options Filter chamber TCB-FCY51DFE TCB-FCY100DE Long life prefilter TCB-PF3DE TCB-PF4D-1E
High-efficiency filter 65 TCB-UFM3DE, TCB-UFM4D-1E Drain pump kit TCB-DP32DFE
High-efficiency filter 90 TCB-UFH7DE, TCB-UFH8D-1E
5 53
56
Mini-SMMS Superior EER & COP (4.61 COP for 4HP). Quiet Operation ( Noise level 49dB(A) for 4HP). Upto 9 indoors may be connected ( 6HP Outdoor Model ). DC Twin rotary compressor delivering higher efficiency. Wide range of indoor units 15 types and different sizes. Compact design ( approx 70% smaller than SMMS equal capacity outdoor ). MCY-MAP
1HT
Full range of SMMSi Controls available .
Piping Diagram
Height between indoor and outdoor units ( Outdoor unit higher than indoor units)
When PMV Kit is not used (Outdoor unit higher than indoor unit)
When PMV Kit is used (Outdoor unit higher than indoor unit)
Not used
Piping length
Used
180
Maximum pipe extension (Liquid pipe, real length) Piping section : L1+L2+a+b+c
150
125
Farthest piping length (Equivalent length) Piping section : L1+L2+C
80
Height difference
(Outdoor unit lower than indoor units)
PMV Kit (Outdoor unit lower than indoor units)
30
Height between indoor and outdoor units (Outdoor unit higher than indoor units) Piping section : H
30
20
Height between indoor and outdoor units (Outdoor unit lower than indoor units) Piping section : H
20
54 57 Technical specifications Outdoor Unit
MCY-MAP0401HT 4 HP
HP
Cooling capacity EER Heating capacity COP
MCY-MAP0501HT 5 HP
MCY-MAP0601HT 6 HP
kW
12.1
14.0
15.5
W/W
4.29
4.03
3.35
kW
12.5
16.0
18.0
W/W
4.61
4.0
3.71
Air Flow
m3/h
5820
6120
6420
Sound pressure level
dB(A)
C/H
49/50
50/52
51/53
Sound power level
dB(A)
C/H
66/67
67/69
68/70
Dimensions (HxWxD)
mm
Weight
1340x900x320
kg
117
Compressor type
Twin Rotary
Refrigerant charge R410A
kg
Suction line type - diameter
In
Liquid line type - diameter
in
7.2
Flare - 5/8” Flare - 3/8”
Brazing - 3/4” Flare - 3/8”
Maximum equivalent length separation*
m
125
Maximum actual piping separation*
m
100
Maximum total pipe length*
m
180
Maximum lift (indoor unit above/below)
m
20/30
Operating range - db
°C
CO
-5~43
Operating range - wb
°C
HP
-15.0~15.5
Power supply
V-ph-Hz
230-1-50
* when PMV Kit is used: Maximum equivalent length separation (80 m); Maximum actual piping separation (65 m); Maximum total pipe length (150 m)
Indoor Connectivity Table Model Name
Size
Cooling Capacity
heating Capacity
Number of indoo units Max
Total capacity on connectable indoor units Min Max
MCY-MAP0401HT
4 HP
12.1kW
12.5kW
6
3.2HP
5.2HP
MCY-MAP0501HT
5 HP
14.0kW
16.0kW
8
4.0HP
6.5HP
MCY-MAP0601HT
6 HP
15.5kW
18.0kW
9
4.8HP
7.8HP
Single VRF indoor unit capacity of maximum 5HP can be connected. •
PMV kit
The PMV kit is an option for super-silent operation, available for hotel rooms and residential applications where noise levels are critical. Ease of installation ntegral condensate pump PMV Kit Model Name
Indoor unit capacity code
RBM-PMV0361E
0.8 – 1 – 1.25 HP
RBM-PMV0362E
For new High wall MMK-AP***3H - 0.8 – 1 – 1.25 HP
RBM-PMV0901E
1.7 – 2 – 2.5 HP
RBM-PMV0902E
For new High Wall MMK-AP***3H - 1.7 – 2 – 2.5 HP
PMV Kit Compatibility Table Model Compact 4 Way Cassette
HP
0.8
1.0
1.3
1.7
2.0
2.5
kW
2.2
2.8
3.6
4.5
5.6
7.1
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
4-Way Cassette 2-Way Cassette 1-Way Cassette
X
Standard Ducted Slim Ducted High Static Duct Ceiling High Wall
X
X
X
Floor Cabinet
X
X
X
Floor Concealed Floor Standing
X
3.0 8.0
3.2 9.0
4.0 11.2
5.0 14.0
55 5
58
SHRM-i - Super Heat Recovery Multi System-i • Multiple (Two/Three) Inverter Heat Recovery VRF. • The three-pipe VRF Super Heat Recovery Multi System (SHRM-i) delivers simultaneously cooling and heating. • Exceptional energy efficiency – COP of 4.4 for 22.4kW. • Compact flow selector unit: it automatically adjusts the temperature either by unit or by area.
MMY-MAP
• Installation Flexibility : Three Pipe connection allows installation height variation of 40 meters ( Equivalent to 10 story building ).
4FT8-E
• Active Oil Management system : As a system, it has more than 1 compressor. This running compressor can get oil and refrigerant from other compressor or modular quickly without any additional power consumption. Full range of SMMSi 17 Controls available. Upto 48 Indoor units may be connected of different types ( 42HP Size ).
Flow selectors RBM-Y1123FE
RBM-Y1803FE
Connectable indoor unit capacity (HP)
Below 4.0
4.0 to below 6.4
Connectable indoor units*
5
RBM-Y2803FE
Appearance
6.4 to 10.0 or less
8
8
*Only group operation is possible with 1 (or 2) remote controller. *Connecion cable kit : RBC-CBK15FE
Branching ts Y-shap e branching t
Branch headers
O utdo or unit connection piping kit
Appearance
(4-branch headers)
Model name
Usage (HP)
(Classification according to ) indoor unit capacity code
RBMBY55FE
Total below 6.4
RBMBY105FE
RBMBY205FE
Total Total 6.4 14.2 or or more more and and below below 25.2 14.2
RBMBY305FE
RBMHY1043FE
RBMHY2043FE
Max. 4 branches Total 25.2 or more
RBMHY1083FE
RBMHY2083FE
RBM-BT14FE
RBM-BT24FE
Max. 8 branches
Total Total 14.2 14.2 or Total or more Total more and below 14.2 and below below 14.2 below 25.2 25.2
Total below 26.0
Total 26.0 or more
56 59
System Diagram 3 Pipe (discharge gas/suction gas/liquid) Outdoor unit FS unit
Cooling
Heating
Piping Layout
4 pipe connection (Outdoor - Outdoor) 3 pipe
FS unit (Flow Selector unit)
Simultaneous operation
Cooling
Cooling
Heating
Heating
Heating
16 60
5
Outdoor units
Capacity Model name (MMY-)
8H P
10HP
MAP0804FT8-E
12HP
MAP1004FT8-E
14HP
MAP1204FT8-E
MAP1404FT8-E
Co oling capacity (kW)
22.4
28.0
33.5
40.0
Heating cap acity (kW)
25.0
31.5
37.5
45.0
Maximum number of indoor units
13
16
20
23
Capacity
16HP
18HP
20HP
Model name (MMY-)
AP1614FT8-E
AP1814FT8-E
AP2014FT8-E
Units in combination (MMY-)
MAP0804FT8-E MAP0804FT8-E
MAP1004FT8-E MAP0804FT8-E
MAP1004FT8-E MAP1004FT8-E
22HP AP2214FT8-E MAP1204FT8-E MAP1004FT8-E
24HP AP2414FT8-E MAP1404FT8-E MAP1004FT8-E
26HP AP2614FT8-E MAP1404FT8-E MAP1204FT8-E
28HP AP2814FT8-E MAP1404FT8-E MAP1404FT8-E
Cooling capacity (kW)
45.0
50.4
56.0
61.5
68.0
73.0
78.5
Heating capacity (kW)
50.0
56.5
63.0
69.0
76.5
81.5
88.0
Maximum number of indoor units
27
Capacity
30
33
37
40
43
47
30HP
32HP
34HP
36HP
38HP
40HP
42HP
Model name (MMY-)
AP3014FT8-E
AP3214FT8-E
AP3414FT8-E
AP3614FT8-E
Units in combination (MMY-)
MAP1004FT8-E MAP1004FT8-E MAP1004FT8-E
MAP1204FT8-E MAP1004FT8-E MAP1004FT8-E
MAP1404FT8-E MAP1004FT8-E MAP1004FT8-E
MAP1204FT8-E MAP1204FT8-E MAP1204FT8-E
AP3814FT8-E MAP1404FT8-E MAP1204FT8-E MAP1204FT8-E
AP4014FT8-E MAP1404FT8-E MAP1404FT8-E MAP1204FT8-E
AP4214FT8-E MAP1404FT8-E MAP1404FT8-E MAP1404FT8-E
Cooling capacity (kW)
85.0
90.0
96.0
101.0
106.5
112.0
118.0
Heating capacity (kW)
95.0
100.0
108.0
113.0
119.5
127.0
132.0
Maximum number of indoor units
48
48
48
* Power: 3-phase 50 Hz 400V (380 - 415V) * The source voltage must not fluctuate more than ±10%. * Rated conditions Cooling: Indoor air temperature 27°C DB/19°C WB, outdoor air temperature 35°C DB Heating: Indoor air temperature 20°C DB, outdoor air temperature 7°C DB/6°C WB
48
48
48
48
18
61
Outdoor unit specifications Single units
Technical specifications Equivalent HP
M o del name Outdoor unit type 1 Cooling capacity (* ) 1 Heating capacity (* ) Power supply (*2)
(M M Y-)
8H P MAP0804FT8-E
(kW) (kW)
Power consumption (kW) Cooling EER (Energ y Efficiency Ratio) Electrical characteristics Power consumption (kW) Heating (*1) COP (Coefficient of Performance) External dimensions (Heig ht / Width / D epth) (mm) Total weig ht (kg ) Compressor M otor output (kW) M otor output (kW) Fan unit A ir volume (m3/h) Suction gas side (mm) Connecting Discharge gas side (mm) Refrigerant piping port Liquid side (mm) diameter Balance pipe (mm) Sound pressure level (Co oling /Heating ) (dB(A))
22.4 25.0 5.17 4.33 5.68 4.40 1,830 / 990 / 780 259 2.3 x 2 1.0 8,700 ø 22.2 ø 19.1 ø 12.7 ø 9.5 55.0 / 57.0
