Adhesive Anchoring Systems
HIT-RE 100 Adhesive Anchoring System 1.0
Product description
1.0 Product description
2.0
Technical data
3.0
Ordering information
The Hilti HIT-RE 100 adhesive anchoring system is used to resist static, wind and seismic tension and shear loads in normal-weight concrete having a compressive strength, f´c, of 17.2 MPa to 58.6 MPa. It is suitable to be used in cracked and uncracked concrete as defined per ICC-ES and ACI.
Listings/Approvals ICC-ES (International Code Council) ESR-3829 NSF/ANSI Std 61 certification for use of HIT-RE 100 in potable water City of Los Angeles Research Report No. 26027
Independent Code Evaluation IBC®/IRC® 2015 (ICC-ES AC308/ACI 355.4) IBC®/IRC® 2012 (ICC-ES AC308/ACI 355.4) IBC®/IRC® 2009 (ICC-ES AC308) IBC®/IRC® 2006 (ICC-ES AC308) LEED®: Credit 4.1-Low Emitting Materials
The Leadership in Energy and Environmental Design (LEED) Green Building Rating system™ is the nationally accepted benchmark for the design, construction, and operation of high performance green buildings.
Hilti HIT-RE 100 adhesive is an injectable two-component epoxy adhesive. The two components are separated by means of a dual-cylinder foil pack attached to a manifold. The two components combine and react when dispensed through a static mixing nozzle attached to the manifold.
• Mixing tube provides proper mixing, eliminates measuring errors and minimizes waste • Meets requirements of ASTM C88114, Type I, II, IV, and V Grade 3, Class A, B, C • Meets requirements of AASHTO specification M235, Type I, II, IV, and V Grade 3, Class A, B, C
Elements that are suitable for use with this system are as follows: threaded steel rods and steel reinforcing bars. Product Features • Seismic qualified with ICC-ES Acceptance Criteria AC308 and ACI 355.4 • Use in water-filled holes and underwater up to 50 m
2.0 Technical data
The following document is a supplement to the Hilti North American Product Technical Guide, Volume 2: Anchor Fastening Technical Guide, Edition 16. Specific sections in this supplement will refer to the aforementioned document. Please refer to the publication in its entirety for complete details on this product including data development, product specifications, general suitability, installation, corrosion and spacing and edge distance guidelines. To consult directly with a team member regarding our anchor fastening products, Hilti’s team of technical specialists on the following mail address
[email protected].
2.1 Material specifications
For material specifications for anchor rods and inserts, please refer to section 3.2.8.
2.2 ACI 318-14 Chapter 17 design
The load values contained in this section are Hilti Simplified Design Tables. The load tables in this section were developed using the Strength Design parameters and variables of ESR-3187 and the equations within ACI 318-14 Chapter 17. For a detailed explanation of the Hilti Simplified Design Tables, refer to section 3.1.6. Data tables from ESR-3187 are not contained in this section, but can be found at www.icc-es.org or at www.hilti.ae.
Hilti Middle East | www.hilti.ae | HIT-RE 100 Metric Technical Supplement 2016 1
Adhesive Anchoring Systems
HIT-RE 100 Adhesive Anchoring System 2.3 Hilti HIT-RE 100 adhesive with deformed reinforcing bars (rebar) Cracked or uncracked concrete
Permissible concete conditions
Permissible drilling methods
Dry concrete
Uncracked Concrete
Water-saturated concrete
Cracked Concrete
Water-filled holes
Hammer Drilling with Carbide Tipped Drill Bit
Submerged (underwater)
Table 1 — Specifications for rebar installed with HIT-RE 100 adhesive Setting information
Symbol Units
Nominal bit diameter
Rebar size 8
10
12
14
16
20
25
28
32
12
14
16
18
20
25
32
35
40
do
mm
minimum
hef,min
mm
60
60
70
75
80
90
100
112
128
maximum
hef,max
mm
160
200
240
280
320
400
500
560
640
Minimum concrete member thickness
hmin
mm
Minimum edge distance1
cmin
mm
40
50
60
70
80
100
125
140
160
Minimum anchor spacing
smin
mm
40
50
60
70
80
100
125
140
160
Effective embedment
hef + 30
hef + 2do
1 Edge distance of 44mm is permitted provided the rebar remains un-torqued.
2 Hilti Middle East | www.hilti.ae | HIT-RE 100 Metric Technical Supplement 2016
.