10HP MAP1004FT8-E
Inverter 28.0 33.5 31.5 37.5 3-phase 4 wires 50Hz 400V (380-415V) 7.28 8.38 3.85 4.00 7.50 9.05 4.20 4.14 1,830 / 990 / 780 1,830 / 1,210 / 780 259 334 3.1 x 2 2.6 x 3 1.0 1.0 9,400 12,000 ø 22.2 ø 28.6 ø 19.1 ø 19.1 ø 12.7 ø 12.7 ø 9.5 ø 9.5 57.0 / 59.0 60.0 / 62.0
Combinations M o del name Outdoor unit type O utdoor unit mo del 1 Cooling capacity (* ) 1 Heating capacity (* ) Power supply (*2)
M M Y-
16HP AP1614FT8-E
M M Y-M A P 0804FT8-E 0804FT8-E (kW) 45.0 (kW) 50.0
Power consumption (kW) EER (Energy Efficiency Ratio) Power consumption (kW) Heating COP (Coefficient of Performance) Total weig ht (kg ) Compressor M otor output (kW) M otor output (kW) Fan unit A ir volume (m3/h) Suction gas side (mm) Connecting Discharge gas side (mm) Refrigerant piping port Liquid side (mm) diameter Balance pipe (mm) Sound pressure level (Co oling /Heating ) (dB(A))
10.42 4.32 11.36 4.40
Cooling
259 2.3 x 2 1.0 8,700
259 2.3 x 2 1.0 8,700 ø 28.6 ø 22.2 ø 19.1 ø 9.5 58.0 / 60.0
18HP AP1814FT8-E
20HP AP2014FT8-E
Inverter 1004FT8-E 0804FT8-E 1004FT8-E 1004FT8-E 50.4 56.0 56.5 63.0 3-phase 4 wires 50Hz 400V (380-415V) 12.45 14.56 4.05 3.85 13.18 15.00 4.29 4.20 259 259 259 259 3.1 x 2 2.3 x 2 3.1 x 2 3.1 x 2 1.0 1.0 1.0 1.0 9,400 8,700 9,400 9,400 ø 28.6 ø 28.6 ø 22.2 ø 22.2 ø 19.1 ø 19.1 ø 9.5 ø 9.5 59.5 / 61.5 60.0 / 62.0
Combinations
40.0 45.0 11.30 3.54 12.70 3.54 1,830 / 1,210 / 780 334 3.1 x 3 1.0 13,000 ø 28.6 ø 22.2 ø 15.9 ø 9.5 62.0 / 64.0
22HP AP2214FT8-E 1204FT8-E 1004FT8-E 61.5 69.0 15.66 3.93 16.55 4.17 334 259 2.6 x 3 3.1 x 2 1.0 1.0 12,000 9,400 ø 34.9 ø 28.6 ø 19.1 ø 9.5 62.0 / 64.0
Technical specifications Equivalent HP
M o del name Outdoor unit type Outdoor unit mo del 1 Cooling capacity (* ) 1 ) Heating capacity (* Power supply (*2)
M M YM M Y-M A P (kW) (kW)
Power consumption (kW) EER (Energy Efficiency Ratio) Power consumption (kW) Heating COP (Coefficient of Performance) Total weig ht (kg ) Compressor M otor output (kW) M otor output (kW) Fan unit A ir volume (m3/h) Suction g as side (mm) Connecting Discharge gas side (mm) Refrigerant piping port Liquid side (mm) diameter Balance pip e (mm) Sound pressure level (Co oling /Heating ) (dB(A))
Electrical characteristics 1(*)
14HP MAP1404FT8-E
Technical specifications Equivalent HP
Electrical characteristics 1(*)
12HP MAP1204FT8-E
Cooling
24HP AP2414FT8-E
26HP AP2614FT8-E
28HP 30HP AP2814FT8-E AP3014FT8-E Inverter 1404FT8-E 1004FT8-E 1404FT8-E 1204FT8-E 1404FT8-E 1404FT8-E 1004FT8-E 1004FT8-E 1004FT8-E 68.0 73.0 78.5 85.0 76.5 81.5 88.0 95.0 3-phase 4 wires 50Hz 400V (380-415V) 18.58 19.48 21.98 22.26 3.66 3.75 3.57 3.82 20.20 21.35 24.60 22.70 3.79 3.82 3.58 4.19 334 259 334 334 334 334 259 259 259 3.1 x 3 3.1 x 2 3.1 x 3 2.6 x 3 3.1 x 3 3.1 x 3 3.1 x 2 3.1 x 2 3.1 x 2 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 13,000 9,400 13,000 12,000 13,000 13,000 9,400 9,400 9,400 ø 34.9 ø 34.9 ø 34.9 ø 34.9 ø 28.6 ø 28.6 ø 28.6 ø 28.6 ø 19.1 ø 22.2 ø 22.2 ø 22.2 ø 9.5 ø 9.5 ø 9.5 ø 9.5 63.5 / 65.5 64.5 / 66.5 65.0 / 67.0 62.0 / 64.0
19 5
62
Combinations
Technical specifications Equivalent HP
M o del name Outdoor unit type O utdoor unit mo del 1 Cooling capacity (* ) Heating capacity (1*) 2 Power supply (* )
M M YM M Y-M A P 1204FT8-E (kW) (kW)
Power consumption (kW) EER (Energy Efficiency Ratio) Power consumption (kW) Heating COP (Coefficient of Performance) Total weig ht (kg ) Compressor M otor output (kW) M otor output (kW) Fan unit A ir volume (m3/h) Suction g as side (mm) Connecting D ischarg e g as side (mm) Refrigerant piping port Liquid side (mm) diameter Balance pip e (mm) Sound pressure level (Co oling /Heating ) (dB(A))
Electrical characteristics 1(*)
32HP AP3214FT8-E
Cooling
334 2.6 x 3 1.0 12,000
1004FT8-E 90.0 100.0 23.15 3.89 23.85 4.19 259 3.1 x 2 1.0 9,400 ø 34.9 ø 28.6 ø 22.2 ø 9.5 63.0 / 65.0
34H P 36HP AP3414FT8-E AP3614FT8-E Inverter 1004FT8-E 1404FT8-E 1004FT8-E 1004FT8-E 1204FT8-E 1204FT8-E 1204FT8-E 96.0 101.0 108.0 113.0 3-phase 4 wires 50Hz 400V (380-415V) 25.86 25.35 3.71 3.98 27.70 27.35 3.90 4.13 259 334 259 259 334 334 334 3.1 x 2 3.1 x 3 3.1 x 2 3.1 x 2 2.6 x 3 2.6 x 3 2.6 x 3 1.0 1.0 1.0 1.0 1.0 1.0 1.0 9,400 13,000 9,400 9,400 12,000 12,000 12,000 ø 34.9 ø 41.3 ø 28.6 ø 34.9 ø 22.2 ø 22.2 ø 9.5 ø 9.5 64.5 / 66.5 65.0 / 67.0
Combinations
Technical specifications Equivalent HP
M o d e l nam e Outdoor unit type O u td o o r u n i t m o d e l Cooling capacity (*1) Heating capacity (*1) Power supply (*2)
MMYMMY-MAP (k W ) (k W )
Power consumption (kW) EER (Energy Efficiency Ratio) Power consumption (kW) Heating COP (Coefficient of Performance) Total weight (kg) Compressor Motor output (kW) Motor output (kW) Fan unit Air volume (m3/h) Su c ti o n g as si d e (mm) Connecting Discharge gas side (mm) Refrigerant piping port ( mm) L i q u i d s i d e diameter B a l a n ce p i p e (mm) Sound pressure level (Cooling/Heating) (dB(A)) Electrical characteristics (*1)
38 H P AP3814FT8-E 1404FT8-E
Cooling
334 3.1 x 3 1.0 13,000
1204FT8-E 106. 5 119. 5 27.85 3.82 30. 6 0 3.91 334 2.6 x 3 1.0 12,000 ø 41. 3 ø 34.9 ø 22 . 2 ø 9. 5 65. 5 / 67. 5
4 0 HP 42HP AP4014T8-E AP4214FT8 -E Inverter 1204FT8-E 1404FT8-E 1404FT8-E 1204FT8-E 1404FT8-E 1404FT8-E 1404FT8-E 112.0 118.0 127.0 132.0 3-phase 4 wires 50Hz 400V (380-415V) 30. 4 0 33.10 3. 6 8 3. 56 3 4. 25 36.90 3.71 3. 58 334 334 334 334 334 334 334 2.6 x 3 3.1 x 3 3.1 x 3 2.6 x 3 3.1 x 3 3.1 x 3 3.1 x 3 1.0 1.0 1.0 1.0 1.0 1.0 1.0 12,000 13,000 13,000 12,000 13,000 13,000 13,000 ø 41. 3 ø 41. 3 ø 34.9 ø 34.9 ø 22 . 2 ø 22 . 2 ø 9. 5 ø 9. 5 6 6. 5 / 68 . 5 67.0 / 69.0
*1 Rated conditions Cooling : Indoor air temperature 27°C DB/19°C WB, Outdoor air temperature 35°C DB Heating : Indoor air temperature 20°C DB, Outdoor air temperature 7°C DB/6°C WB The reference piping consists of 5 m of main piping and 2.5 m of branch piping connected with 0 metre height. *2 The source voltage must not fluctuate more than ±10%.
Single unit (SHRM)
Technical specifications
Eq u i v a l e n t H P M o d e l nam e O u td o o r u n i t t y p e Cooling capacity (*1) Heating capacity (*1) Power supply (*2)
(MMY-) (k W ) (k W )
Power consumption (kW) Cooling EER (Energy Ef f icienc y Ratio) Electrical characteristics Power consumption (kW) Heating (*1) COP (Coefficient of Performance) External dimensions (Height / Width / Depth) (mm) Total weight (kg) Co m p r e s s o r M o to r o u t p u t (k W ) M o to r o u t p u t (k W ) Fan unit A i r vo l u m e (m3/h) Suction gas side (mm) Connecting Discharge gas side (mm) Refrigerant piping port Liquid side (mm) diameter Balance pipe (mm) S o u n d p r e s s u r e l e ve l (dB(A))
12HP MAP1202FT8-E Inver ter unit 33.5 35.5 3-phase 4 wires 50Hz 400V (380 - 415V ) 12.90 2.6 0 9.65 3.68 1,800 / 990 / 750 263 4.2 x 2 0.60 10,500 ø 28.6 ø 19.1 ø 12.7 ø 9.5 59.0
Note: SHRM is for use as a standalone unit and cannot be combined with SHRM-i.
20
63 Model: MMY-MAP0804FT8-E, MAP1004FT8-E 60
100
755 (Anchor bolt pitch)
670
610
790
(including steady leg)
Foundation
4-15x20 (Long hole) 100
990
60
700
(Anchor bolt hole pitch)
780
755 (anchor bolt pitch)
Mounting surface of bottom plate
Foundation
1595
1830
50
700 (Anchor bolt hole pitch)
500
85
2-60x200 square hole (for freight handling)
(220)*1
213 219 257
687
(75)*1
L-shape pipe Balance pipe connecting port 9.5
Refrigerant pipe connecting port (Liquid side) 12.7
(Note) 1. If there is an obstacle at the upper side of the outdoor unit, Refrigerant pipe connecting port set the top end of the outdoor unit 2000mm apart from the obstacle. (Discharge gas side) 19.1 2. Limit the height of the obstacle surrounding the outdoor unit to 800mm or less from the bottom end of the outdoor unit. 3. If a locally procured pipe is drawn horizontally from the front of the outdoor unit to a traversing pipe, keep a minimum 500mm between the outdoor unit and the traversing pipe.
Refrigerant pipe connecting port (Suction gas side) 22.2
*1 Recommended cutting position of L-shape pipe
(Unit: mm)
Model: MMY-MAP1204FT8-E, MAP1404FT8-E
755 (Anchor bolt pitch)
4-15x20 (Long hole)
60
ø22.2
670
ø19.1
ø15.9
100
ø12.7
610
MAP1204FT8-E MAP1404FT8-E
Mounting surface of bottom plate Foundation
B 780 790 (Including steady leg)
A
755 (Anchor bolt pitch)
Applied model (MMY-)
920 (Anchor bolt hole pitch)
60
100
1210 920
Foundation
1595
(75)*1
85
(220)*
1
687
1830
50
(Anchor bolt hole pitch)
620
2-60x200 square hole (for freight handling)
Balance pipe connecting port 9.5
(Note) 1. If there is an obstacle at the upper side of the outdoor unit, set the top end of the outdoor unit 2000mm apart from the obstacle. 2. Limit the height of the obstacle surrounding the outdoor unit to 800mm or less from the bottom end of the outdoor unit. 3. If a locally procured pipe is drawn horizontally from the front of the outdoor unit to a traversing pipe, keep a minimum 500mm between the outdoor unit and the traversing pipe.
L-shape pipe
Refrigerant pipe connecting port (Liquid side) A
Refrigerant pipe connecting port (Suction gas side) 28.6
Refrigerant pipe connecting port (Discharge gas side) B *1 Recommended cutting position of L-shape pipe
(Unit: mm)
21 5
64 Model : MMY-MAP1202FT8-E (SHRM)
Foundation
Refrigerant pipe connecting port (Suction gas side) 28.6
500 2-60x150 square hole (for freight handling)
(Note) 1. If there is an obstacle at the upper side of the outdoor unit, set the top end of the outdoor unit 2000mm apart from the obstacle. 2. Limit the height of the obstacle surrounding the outdoor unit to 800mm or less from the bottom end of the outdoor unit. 3. If a locally procured pipe is drawn horizontally from the front of the outdoor unit to a traversing pipe, keep a minimum 500mm between the outdoor unit and the traversing pipe.
*1
88
201
700
1640
1800
165
700 (Anchor bolt hole pitch)
Foundation
755 (Anchor bolt pitch)
80 630
610
990
80
4-15x20 (Long hole)
100
700 (Anchor bolt hole pitch)
790 (Including steady leg)
750 755 (Anchor bolt pitch)
100
Mounting surface of bottom plate
Refrigerant pipe connecting port (Discharge gas side) 19.1
Refrigerant pipe connecting port (Liquid side) 12.7
*1 Recommended cutting position of L-shape pipe
(Unit: mm)
65
Refrigerant piping design Allowable Length of Refrigerant Pipes and Allowable Height Difference between Units
D Follower unit
A B C Header Follower Follower unit unit unit
Height difference between outdoor units H3 ≤ 5 m
Ld La
Lb
Height difference between outdoor and indoor units: H1 ≤ 70 m
Main piping L1
LA
Lc
Outdoor unit connecting pipes
Outdoor unit
LB
Outdoor unit connection piping kit (For linking of outdoor units) The longest piping between outdoor units: L0 ≤ 25 m
Branching header Indoor unit connecting pipe Indoor unit a b
First branching section
L3
L7
Y-shaped branching t
c
d
e
The longest piping length: L≤ 235 m The longest piping length from the first branch: Li ≤ 90 m Y-shaped branching t f
g
Height difference between indoor units: H2 ≤ 40 m
L6
L5
L4
h
i
j
Indoor unit (j)
5
66
System Restriction Outdoor unit combination
Up to 4 units
Total capacity of outdoor units
Up to 48 HP
Indoor unit connection
Up to 48 units
Total capacity of indoor units (varies depending on the height difference between indoor units.)
H2 ≤ 15m
135% of outdoor units’ capacity
15m < H2
105% of outdoor units’ capacity
Cautions for Installation • • • •
Set the outdoor unit first connected to the bridging pipe to the indoor units as the header unit. Install the outdoor units in order of their capacity codes: A (header unit) ≥ B ≥ C ≥ D When connecting gas pipes to indoor units, use Y-shaped branching ts to keep pipes level. When piping to outdoor units using Outdoor unit connection piping kits, intersect the pipes to the outdoor unit and those to indoor units at a right angle as shown in figure 1 on “INSTALLATION MANUAL (6. INSTALLATION OF THE OUTDOOR UNIT)”. Do not connect them as in figure 2 on “INSTALLATION MANUAL (6. INSTALLATION OF THE OUTDOOR UNIT)”.
Allowable Length and Allowable Height Difference of Refrigerant Piping Item Total extension of pipe (liquid pipe, real length)
Less than 96kW 96kW or more
Farthest piping length L (∗1)
Pipe length
Height difference
Main piping length
Less than 34HP or less
Allowable value
Pipes
300m
LA + LB + La + Lb + Lc + Ld + L1 + L2 + L3 + L4 + L5 + L6 + L7 + a+b+c+d+e+f+g+h+i+j
34HP or more
500m
Equivalent length
235m
Real length
190m
LA + LB + Ld + L1 + L3 + L4 + L5 + L6 + j
Equivalent length
120m (∗2)
L1
Real length
100m (∗2)
Farthest equivalent piping length from the first branch Li∗1) (
90m (∗3)
L3 + L4 + L5 + L6 + j
Farthest equivalent piping length between outdoor units L0∗1) (
25m
LA + LB + Ld (LA + Lb, LA + LB + Lc)
Maximum equivalent piping length of pipes connected to outdoor units
10m
Maximum real length of pipes connected to indoor units
30m
a, b, c, d, e, f, g, h, i, j
Maximum equivalent length between branching sections
50m
L2, L3, L4, L5, L6, L7
Upper outdoor units
70m (∗4)
—
Lower outdoor unit
40m (∗5)
—
Height between indoor units H2
40m
—
Height between indoor units H3
5m
Height between outdoor and indoor units H1
La, Lb, Lc, Ld
∗1: Farthest outdoor unit from the first branch: (D), farthest indoor unit: (j) ∗2: If the total capacity of outdoor units is 46HP or more, make the equivalent length 70m (real length 50m) or less. ∗3: Make the difference 65m or less if the height difference between outdoor and indoor units (H1) is more than 3m. ∗4: Make the difference 50m or less if the height difference between indoor units (H2) is more than 3m. ∗5: Make the difference 30m or less if the height difference between indoor units (H2) is more than 3m.
—
67
Selection of refrigerant piping 6 Header branching pipe
Branching piping Follower unit 3
Follower unit 1 Header unit
Follower unit 2
Outdoor unit
1
1
1
1
2
2
1 Outdoor unit connecting piping
5
4
Balance pipe ø9.5 1st branching 1 section
7
5
5
5
5
5
Indoor unit branching t 4
4
4
5
5
5
4
7 Branching t for
Main connecting piping between outdoor units
5
6 Y-shape
3 Main piping 2
2
4
Indoor unit connecting piping
outdoor unit
Indoor unit connecting piping Indoor unit
1
Pipe size of outdoor unit (Table 1) Model name MMYMAP0804* MAP1004* MAP1204* MAP1404* MAP1604*
2
Gas side ø22.2 ø22.2 ø28.6 ø28.6 ø28.6
Liquid side ø12.7 ø12.7 ø12.7 ø15.9 ø15.9
Connecting pipe size between outdoor units (Table 2)
Total capacity code of outdoor units at downstream side * 1 16 to below 22 22 to below 26 26 to below 36 36 or more 3
6
Gas side ø28.6 ø34.9 ø34.9 ø41.3
Liquid side ø15.9 ø15.9 ø19.1 ø22.2
Balance pipe ø9.5
Y-shape branching t *2 *3 *8
Branching header *2 *3 *6 *8
7
Pipe size between branching sections (Table 4)* 5
SMMS-i 8HP to 48HP Total capacity code of indoor units at downstream side * 1 2.4 or less 2.4 to below 6.4 6.4 to below 12.2 12.2 to below 20.2 20.2 to below 35.2 35.2 or more
Gas side ø12.7 ø15.9 ø22.2 ø28.6 ø34.9 ø41.3
Liquid side ø9.5 ø9.5 ø12.7 ø15.9 ø19.1 ø22.2
Total capacity code of indoor unit * 1 Below 6.4 6.4 to below 14.2 14.2 to below 25.2 25.2 or more For 4 Below 14.2 14.2 to below 25.2 branching For 8 Below 14.2 14.2 to below 25.2 branching
Total capacity code of outdoor unit Branching Below 26 t for outdoor unit 26 or more
8
Model name RBM-BY55E RBM-BY105E RBM-BY205E RBM-BY305E RBM-HY1043E RBM-HY2043E RBM-HY1083E RBM-HY2083E
Selection of branching t for outdoor unit (Table 7)
Size of main pipe (Table 3)
Total capacity code of all Gas side Liquid side outdoor units * 1 B elow 6 ø 15 .9 ø 9 .5 6 to below 8 ø19.1 ø9.5 8 to below 12 ø22.2 ø12.7 12 to below 14 ø28.6 ø12.7 14 to below 22 ø28.6 ø15.9 22 to below 36 ø34.9 ø19.1 36 to below 46 ø41.3 ø22.2 ø41.3 ø22.2 46 or more *7 Determine thickness of the main pipe according to capacity of the outdoor units. 4
Selection of branching section (Table 6)
ts Gas (Y-shape) ø31.8
Liquid (T-shape)
Balance (T-shape)
ø19.1
ø9.5
ø28.6
ø25.4 ø19.1 ø19.1 ø38.1
ø38.1
ø9.5
ø22.2
ø9.5
ø9.5
ø28.6 ø22.2 ø22.2
ø9.5
ø9.5
Model name RBMBT14E RBMBT24E
Minimum wall thickness for R410A application (Table 8) Soft
OK OK OK OK No Good* 4 No Good* 4 No Good* 4 No Good* 4 No Good* 4
Half hard or hard OD (Inch) OD (mm) OK OK OK OK OK OK OK OK OK
1/4'' 3/8'' 1/2'' 5/8'' 3/4'' 7/8'' 1.1/8'' 1.3/8'' 1.5/8''
6.35 9.52 12.70 15.88 19.05 22.20 28.58 34.92 41.28
Minimum wall thickness (mm) 0.80 0.80 0.80 1.00 1.00 1.00 1.00 1.10 1.25
If the total capacity code value of indoor units exceeds that of the outdoor units, apply the capacity code of outdoor units. 5
Piping of indoor unit (Table 5)
Capacity rank 005 type to Actual length 15 m or less 012 type Actual length exceeds 15 m 015 type to 018 type 024 type to 056 type 072 type to 096 type
*1 *2 *3 *4 *5 *6 *7 *8
Gas side ø9.5 ø12.7 ø12.7 ø15.9 ø22.2
Liquid side ø6.4 ø6.4 ø6.4 ø9.5 ø12.7
Code is determined according to the capacity rank. When using a branching t for the 1st branch, select according to capacity code of the outdoor unit. For 1 line after branching header indoor units with a maximum capacity code of 6.0 in total can be connected. If the pipe size is Ø19.0 or more, use a suitable material as detailed in the installation manual. If the piping size becomes over main piping size, select the size same as main piping. When the first branch is a header with the outdoor total capacity codes of 12 to 26, apply the model RBM- HY2043E(4-branch) o r RBMHY2083E(8-branch) regardless of the total capacity codes of the down-stream indoor units. The maximum equivalent length of main pipe should be 70m or shorter. When the sum of capacity code of indoor units exceeds the capacity code of outdoor units, select according to capacity code of the outdoor units.