Adhesive Anchoring Systems
HIT-RE 100 Adhesive Anchoring System Table 2 - Hilti HIT-RE 100 adhesive design strength with concrete / bond failure for metric rebar in uncracked concrete1,2,3,4,5,6,7,8 Nominal rebar diameter mm 8
10
12
14
16
20
25
28
32
Tension — ϕNn Shear — ϕVn Effective embedment ƒ´c = 25 MPa ƒ´c = 30 MPa ƒ´c = 40 MPa ƒ´c = 50 MPa ƒ´c = 25 MPa ƒ´c = 30 MPa ƒ´c = 40 MPa ƒ´c = 50 MPa mm kN kN kN kN kN kN kN kN 60 72 96 160 60 90 120 200 70 108 144 240 75 126 168 280 80 144 192 320 90 180 240 400 100 225 300 500 112 252 336 560 128 288 384 640
9.0 10.7 14.3 23.9 11.2 16.8 22.4 37.3 15.7 24.2 32.2 53.7 18.9 31.8 42.4 70.6 22.5 40.5 54.1 90.1 27.7 60.3 80.4 134.0 32.5 90.6 120.8 201.4 38.5 110.7 147.6 246.0 47.1 140.7 187.6 312.6
9.1 10.9 14.6 24.3 11.4 17.1 22.8 38.0 16.0 24.6 32.8 54.7 19.3 32.4 43.2 71.9 22.9 41.3 55.0 91.7 30.4 61.4 81.9 136.4 35.6 92.3 123.1 205.1 42.2 112.7 150.3 250.5 51.6 143.3 191.0 318.3
9.4 11.3 15.0 25.0 11.7 17.6 23.5 39.1 16.4 25.3 33.8 56.3 19.8 33.3 44.4 74.0 23.6 42.5 56.7 94.4 31.6 63.2 84.3 140.4 41.1 95.0 126.6 211.1 48.7 116.0 154.7 257.8 59.5 147.4 196.6 327.6
9.6 11.5 15.4 25.6 12.0 18.0 24.0 40.0 16.8 25.9 34.5 57.6 20.3 34.1 45.4 75.7 24.1 43.4 57.9 96.6 32.3 64.6 86.2 143.6 43.2 97.1 129.5 215.8 52.7 118.6 158.2 263.6 66.6 150.8 201.0 335.0
9.6 23.1 30.9 51.4 12.1 36.2 48.2 80.4 33.8 52.1 69.4 115.7 40.7 68.5 91.3 152.1 48.5 87.3 116.4 194.0 59.8 129.9 173.1 288.6 70.0 195.2 260.3 433.8 83.0 238.4 317.9 529.8 101.4 303.0 404.0 673.3
9.8 23.6 31.4 52.4 12.3 36.8 49.1 81.8 34.4 53.0 70.7 117.8 41.5 69.7 93.0 154.9 49.4 88.9 118.6 197.6 65.5 132.2 176.3 293.9 76.7 198.8 265.0 441.7 90.9 242.8 323.7 539.5 111.0 308.5 411.4 685.6
10.1 24.3 32.3 53.9 12.6 37.9 50.5 84.2 35.4 54.6 72.8 121.3 42.7 71.8 95.7 159.5 50.8 91.5 122.0 203.4 68.1 136.1 181.5 302.4 88.5 204.6 272.8 454.6 105.0 249.9 333.2 555.3 128.2 317.5 423.4 705.7
10.3 24.8 33.1 55.1 12.9 38.8 51.7 86.1 36.2 55.8 74.4 124.0 43.7 73.4 97.8 163.1 52.0 93.6 124.8 208.0 69.6 139.2 185.6 309.3 93.0 209.2 278.9 464.9 113.6 255.5 340.7 567.8 143.4 324.7 432.9 721.6
1 2 3 4
See Section 3.1.8 for explanation on development of load values. See Section 3.1.8.6 to convert design strength value to ASD value. Linear interpolation between embedment depths and concrete compressive strengths is not permitted. Tabular values represent a single anchor without reductions for edge distance, anchor spacing, or concrete thickness. Shaded cells indicate that bond strength is the controlling failure mode. Compare to the steel values in Table 4. The lesser of the values is to be used for design. 5 Values are for the following temperature range: maximum short term temperature = 55°C, maximum long term temperature = 43°C. Short term elevated concrete temperatures are those that occur over brief intervals, e.g., as a result of diurnal cycling. Long term concrete temperatures are roughly constant over significant periods of time. 6 Tabular values are for dry concrete conditions. For water saturated concrete, water-filled drilled holes, or submurged (underwater) applications multiply design strength by 0.61. 7 Tabular values are for short term loads only. For sustained loads including overhead use, see Section 3.1.8.8. 8 Tabular values are for normal-weight concrete only. For lightweight concrete multiply design strength by λa as follows: For sand-lightweight, λa = 0.51. For all-lightweight, λa = 0.45. 9 Tabular values are for holes drilled in concrete with carbide tipped hammer drill bit. Diamond core drilling is not permitted. 10 Tabular values are for static loads only. Seismic design is not permitted for uncracked concrete.