59 5
68 Indoor unit accessories Indoor unit
Parts Name
Model Name
Applied Model
Notes
Remarks
RBC-U31PG(W)-E Ceiling 4-way air discharge cassette type
Compact 4-way Cassette (600x600) type
TCB-GFC1602UE
For fresh air inlet box
Auxiliary fresh air flange Spacer for height adjustment
TCB-FF101URE2
For easy fresh air intake by using the knockout hole of indoor unit. (dia.=100 mm)
TCB-SP1602UE
Height=50 mm
Air discharge direction kit
TCB-BC1602UE
Ceiling
RBC-UM11PG(W)E
Auxiliary fresh air flange
TCB-FF101URE2
Super long life filter
Auxiliary fresh air flange Ceiling
Drain pump kit Slim duct type
Auxiliary fresh air flange Drain pump kit
Ceiling Type Elbow piping kit
Concealed duct type 6 Series
*European market only
Spigot Shaped Flange
For easy fresh air intake by using the knockout hole of indoor unit. (dia.=100 mm)
MMU-AP0182 to 0302WH
RBC-UW1403PG(W)-E TCB-LF283UW-E
MMU-AP0362/0482/0562WH MMU-AP0072 to 0152WH
TCB-LF803UW-E
MMU-AP0182 to 0302WH
TCB-LF1403UW-E
MMU-AP0362/0482/0562WH
TCB-FC283UW-E TCB-FC803UW-E
MMU-AP0072 to 0152WH
TCB-FC1403UW-E
MMU-AP0362/0482/0562WH
TCB-FF151US-E
MMU-AP***2WH
For fresh air intake by using the knockout hole of indoor unit. (dia.=150mm)
RBC-UY136PG
MMU-AP***4YH-E
Required accessory
MMU-AP0182 to 0302WH
Required accessory
Dust collecting effect: 50% (Weight method)
Use with TCB-FC803UW-E Use with TCB-FC1403UW-E
For super long life filter
MMU-AP***4SH-E For easy fresh air intake by using the knockout hole of indoor unit. (dia.=100 mm)
TCB-UFM1D-1E
MMD-AP0184H-E
TCB-UFM2D-1E (2 pcs.) TCB-UFM1D-1E (2 pcs.)
MMD-AP0244/0274/0364H-E
TCB-UFM3DE
MMD-AP0724/0964H-E
TCB-UFH5D-1E
MMD-AP0184H-E
TCB-UFH6D-1E (2 pcs.)
MMD-AP0244/0274/0364H-E
TCB-UFH5D-1E (2 pcs.)
MMD-AP0484H-E
TCB-UFH7DE
MMD-AP0724/0964H-E
TCB-PF1D-1E
MMD-AP0184H-E
TCB-PF2D-1E (2 pcs.)
MMD-AP0244/0274/0364H-E
TCB-PF1D-1E (2 pcs.) TCB-PF3DE
MMD-AP0484H-E MMD-AP0724/0964H-E
TCB-FCY21DE
MMD-AP0184H-E
TCB-FCY31DE
MMD-AP0244/0274/0364H-E
TCB-FCY51DE
MMD-AP0484H-E
TCB-FCY100DE TCB-DP31DE
MMD-AP0724/0964H-E
TCB-DP32DE TCB-FF101URE2
MMD-AP0724/0964H-E
Stand-up 330 or less (from bottom face of ceiling)
MMD-AP***4SPH-E
For fresh air intake by using the knockout hole of indoor unit. (dia.=100mm)
MMC-AP0154/0184H-E
Stand-up 600 or less (from bottom face of ceiling)
TCB-DP22CE2
Use with TCB-FC283UW-E
Required accessory
RBC-US21PGE TCB-FF101URE2
Filter chamber
Required accessory
RBC-UW803PG(W)-E
Auxiliary fresh air flange
Long life prefilter
Air direction charge by cutting off air discharge port (3 pcs) MMU-AP***4MH-E MMU-AP0072 to 0152WH
TCB-BUS21HWE
High-efficiency filter 90
MMU-AP***2H
RBC-UW283PG(W)-E
Front air discharge unit
High-efficiency filter 65
Concealed duct high static pressure type
For fresh air intake by using the knockout hole of fresh air filter chamber. (dia.=100 mm) Use with TCB-GFC1602UE
TCB-GB1602UE
Fresh air filter chamber
Filter chamber
1-way air discharge cassette type
Required accessory
RBC-U31PGS(WS)-E*
Ceiling
2-way air discharge cassette type
RBC-U31PGS(W)-E*
Fresh air inlet box
MMD-AP0484H-E
MMD-AP0481H-E to 0484H-E
MMC-AP0244 to 0484H-E
TCB-KP12CE2
MMC-AP0154/0184H-E
TCB-KP22CE2 TCB-SF56C6BE
MMC-AP0244 to 0484H-E MMD-AP0076 to 0186BHP-E
TCB-SF80C6BE
MMD-AP0246 to 0306BHP-E
TCB-SF160C6BE
MMD-AP0366 to 0566BHP-E
Use with TCB-FCY21DE Dust collecting effect: 65% (NBS Colorimentric method)
Use with TCB-FCY31DE Use with TCB-FCY51DE Use with TCB-FCY100DE Use with TCB-FCY21DE
Dust collecting effect: 90% (NBS Colorimentric method)
Use with TCB-FCY31DE Use with TCB-FCY51DE Use with TCB-FCY100DE Use with TCB-FCY21DE
Dust collecting effect: 50% (Weight method)
Use with TCB-FCY31DE Use with TCB-FCY51DE Use with TCB-FCY100DE
For high efficiency filter or long life prefilter.
Needed when drain pump kit is used
For multi duct connection at unit outlet.
Use with TCB-KP12CE2 Use with TCB-KP22CE2
60
69 Indoor unit accessories Indoor unit
High-efficiency filter 65
High-efficiency filter 90 Fresh air intake indoor unit type
Model Name
Parts Name
Long life prefilter
Filter chamber Drain pump kit
Applied Model
Notes
Remarks
TCB-UFM3DE
MMD-AP0721/0961HFE
TCB-UFM4D-1E
MMD-AP0481HFE
TCB-UFH7DE
MMD-AP0721/0961HFE
TCB-UFH8D-1E
MMD-AP0481HFE
TCB-PF3DE
MMD-AP0721/0961HFE
TCB-PF4D-1E
MMD-AP0481HFE
TCB-FCY51DFE
MMD-AP0481HFE
TCB-FCY100DE
MMD-AP0721/0961HFE
TCB-DP32DFE
MMD-AP0481/0721/0961HFE Stand-up 330 or less (from bottom face of ceiling)
Dust collecting e ect: 65% (NBS Colorimentric method)
Use with TCB-PF3DE
Dust collecting e ect: 90% (NBS Colorimentric method)
Use with TCB-PF3DE
Use with TCB-PF4D-1E
Use with TCB-PF4D-1E Use with TCB-FCY100DE
Dust collecting e ect: 50% (Weight method)
Use with TCB-FCY51DFE
For high-efficiency filter or long life prefilter
Combination Pattern 1) Accessory for 4-way air discharge cassette type: combination pattern
1
2
3
4
5
6
Ceiling
Fresh air inlet box + Fresh air lter chamber
Fresh air lter chamber
Auxiliary fresh air flange
Spacer for height adjustment
Air discharge direction kit
OK
OK
OK
OK
OK
1
Ceiling
2
Fresh air inlet box + Fresh airfilter chamber
OK
OK
OK
OK
3
Fresh airfilter chamber
OK
OK
OK
OK
4
Auxiliary fresh air flange
OK
OK
OK
OK
OK
5
Spacer for height adjustment
OK
OK
OK
OK
6
Air discharge direction kit
OK
OK
OK
OK
2) Accessory for concealed duct high static pressure type/fresh air intake indoor unit type: combination pattern
1
2
High-efficiency filter 65 High-efficiency filter 90 -
OK
3
4
5
Long life prefilter
Filter chamber
Drain pump kit
OK
OK
OK
OK
OK
OK
OK
OK
1
High-efficiency filter 65
2
High-efficiency filter 90
3
Long life pre filter
OK
OK
4
Filter chamber
OK
OK
OK
5
Drain pump kit
OK
OK
OK
-
OK
OK OK
5
70
Œª≥±¨ª ›±≤¨Æ±¥¥ªÆ Œfi›Ûfl”ÃÌÓ€ ¯Œfi›Ûfl”ÃÌÔ€˜ ¯≥ø∑≤ ©∑ƪº ƪ≥±¨ª Ω±≤¨Æ±¥¥ªÆ˜ Ô
È
Ë
Á Ó ÔÍ ÔÁ ÔÈ
Ó Ì
Ô
Ï
‹∑≠∞¥øß ≠ªΩ¨∑±≤
ÔÓ Î ÔÔ
Í ÔÎ ÔÌ
ÔË
ÓÁ ÓË
—∞ªÆø¨∑±≤ ≠ªΩ¨∑±≤
ÌÓ ÓÓ
Ì ÓÏ ÌÔ
ÓÎ ÓÌ
‹∑≠∞¥øß ≠ªΩ¨∑±≤ Ô Õ€ÃÃ◊“Ÿ º∑≠∞¥øß ‹∑≠∞¥øßªº º´Æ∑≤π ≠ª¨´∞ ±∫ ¨∏ª ¨∑≥ªÆÙ ª¨ΩÚ —∞ªÆø¨∑±≤ ≥±ºª ≠ª¥ªΩ¨ º∑≠∞¥øß
Ó Ã∏ª ≠ª¥ªΩ¨ªº ±∞ªÆø¨∑±≤ ≥±ºª ∑≠
ÔÌ “± ∫´≤Ω¨∑±≤ º∑≠∞¥øß
Ã∑≥ª ±∫ ¨∏ª ¨∑≥ªÆ ∑≠ º∑≠∞¥øßªºÚ ¯…∏ª≤ ø ∞Ʊ楪≥ ±ΩΩ´Æ≠Ù ¨∏ª Ω∏ªΩµ Ω±ºª ∑≠ º∑≠∞¥øßªºÚ˜
Î Ã∑≥ªÆ Հà ◊“ ≠ª¨´∞ º∑≠∞¥øß
…∏ª≤ ∞´≠∏∑≤π ¨∏ª Ã∑≥ªÆ Հà ◊“ æ´¨¨±≤Ù ¨∏ª º∑≠∞¥øß ±∫ ¨∏ª ¨∑≥ªÆ ∑≠ ≠ª¥ªΩ¨ªº ∑≤ ±ÆºªÆ ±∫ ≈—⁄⁄√ ƪ∞ªø¨ ≈—⁄⁄√ —⁄⁄ ¨∑≥ªÆ ≈—“√ “± º∑≠∞¥øßÚ
™±¥´≥ª ≠ª¥ªΩ¨ º∑≠∞¥øß ÔÏ fl∑Æ Ã∏ª ≠ª¥ªΩ¨ªº ø∑Æ ™±¥´≥ª ≥±ºª ∑≠ º∑≠∞¥øßªºÚ ¯flÀט ¯ ”€‹Ú˜
–±©ªÆÛ≠ø™∑≤π ≥±ºª º∑≠∞¥øß ÔÈ ‹∑≠∞¥øßªº º´Æ∑≤π Ωø∞øΩ∑¨ß
Ô Õª¨ ´∞ ¨ª≥∞ªÆø¨´Æª º∑≠∞¥øß Ã∏ª ≠ª¥ªΩ¨ªº ≠ª¨ ´∞ ¨ª≥∞ªÆø¨´Æª ∑≠ º∑≠∞¥øßªºÚ ÔÔ Œª≥±¨ª Ω±≤¨Æ±¥¥ªÆ ≠ª≤≠±Æ
º∑≠∞¥øß ‹∑≠∞¥øßªº ©∏∑¥ª ¨∏ª ≠ª≤≠±Æ ±∫ ¨∏ª ƪ≥±¨ª Ω±≤¨Æ±¥¥ªÆ ∑≠ ´≠ªºÚ
ÔÓ –Œ€Ûÿ€flà º∑≠∞¥øß
‹∑≠∞¥øßªº ©∏ª≤ ¨∏ª ∏ªø¨∑≤π ±∞ªÆø¨∑±≤ ≠¨øÆ¨≠ ±Æ ºª∫Ʊ≠¨ ±∞ªÆø¨∑±≤ ∑≠ ΩøÆÆ∑ªº ±´¨Ú …∏∑¥ª ¨∏∑≠ ∑≤º∑Ωø¨∑±≤ ∑≠ º∑≠∞¥øßªºÙ ¨∏ª ∑≤º±±Æ ∫ø≤ ≠¨±∞≠Ú
ÓÌ
æ´¨¨±≤ ¯›∏ªΩµ æ´¨¨±≤˜ Ã∏ª ›ÿ€›’ æ´¨¨±≤ ∑≠ ´≠ªº ∫±Æ ¨∏ª Ω∏ªΩµ ±∞ªÆø¨∑±≤Ú ‹´Æ∑≤π ≤±Æ≥ø¥ ±∞ªÆø¨∑±≤Ù º± ≤±¨ ´≠ª ¨∏∑≠ æ´¨¨±≤Ú
ÓÏ
≠ø™∑≤π ≥±ºª æß ¨ª≥∞±ÆøÆß ∞ªøµÛΩ´¨ ¥∑≥∑¨∑≤π ¨∏ª ∞±©ªÆ Ω´ÆÆª≤¨ ¥ª™ª¥ ±∫ ¨∏ª ±´¨º±±Æ ´≤∑¨Ú ¥±Ωµ º∑≠∞¥øß ÔË ‘±´™ªÆ ‹∑≠∞¥øßªº ©∏ª≤ ¨∏ªÆª ∑≠ ø
È Ã€Õà ƴ≤ º∑≠∞¥øß
Á Õ…◊“Ÿ º∑≠∞¥øß ‹∑≠∞¥øßªº º´Æ∑≤π ´∞Òº±©≤ ≥±™ª≥ª≤¨ ±∫ ¨∏ª ¥±´™ªÆÚ
æ´¨¨±≤ ¯Ã∑≥ªÆ ≠ª¨ æ´¨¨±≤˜ Ã◊”€Œ Հà 洨¨±≤ ∑≠ ´≠ªº ©∏ª≤ ¨∏ª ¨∑≥ªÆ ∑≠ ≠ª¨ ´∞Ú
‹∑≠∞¥øßªº º´Æ∑≤π ºÆß ±∞ªÆø¨∑±≤ ∑≤ ≠ª¥∫ÛΩ¥ªø≤∑≤π ∫´≤Ω¨∑±≤Ú
À≤∑¨ “´≥æªÆ º∑≠∞¥øß À≤∑¨ ≤´≥æªÆ ±∫ ¨∏ª ∑≤º±±Æ ´≤∑¨ ≠ª¥ªΩ¨ªº ©∑¨∏ ¨∏ª ´≤∑¨ ≠ª¥ªΩ¨ æ´¨¨±≤ ±Æ øæ≤±Æ≥ø¥ ∑≤º∑Ωø¨ª ¨∏ª ∑≤º±±ÆÒ±´¨º±±Æ ´≤∑¨Ú
‹∑≠∞¥øß≠ ¥±´™ªÆ ∞±≠∑¨∑±≤Ú
ÓÓ
±∞ªÆø¨∑±≤ ∑≤ ≠ª¥∫ÛΩ¥ªø≤∑≤π ÔÍ ‹Æß ∫´≤Ω¨∑±≤
¥±´™ªÆÛ¥±Ωµªº ´≤∑¨ ∑≤ ¨∏ª πÆ±´∞ ¯∑≤Ω¥´º∑≤π Ô ∑≤º±±Æ ´≤∑¨ æß Ô ±´¨º±±Æ ´≤∑¨˜Ú
Ë ‘±´™ªÆ ∞±≠∑¨∑±≤ º∑≠∞¥øß
ÎÈ
“´≥æªÆ º∑≠∞¥øß ÔÎ ‘±´™ªÆ ¯ª®ø≥∞¥ªÊ ÔÙ ÓÙ Ì٠Ϙ
å ∑≠ º∑≠∞¥øßªºÙ Ω¥ªø≤
‹∑≠∞¥øßªº º´Æ∑≤π ø ¨ª≠¨ Æ´≤Ú
æ´¨¨±≤ ¯fl∑Æ ™±¥´≥ª ≠ª¥ªΩ¨ æ´¨¨±≤˜ Õª¥ªΩ¨≠ ¨∏ª ºª≠∑ƪº ø∑Æ ™±¥´≥ª ≥±ºªÚ
¯ÿ◊Ÿÿ˜ ¯‘—…˜
Í ⁄∑¥¨ªÆ º∑≠∞¥øß ◊∫ ç⁄◊‘ÀŒ
ÓÔ
‹∑≠∞¥øßªº ∑∫ ¨∏ªÆª ∑≠ ≤± ∫´≤Ω¨∑±≤ ª™ª≤ ∑∫ ¨∏ª æ´¨¨±≤ ∑≠ ∞´≠∏ªºÚ
Ì ›ÿ€›’ º∑≠∞¥øß
Ï Ã∑≥ªÆ ¨∑≥ª º∑≠∞¥øß
ÓÈ
ÓÍ ÓÔ
—∞ªÆø¨∑±≤ ≠ªΩ¨∑±≤
º∑≠∞¥øßªºÚ ‹∑≠∞¥øßªº ©∏∑¥ª ¨∏ª ∞Ʊ¨ªΩ¨∑™ª ºª™∑Ωª ©±Æµ≠ ±Æ ø ∞Ʊ楪≥ ±ΩΩ´Æ≠Ú
ÔÏ
ÔÁ
Ω±≤º∑¨∑±≤ªÆ ∑≠ ´≠ªº ´≤ºªÆ ¨∏ª Ωª≤¨Æø¥ Ω±≤¨Æ±¥ ∑≤ Ω±≥æ∑≤ø¨∑±≤ ©∑¨∏ ø Ωª≤¨Æø¥ Ω±≤¨Æ±¥ ƪ≥±¨ª Ω±≤¨Æ±¥¥ªÆÚ ◊≤ Ωø≠ª ¨∏ª ƪ≥±¨ª Ω±≤¨Æ±¥¥ªÆ ∑≠ º∑≠øæ¥ªº æß ¨∏ª Ωª≤¨Æø¥ Ω±≤¨Æ±¥ Ú Ã∏ª æ´¨¨±≤ ±∞ªÆø¨∑±≤ ∑≠ ≤±¨ øΩΩª∞¨ªºÚ €™ª≤ ©∏ª≤ ß±´ ∞´≠∏ —“Ò—⁄⁄Ù ”—‹€Ù ±Æ À”–Ú æ´¨¨±≤Ù ø≤º ¨∏ª æ´¨¨±≤ ±∞ªÆø¨∑±≤ ∑≠ ≤±¨ øΩΩª∞¨ªºÚ ¯Õª¨¨∑≤π≠ ≥øºª æß ¨∏ª ƪ≥±¨ª Ω±≤¨Æ±¥¥ªÆ ™øÆß ©∑¨∏ ¨∏ª Ωª≤¨Æø¥ Ω±≤¨Æ±¥ ≥±ºªÚ ⁄±Æ ºª¨ø∑¥≠٠ƪ∫ªÆ ¨± ¨∏ª —©≤ªÆé≠ ”ø≤´ø¥ ±∫ ¨∏ª Ωª≤¨Æø¥ Ω±≤¨Æ±¥ ƪ≥±¨ª Ω±≤¨Æ±¥¥ªÆÚ˜
æ´¨¨±≤ ¯⁄∑¥¨ªÆ ƪ≠ª¨ æ´¨¨±≤˜ Œª≠ª¨≠ ¯€Æø≠ª≠˜ ç⁄◊‘ÀŒ å º∑≠∞¥øßÚ
ÓÍ
æ´¨¨±≤ ¯–±©ªÆÛ≠ø™ª ±∞ªÆø¨∑±≤˜ Õfl € æ´¨¨±≤ ∑≠ ´≠ªº ∫±Æ ∞±©ªÆÛ ≠ø™ª ±∞ªÆø¨∑±≤Ú ›ø≤≤±¨ æª ´≠ªº ∑≤ Õ””Õ≠Ú
ÓÈ
æ´¨¨±≤ …∏ª≤ ¨∏ª æ´¨¨±≤ ∑≠ ∞´≠∏ªºÙ ±∞ªÆø¨∑±≤ ≠¨øÆ¨≠Ù ø≤º ∑¨ ≠¨±∞≠ æß ∞´≠∏∑≤π ¨∏ª æ´¨¨±≤ øπø∑≤Ú …∏ª≤ ±∞ªÆø¨∑±≤ ∏ø≠ ≠¨±∞∞ªºÙ ¨∏ª ±∞ªÆø¨∑±≤ ¥ø≥∞ ø≤º ø¥¥ ¨∏ª º∑≠∞¥øß≠ º∑≠ø∞∞ªøÆÚ
Ì
æ´¨¨±≤ ¯—∞ªÆø¨∑±≤ ≠ª¥ªΩ¨ æ´¨¨±≤˜ Õª¥ªΩ¨≠ ºª≠∑ƪº ±∞ªÆø¨∑±≤ ≥±ºªÚ
ÌÔ
æ´¨¨±≤ ¯À≤∑¨Ò‘±´™ªÆ ≠ª¥ªΩ¨ æ´¨¨±≤˜ Õª¥ªΩ¨≠ ø ´≤∑¨ ≤´≥æªÆ ¯¥ª∫¨˜ ø≤º ¥±´™ªÆ ≤´≥æªÆ ¯Æ∑π∏¨˜Ú
æ´¨¨±≤ ¯ ª≤¨∑¥ø¨∑±≤ æ´¨¨±≤˜ ª≤¨∑¥ø¨∑±≤ æ´¨¨±≤ ∑≠ ´≠ªº ©∏ª≤ ø ∫ø≤ ©∏∑Ω∏ ∑≠ ≠±¥º ≠ª∞øÆø¨ª¥ß ∑≠ Ω±≤≤ªΩ¨ªºÚ å ∑≠ º∑≠∞¥øßªº ±≤ ¨∏ª ƪ≥±¨ª Ω±≤¨Æ±¥¥ªÆ ©∏ª≤ ∞´≠∏∑≤π ¨∏ª ª≤¨∑¥ø¨∑±≤ æ´¨¨±≤Ù ø ∫ø≤ ∑≠ ≤±¨ Ω±≤≤ªΩ¨ªºÚ
ÓÎ
Ω±≤¨Æ±¥ º∑≠∞¥øß Ó ›ª≤¨Æø¥ ‹∑≠∞¥øßªº ©∏ª≤ ¨∏ª ø∑Æ
ÓÁ
æ´¨¨±≤ ¯Õ©∑≤πÒ…∑≤º º∑ÆªΩ¨∑±≤ æ´¨¨±≤˜ Õª¥ªΩ¨≠ ø´¨±≥ø¨∑Ω ≠©∑≤π ±Æ ≠ª¨¨∑≤π ¨∏ª ¥±´™ªÆ º∑ÆªΩ¨∑±≤Ú
ÓË —∞ªÆø¨∑±≤ ¥ø≥∞
‘ø≥∞ ∑≠ ¥∑¨ º´Æ∑≤π ±∞ªÆø¨∑±≤Ú ‘ø≥∞ ∑≠ ±∫∫ ©∏ª≤ ≠¨±∞∞ªºÚ ±∞ªÆø¨∑≤π ¨∏ª ∞Ʊ¨ªΩ¨∑±≤ ºª™∑Ωª ±Æ øæ≤±Æ≥ø¥ ¨∑≥ªÚ
À“◊ÃÊ Õª¥ªΩ¨≠ ø≤ ∑≤º±±Æ ´≤∑¨ ©∏ª≤ øº∂´≠¨∑≤π ©∑≤º º∑ÆªΩ¨∑±≤ ©∏ª≤ ≥´¥¨∑∞¥ª ∑≤º±±Æ ´≤∑¨≠ øÆª Ω±≤¨Æ±¥¥ªº ©∑¨∏ ±≤ª ƪ≥±¨ª Ω±≤¨Æ±¥¥ªÆÚ ¯ÏÛ©øß ø∑Æ º∑≠Ω∏øÆπª Ωø≠≠ª¨¨ª ¨ß∞ª ±≤¥ß˜ ‘—À €ŒÊ Õª¥ªΩ¨≠ ø ¥±´™ªÆ ©∏ª≤ ≠ª¨¨∑≤π ¥±´™ªÆ ¥±Ωµ ±Æ ©∑≤º º∑ÆªΩ¨∑±≤ øº∂´≠¨≥ª≤¨ ∑≤ºª∞ª≤ºª≤¨¥ßÚ
ÌÓ
æ´¨¨±≤ ¯Õª¨ ´∞ ¨ª≥∞ªÆø¨´Æª æ´¨¨±≤˜ flº∂´≠¨≠ ¨∏ª Ʊ±≥ ¨ª≥∞ªÆø¨´ÆªÚ Õª¨ ¨∏ª ºª≠∑ƪº ≠ª¨ ¨ª≥∞ªÆø¨´Æª ±Æ æß ∞´≠∏∑≤π Ú
—–Ã◊—“Ê Œª≥±¨ª Ω±≤¨Æ±¥¥ªÆ ≠ª≤≠±Æ À≠´ø¥¥ß ¨∏ª À”–Ú ≠ª≤≠±Æ ±∫ ¨∏ª ∑≤º±±Æ ´≤∑¨ ≠ª≤≠ª≠ ¨∏ª ¨ª≥∞ªÆø¨´ÆªÚ Ã∏ª ¨ª≥∞ªÆø¨´Æª ≠´ÆÆ±´≤º∑≤π ¨∏ª ƪ≥±¨ª Ω±≤¨Æ±¥¥ªÆ Ωø≤ ø¥≠± æª ≠ª≤≠ªºÚ ⁄±Æ ºª¨ø∑¥≠Ù Ω±≤¨øΩ¨ ¨∏ª ºªø¥ªÆ ∫Ʊ≥ ©∏∑Ω∏ ß±´ ∏ø™ª ∞´ÆΩ∏ø≠ªº ¨∏ª ø∑Æ Ω±≤º∑¨∑±≤ªÆÚ ˆ Ã∏ª Œfi›Ûfl”ÃÌÔ€ º±ª≠ ≤±¨ ∏ø™ª ø Õfl € æ´¨¨±≤Ú fi´¨¨±≤≠ º∑≠∞¥øßªº ∑≤ ∞∏±¨± ™øÆß ≠¥∑π∏¨¥ß ∫±Æ Œfi›Ûfl”ÃÌÔ€Ú
61 71
Remote Controller - Wireless Kit Wireless Handset Easy to use remote control with a compact button layout and a fresh new design. • Setting operation mode: cool, heat, dry, fan. • Setting of temperature and fan speed • Swing louver or fix louver position. • Hi power function for an extra strong air flow. • Comfort sleep operation: to save energy the air flow is controlled automatically; depending on timer the indoor unit turns off automatically after 1,3 5 or 9 hrs. • Quiet Mode: the indoor unit operates at a super low fan speed level for extra quiet operation.
Control by 2 remote controllers is available. • Check code display * The wireless remote control cannot be connected to Concealed duct high static pressure type or Fresh air intake indoor unit type.
RBC-AX32U(W)-E/RBC-AX32U(WS)-E Integral receiver (For 4-way air discharge cassette)
RBC-AX23UW(W)-E Integral receiver (For 2-way air discharge cassette)
RBC-AX32CE2 Integral receiver (For Ceiling, 1-way air discharge cassette (MMU-AP***4SH-E)
TCB-AX32E2 Stand alone receiver (For 4-way air discharge cassette, Compact 4-way cassette, 2-way air discharge cassette, Ceiling, Concealed duct standard, Slim duct, Floor standing cabinet, Floor standing, 1-way discharge cassette (MMU-AP***4YH-E)
Remote Controller - Wired Remote controller with weekly timer (7-day timer function) RBC-AMS41E • Clock display • Schedule timer: Possible to program schedule timer (7-day timer) function Possible to program 8 functions for each day of the week * The following items can be set in program: Operation time, Operation start/stop, Operation mode, Temperature setting, Restriction on button operation
Lite - Vision Plus Remote Controller The RBC-AMS51E is the new local remote controller with a built in 7-Day Timer. It features a backlight display with operation instructions shown in 11 languages.
RBC-AMS51E-ES : English, Spanish, Portuguese, French, Dutch, German. RBC-AMS51E-EN : English, Italian, Polish, Greece, Russian, Turkish. Function: • Operation On/Off • Operation Mode. • Set Temperature • Air Flow Control • Air Direction Control • Programmable Button Restrictions. • Error Code • Filter Sign
Features: • Possibility to set and display the room name to easily set-up and monitor the working parameters. • New Modern and desirable controller design with menu driven display. • Save mode by schedule timer to optimize energy consumption. • Room temperature display always available. • Two “Hot Keys” (F1, F2) for easy operation of air conditioner functions. • Easy to read layout including display of Indoor Unit Model Name and serial number. • Built-in backup power. Settings are kept in memories up to 48 hours in case of power failure • Remote TA sensor available in controller. • Can be connected to a single Indoor Unit or a group of up to 8 Indoor Units.
Up to 8 indoor unit
Local control wiring diagram
5
62 72
Central Controller ON-OFF controller TCB-CC163TLE2
• Individual control of up to 16 indoor units. • Connection by 2 remote controllers is available. • Setting of simultaneous ON/OFF 3 times per day combined with the weekly timer.
Central remote controller TCB-SC642TLE2
• Individual control of up to 64 indoor units. • Individual control for max. 64 indoor units divided into 1 to 4 zone (Up to 16 indoor units for each zone) • Up to 16 outdoor header units are connectable • 4 types of central control settings to inhibit individual operation by remote controller can be selected. • Setting for one of 1 to 4 zones is available. • Usable with other central control devices (Up to 10 central control devices in one control circuit) • Two control mode selectivity (Central controller mode ) Remote controller mode • Setting of simultaneous ON/OFF 3 times per day combined with the weekly timer.
Schedule Timer TCB-EXS21TLE
• Schedule timer mode – 6 programmings per day – Enabling 8 groups to be programmed – A maximum of 64 indoor units can be controlled – A maximum of 100 hours back-up power supply • Weekly timer mode – 7 types of weekly schedule and 3 programmings per day – Can program off mode by one-minute units.
Compliant Manager The Compliant Manager Controller is an advanced Central Control device that is used for VRF Equipment and can be connected to up to 128 Indoor Units.
BMS-CM1280TLE Function • Operation On/Off. • Operation Mode • Set TemperatSet Temperature • Air Flow Control • Air Direction Control • Error Code • Filter Sign
• Advanced Zone Configuration. • External Input for Simultaneous Indoor Unit ON/OFF Control and external Alarm Input. • External Output for Operation status and Alarm Status. • 4-Pattern Permit/Prohibit Functions. • Return Back Function Available.
Central Control Device
63 73
Advance control systems Smart Manager with Data Analyzer The Smart Manager has the same hardware Control Function as the BMS-CM1280TLE Controller, but also has the ability of control from a Local Area Network and , with the use of an additional Interface, is capable of Energy Monitoring and Report Creation Functions. This controller is ideal where advanced control, Energy Monitoring, advanced scheduling or access to individual Air Conditioners is required from networked computer systems. Web Browser Control Software Features • List View available -Displays all Indoor Units from one screen • Set View available – Shows Basic Indoor Unit settings on main screen g • Advanced Operation and Master schedule functions available • Up to 4 Concurrent s can be connected • Up to 32 s can be programmed with different levels of access (at least 1 must be level)
BMS-SM1280ETLE
Power Meter Pulse signal
BMS-IFWH5E
RS-485 Network
TCC-Link Line 1 Digital Input Output signal
TCC-Link Line 2 BMS-IFDD03E
TCB-EXS21TLE Schedule Timer
Digital Inputs Digital Outputs
TCB-PCNT30TLE2*
NETWORK HUB
* TCC-Link Adaptor for Digital/Super Digital Indoor Units.
Up to 32 s Max. 4 Concurrent s
Equipment List Device
Number of pieces
Description
BMS-SM1280ETLE
1
Up to 128 indoor unit can be connected to Smart Manager
BMS-IFDD03E
Up to 4 Boards
Interface for Digital Input & Outputs. Can connect up to 8 Power Meters per Board (Optional )
BMS-IFWH5E
Up to 4 Boards
Interface for Power Meter (Energy Monitoring Option only)
Number of pieces
Energy consumption history (days) Description
Locally Procured Item Device
Energy consumption comparison
Alarm list
Energy consumption history (hours)
Power Meter
Digital Energy Meter with Pulse Output ( Energy Monitoring Option only)
PC
For Operation Monitoring
Network Hub
For LAN Connection.
Energy consumption history (days)
T_12_CT_GEN_EN__print.indd 165
Energy consumption comparison
Alarm list
TOSHIBA | 165
02/03/12 14.31
Energy consumption history (Hours)
62 64 74
5
Advance control systems Touch-screen controller • Touch-screen controller Using the touch-screen controller provides a clear display and enables easy operation. A maximum of 512 units are controllable using the one-touch controller. • Function – Operation monitoring – Operation control – Operation Schedule – Error Code – Alarm List – Energy monitoring/Billing – Digital I/O Signal Control
Touch-screen Controller BMS-CT5120E
Up to 12
Up to 8
Up to 8
Relay Interface BMS-IFLSV4E For TCS-NET
Relay Interface BMS-IFWH5E For Energy Monitoring (Optional)
Relay Interface BMS-IFDD03E For Digital I/O (Optional)
CONTROL WIRING RS-485 Network
TCS-Net Relay I/F BMS-IFLSV4E TCC-Link Network
Energy Monitoring I/F BMS-IFWH5E
Digital Input/Output I/F BMS-IFDD03E
• Power Meter (Local Supply) 1 kWh/pulse or 10 kWh/pulse (Pulse duration 50 to 1000 ms) (Maximum 8 power meter per interface)
Digital I/O Digital Input 1
Digital Input 8
Digital Output 1 Power Meter 1
-
Digital Output 4 Network Hub
Power Meter 8
PC for Energy Monitoring
65 75
Advance control systems WEB Based Controller
WEB Based Controller BMS-WB2561PWE (Web Server/Gateway Server)
WEB Based Controller BMS-WE01GTE (Master Server)
Up to 8 Relay Interface BMS-IFLSV4E For TCS-NET
•WEB Based Controller Signals and provides the following functions : – Operation monitoring – Operation control – Operation Schedule – Error Code – Alarm List – Energy monitoring/Billing – Digital I/O Signal Control Connect the WEB server for every 256 indoor units, and connect a gateway server upstream from the server.
Up to 4
Up to 4
Relay Interface BMS-IFWH5E For Energy Monitoring (Optional)
Relay Interface BMS-IFDD03E For Digital I/O (Optional)
Web Based Controller (Web Server System) System diagram for connecting 256FCUs or less TCS-NET Interface BMS-IFLSV4E
WEB Server BMS-WB2561PWE
TCS-NET Interface BMS-IFLSV4E
Local Supply
Web Based Controller (Master Server System) System diagram for connecting upto 2048FCU TCS-NET Interface BMS-IFLSV4E
Master Server BMS-WB01GTE
Gateway BMS-WB2561PWE
TCS-NET Interface BMS-IFLSV4E
Gateway BMS-WB2561PWE
Local Supply
5
66 76
Open Network systems BACnet® system • BACnet®
The BACnet® system operates in conjunction with the BAC net server. Server uses object signals to provide the following functions: Object signals command – ON/OFF – Mode: cool/heat/fan – Temperature setting – Central/local – Fan speed Monitoring – ON/OFF etc.
Intelligent Server BMS-LSV9E
Mode – Cool/heat/fan/failure – Temperature setting – Room temperature – Central/local, etc.
Relay Interface BMS-IFLSV4E For TCS-NET
BACnet® Server Software BMS-STBN10E
BACnet® IP BMS-STBN10E Local supply
RS-485
TCS-NET Relay Interface BMS-IFLSV4E
Main bus
Intelligent server (BACnet® server software required) BMS-LSV9E
KNX® Interface • KNX® The KNX® interface manages the SMMS-i air conditioning system as a KNX® device to communicate with the custormer s Home automation. Accessible to 64 units per one , Signals and provides the following functions: – ON/OFF – Mode: cool/heat/fan – Air flow and fan speed – Temperature setting – Filter reset
TO-AC-KNX-64
KNX Control
Main bus KNX Network
KNX Interface TO-AC-KNX-64 Lighting
Blind & Shutter
Electrical appliance
Audio & Video
67 77
Open Network systems BACnet® system • LonWorks® LN Interface The LonWorks® interface manages the SMMS-i air conditioning system as a Lon device to communicate with the custormer’s Building Management System and to monitor operational status. A maximum of 64 units are controllable per interface. • SNVT signal Signals and provides the following functions: Object signals command – ON/OFF – Mode: cool/heat/fan – Temperature setting – Central/local
LN Interface TCB-IFLN642TLE
• Monitoring – ON/OFF • Mode – Cool/heat/fan/failure – Temperature setting – Room temperature – Central/local, etc.
Main Bus Local supply
LN Interface TCB-IFLN642TLE
Modbus® • Modbus® The Modbus® interface manages the SMMS-i air conditioning system as a Modbus® device to communicate with the custormer’s Building Management System. Accessible to 64 units per one TCB-IFMB641TLE, 15 TCB-IFMB641TLEs on one Modbus® Master (prepared by ).
Modbus Interface TCB-IFMB641TLE
Signals and provides the following functions: – ON/OFF – Mode: cool/heat/fan – Air flow/Louver setting – Temperature setting – Filter reset – Accumulated operation time, etc.
Local supply
Main Bus
RS-485
Modbus® Interface TCB-IFMB641TLE
1. LonWorks®: ed trademark Echelon corporation 2. BACnet®: ANSI/ASHRAE 135-1995, A data Communication Protocol for Building Automation and Control Networks. 3. Modbus® is a ed trademark of Schneider E.
5
68 78
Application Controls TCB-PCDM4E
Power peak-cut Control • Feature
Size: 71 x 85 (mm)
The upper limit capacity of the outdoor unit is restricted based on the outdoor power peck selected setting. * Install the optional P.C. board in the inverter assembly of the outdoor header unit.
• Function Two control settings are selectable by setting SW07 on the interface P.C. board on the header outdoor unit.
TCB-PCMO4E
Size: 55.5 x 60 (mm)
Snowfall fan control • Feature
The upper limit capacity of the outdoor unit is restricted based on the outdoor power peck selected setting.
* Install the optional P.C. board in the inverter assembly of the outdoor header unit.
External master ON/OFF control • Feature
The outdoor unit starts or stops the system.
Night operation (Sound reduction) control • Feature
Sound level can be reduced by restricting the compressor and fan speeds.
Operation mode selection control • Feature
The control can restrict the selectable operation mode.
TCB-IFCB5-PE This is an application control PC Board that is capable of providing two different control functions when connected to a Toshiba Indoor Unit, these are:
• •
• Window Switch Function • Remote Location On/Off Controller
TCB-IFCB5-PE
Each time the window is opened ( open) the Indoor Unit operation is turned Off and will not operate again until the window is closed. There are two possible operation selections for when the window is closed again.
Standard Function Mode
• Standard Function Mode The Indoor Unit operation remains Off.
Return Function Mode
• Return Function Mode The Indoor Unit will revert to the last setting before the window was opened.
69 79 TCB-PCIN4E Size: 73 × 79 (mm)
* Install the optional P.C. board in the inverter assembly of the outdoor header unit.
Error/Operation output control
• Feature Enables external output of error and operation signals.
Compressor operation output • Feature
L1 : Operation monitoring lamp L2 : Error monitoring lamp Operation monitoring: Display relay is ON with more than one indoor unit operation. EMG monitoring: Display relay is ON when the system is in error status.
Enables external signal output for each compressor that is in operation within any given outdoor unit. This feature provides a practical method for calculating total operating times for each compressor.
Operating rate output • Feature
External output of system operating rates enables remote monitoring of operating conditions.
TCB-IFCB-4E2 Remote location ON/OFF control box Size: 200 × 170 × 66 (mm)
• Feature Start and stop of the air conditioner is possible by an external signal and indication of operation/alarm externally. Operation
Monitoring ON/OFF status (for indoor unit) Alarm status (system & indoor unit stop) ON/OFF command Air conditioner can be turned ON/OFF by the external signals. The external ON/OFF signals will initiate the signals shown below.
ON/OFF
Interface Display Remote Controller
Non-voltage ON/OFF continuous signal
COM
TCB-PCNT30TLE2
Network adapter
Size: 85 × 52 (mm) Install optional P.C. board in E-parts of the indoor unit.
• Feature Link adapter for “1:1 model” to enable connection to VRF system network. 1:1 model: Super digital inverter Digital inverter Used only for light commercial products
ON-OFF control
Central control devices
Indoor unitIndoor unit
Indoor control P.C.board
Adaptor
A
ON-OFF Controller TCB-CC163TLE2
Indoor unit
U3 U4 Indoor control P.C.board
B
A
B
Indoor control P.C.board A
B
Remote controller
Controller TCB-SC642TLE2 Connecting terminal block BLU
U3 U4 BLU 1 2 SMMS-i control wiring
1 2 CN40 (BIU) CN51 (RED)
1:1 model connection interface
adapter Indoor units
Digital Inverter Super Digital Inverter Outdoor unit
1 2 3 4 5
1 2 3 4 5
WHI RED RED RED RED
1 2 3 4 5
1 CN50 (WHI) 2 Indoor control 3 P.C.board 4 5
66 70 80
5 General Purpose Interface General purpose interface TCB-IFCG1TLE
Concept
TCC-LINK
• Controls the operation status of each indoor unit. • ON/OFF control of peripheral equipment via the relay point of Toshiba's BMS. (1pt only) • Provides 4-channel relay control, 6-channel digital input, 2-channel analog voltage input and output, and 2-channel temperature measurement functions via Modbus I/F.
Programmable conjunction function (HA) Daiseikai
Sensor
Switches
Pump/ motor
Operation of specified indoor units can interlock with input signal.
Lights
GSM Phone Control Interface
Concept
GSM phone control interface TCB-IFGSM1E
GSM modem
• ON/OFF control and status monitoring of the air-conditioner via the SMS system of GSM mobile phones. • Up to 5 mobile phone numbers can be ed for on/off control and status monitoring. • Auto alarm transfer function for SMMS-i, SDI, DI. • Up to 5 mobile phone numbers can be ed for an alarm signal output.
RC-232C
AC Adapter Not required when CN61 is used
Indoor units connectors Toshiba Indoor Units have a number of Connectors built in to allow for connection and control of external equipment and control/monitoring of the Air Conditioner Cable Model Name
Function
Connector
Outline
TCB-KBCN32VEE
Fan output
CN32.
External Ventilation fan control from Remote controller.
TCB-KBCN60OPE
Option output
CN60
Operation status signal output (cooling, heating, fan, defrost, thermo-ON)
TCB-KBCN61HAE
Operation Input / Output
CN61
External ON/OFF control, operation ON/ OFF status output, alarm status output
TCB-KBCN70OAE
Option error input
CN70
Alarm display on Remote controller by this input
TCB-KBCN73DEE
Demand input
CN73
Forced thermo-o control by this input
TCB-KBCN80EXE
Outside error input
CN80
Generate check code “L30” (for 1 minutes continuously) to stop forcedly the operation
71 81 Control Devices Model Number
Reference
Description
Used with
RBC-AMT32E
Wired Remote Controller
Main wired remote controller
VRF and VRF Air-to-air heat exchangers with (DX coil) indoor units
RBC-AS41E
Simplified Wired Remote Controller
As above but designed for hotel and domestic applications
VRF and VRF Air-to-air heat exchanges with (DX coil) indoor units
NRC-01HE
Wired Remote Controller
Wired remote controller for Air-to-air heat exchanger, including with DX coil and humidifiers models
New Air-to-air heat exchangers and Air-to-air heat exchangers with DX coil
TCB-EXS21TLE
Schedule timer
Operating in weekly timer mode or schedule timer mode
VRF and VRF Air-to-air heat exchangers with (DX coil) indoor units
RBC-AMS41E
Remote controller with schedule timer
Enables to control indoor unit operation with schedule timer (7-days) allowing to program 8 functions/day + clock display
VRF and VRF Air-to-air heat exchangers with (DX coil) indoor units
RBC-AMS51E-EN RBC-AMS51E-ES
Lite-Vision plus Remote Controller
Local Controller with Multi-Language LCD display, a built-in 7-Day timer, Energy Saving options and return back function. EN =English, Italian, Polish, Greek, Russian, Turkish. ES = English, Spanish, Portuguese, French, Dutch, German
VRF and VRF Air-to-air heat exchangers with (DX coil) indoor units
RBC-AX32CE2
Infra-red Remote Kit
Wireless remote controller
All ceiling units and one-way cassettes (SH series)
TCB-AX32E2
Infra-red Remote Kit
Wireless remote controller
All other units (including compact 4-way cassette
RBC-AX23UW(W)-E
Wireless remote unit kit
Wireless remote unit kit for 2-way cassette
2-way-cassette MMU-AP***2WH
RBC-AX32U(W)-E
Wireless remote unit kit
Wireless remote unit kit for 4-way cassette
RBC-U31PG(W)-E & RBC-U31PGS(W)-E s for 4-way cassette indoors.
RBC-AX32U(WS)-E
Wireless remote unit kit
Wireless remote unit kit for 4-way cassette
With RBC-U31PGS(WS)-E s for 4-way cassette indoors.
TCB-TC21LE2
Remote temperature sensor
Remote temperature sensor for cassette & duct
All VRF
TCB-SC642TLE2
Central Remote Controller
Enables the control of up to 64 individual units
All VRF indoor units.
TCB-CC163TLE2
On / Off Controller
Enables On / Off control (Max. 16 units)
All VRF indoor units.
TCB-IFCB5-PE
Remote location On / Off Control Box
Enables remote location On / Off control
All VRF indoor units.
BMS-WB2561PWE
Web Based Controller ( Web Gateway )
Gateway server. Network Intranet connection, yearly schedule, error message history, up to 256 IDUs
All VRF indoor units.
BMS-WB01GTE
Web Based Controller ( Web Server )
Web server. Network Intranet connection, yearly schedule, error message history,up to 2048 IDUs All VRF indoor units.
All VRF indoor units.
BMS-CM1280TLE
Compliant Manager
Enables full control of up to 128 indoor units
All VRF indoor units.
BMS-SM1280ETLE
Smart Manager with Data analyzer
Enables full control of up to 128 indoor units with Energy Monitoring and Advanced Control Options
All VRF indoor units.
5
72 82 Control Devices Model Number
Reference
Description
Used with
BMS-TP0641ACE
Touch Screen Controller
Enables full control of up to 64 indoor units, ML
All VRF
BMS-TP5121ACE
Touch Screen Controller
Enables full control of up to 512 indoor units, ML
All VRF
BMS TP0641PWE
Touch Screen Controller
Enables full control of up to 64 indoor units with BMS-electric billing, ML
All VRF
BMS-TP5121PWE
Touch Screen Controller
Enables full control of up to 512 indoor units with electric billing, ML
All VRF
BMS-IFLSV4E
TCS-Net Relay Interface
Relay for integration to TCS-Net
Bacnet gateway, Touch-screens & Web based controller
BMS-IFWH5E
Energy monitoring relay interface
Energy monitoring relay interface
Touch screen controller, Compliant manager, Web based controller, Smart Manager
BMS-IFDD03E
Digital I/O relay interface
Digital I/O relay interface
Touch screen controller, Compliant manager, Web based controller, Smart Manager
BMS-LSV9E
Intelligent Server
Bacnet Gateway
Requires software BMS-STBN08E & Interface BMS-IFLSV3E
BMS-STBN10E
BACnet
Server Software
Enables integration with BACnet
BMS-STCC06E
Intelligent Server Software
Software package for the intelligent server
All VRF indoor units.
TCB-IFLN642TLE
Lonworks® Gateway
Allows control of 64 indoor units from a Lonworks based BMS
All VRF indoor units.
TCB-IFMB641TLE
Modbus Interface
Allows control of 64 indoor units from a Modbus based BMS
All VRF indoor units.
TO-AC-KNX-64
KNX Interface
Allows control of 64 indoor units from a KNX based BMS/Home Auto machine
All VRF indoor units.
TCB-IFCG1TLE
General purpose interface
Enables control of A/C by the DI/DO and AI/AO
All VRF indoor units.
TCB-IFGSM1E
GSM control interface
Allows ON/OFF control, operation status monitoring & alarm monitoring of A/C
All VRF indoor units.
TCB-PX30MUE
Terminal box
Steel Terminal box to connect to
TCB-PCNT30TLE2 , TCB-IFCB5-PE
TCB-PX100PE
Terminal box
Plastic Terminal box to connect to
TCB-PCNT30TLE2 , TCB-IFCB5-PE
TCB-IFCB-4E2
Application Control PC Board
Remote On/Off Control
All VRF indoor units.
TCB-IFCB5-PE
Application Control PC Board
Window Switch Remote On/Off control
All VRF indoor units.
TCB-PCDM4E
Application Control PC Board
Power Peak Cut Control
SMMS, SMMS-i, SHRM and Mini-SMMS Outdoor Units
TCB-PCMO4E
Application Control PC Board
External Master ON/OFF Control Board
SMMS, SMMS-i, SHRM and Mini-SMMS Outdoor Units
TCB-PCIN4E
Connectors
Error/Individual compressor Operation Output Control Board
SMMS SMMS i SHRM d Mi i SMMS O td U it
TCB-KBCN32VEE
For CN32
All VRF indoor units.
TCB-KBCN60OPE
For CN60
All VRF indoor units.
For CN61
All VRF indoor units.
TCB-KBCN70OAE
For CN70
All VRF indoor units.
TCB-KBCN73DEE
For CN73
All VRF indoor units.
TCB-KBCN80EXE
For CN80
All VRF indoor units.
TCB-KBCN61HAE
Application Control PC Board
73 83
SMMS-i Selection Tools Everything at the click of a button
Sophisticated system design software has been developed for the whole SMMS-i range and is a useful and irreplaceable tool for engineers, architects, installers and, in general, for anyone who wants to apply innovative Toshiba solutions. With this software, the can create a complete VRF system by simply clicking on the icons for the indoor units and the other connection components. It is also possible to define, in advance, relevant parameters such as outside and inside temperatures fan speed pipe system length and routing etc. The software automatically manages all the parameters entered, and the actual system capacity for the conditions required can be quickly calculated and simulated during the design stage. The software constantly monitors possible design errors and warns the , when it reaches the system limits. Features
* Graphical representation of the required pipe connection system and pipe sizing. * Specific details and data of the system selected: heating capacity, sensible and total cooling capacity, actual cooling capacity, additional refrigerant charge and pricing indications.
* Multiple system management as a single project * Export function to transfer the project report using standard Microsoft Word and Adobe Acrobat (PDF). The images can also be exported to an AutoCAD (DXF) file.
* Automatic regeneration when adding or amending an existing project selection. * Indoor unit fan speed indication (high /medium/low) on the system Report
Indoor Unit Selection
Refrigerant Line Diagram
Diagnostic software -DynaDoctor
( TCB-DK01SSE )
The correct operation of sophisticated systems such as VRF is important to the long-term reliability of the system. In order to assist with the correct commissioning of SMMS-i, Toshiba has developed a diagnostic software programme a valuable tool for the commissioning and service engineer. The engineer can connect to the VRF system using a dedicated interface – enabling the of all operating parameters and providing the engineer with detailed information for instant analysis or record.
Description of DynaDoctor Parts Dyna Doctor Hardware for SMMS-i Software for SMMS-i
Running Parameter views
5
74 84
Sharjah
About :
AHI Carrier Toshiba Solution Center is a world class training center, to cater product training and troubleshooting requirements of AHI Carrier’s Customer, Channel technicians & sales staff. This is to achieve greater customer satisfaction by : • Responding to their technical requirements quickly. • Identifying scope of product improvements by observing the products in running conditions.
Facilities :
• Product Display : Showcasing Toshiba Range of products for Residential, Small Offices & Large Buildings. • Product trainings : Hands-on product trainings. • VRF Live demonstration • Control Training : Hands-on training for VRF control system. • Troubleshooting
85
Conversion Table
5
86
Notice: Toshiba is commited to continuously improving its products to ensure the highest quality and reliability standards, and to meet local regulations and market requirements. All features and specifications are subject to change without prior notice.