Hilti Middle East | www.hilti.ae | HIT-RE 100 Metric Technical Supplement 2016 3
Adhesive Anchoring Systems
HIT-RE 100 Adhesive Anchoring System Table 3 — Hilti HIT-RE 100 adhesive design strength with concrete / bond failure for metric rebar in cracked concrete 1,2,3,4,5,6,7,8,9,10 Nominal rebar diameter mm 10
12
14
16
20
25
28
32
Tension — ϕNn Shear — ϕVn Effective embedment ƒ´c = 25 MPa ƒ´c = 30 MPa ƒ´c = 40 MPa ƒ´c = 50 MPa ƒ´c = 25 MPa ƒ´c = 30 MPa ƒ´c = 40 MPa ƒ´c = 50 MPa mm kN kN kN kN kN kN kN kN 60 90 120 200 70 108 144 240 75 126 168 280 80 144 192 320 90 180 240 400 100 225 300 500 112 252 336 560 128 288 384 640
4.2 6.3 8.4 14.0 5.9 9.1 12.1 20.1 7.3 12.3 16.5 27.4 9.0 16.1 21.5 35.8 12.6 25.2 33.6 56.0 17.0 38.2 50.9 84.8 19.9 44.9 59.8 99.7 24.3 54.7 72.9 121.6
4.3 6.4 8.5 14.2 6.0 9.2 12.3 20.5 7.5 12.6 16.8 27.9 9.1 16.4 21.9 36.5 12.8 25.6 34.2 57.0 17.3 38.9 51.8 86.4 20.3 45.7 60.9 101.6 24.8 55.7 74.3 123.8
4.4 6.6 8.8 14.7 6.2 9.5 12.7 21.1 7.7 12.9 17.2 28.7 9.4 16.9 22.5 37.5 13.2 26.4 35.2 58.7 17.8 40.0 53.3 88.9 20.9 47.0 62.7 104.5 25.5 57.3 76.4 127.4
4.5 6.7 9.0 15.0 6.3 9.7 13.0 21.6 7.9 13.2 17.6 29.4 9.6 17.3 23.0 38.4 13.5 27.0 36.0 60.0 18.2 40.9 54.5 90.9 21.4 48.1 64.1 106.9 26.1 58.6 78.2 130.3
4.5 13.6 18.1 30.1 12.7 19.5 26.0 43.4 15.8 26.6 35.4 59.1 19.3 34.7 46.3 77.1 27.1 54.2 72.3 120.5 36.5 82.2 109.6 182.6 43.0 96.6 128.9 214.8 52.4 117.8 157.1 261.8
4.6 13.8 18.4 30.7 12.9 19.9 26.5 44.2 16.1 27.1 36.1 60.2 19.6 35.4 47.1 78.6 27.6 55.2 73.7 122.8 37.2 83.7 111.6 186.0 43.7 98.4 131.2 218.7 53.3 120.0 160.0 266.6
4.7 14.2 19.0 31.6 13.3 20.5 27.3 45.5 16.6 27.9 37.1 61.9 20.2 36.4 48.5 80.9 28.4 56.9 75.8 126.3 38.3 86.1 114.9 191.4 45.0 101.3 135.1 225.1 54.9 123.5 164.7 274.4
4.8 14.5 19.4 32.3 13.6 20.9 27.9 46.5 17.0 28.5 38.0 63.3 20.7 37.2 49.6 82.7 29.1 58.1 77.5 129.2 39.1 88.1 117.4 195.7 46.0 103.6 138.1 230.2 56.1 126.3 168.4 280.6
1 2 3 4
See Section 3.1.8 for explanation on development of load values. See Section 3.1.8.6 to convert design strength value to ASD value. Linear interpolation between embedment depths and concrete compressive strengths is not permitted. Tabular values represent a single anchor without reductions for edge distance, anchor spacing, or concrete thickness. Shaded cells indicate that bond strength is the controlling failure mode. Compare to the steel values in Table 4. The lesser of the values is to be used for design. 5 Values are for the following temperature range: maximum short term temperature = 55°C, maximum long term temperature = 43°C. Short term elevated concrete temperatures are those that occur over brief intervals, e.g., as a result of diurnal cycling. Long term concrete temperatures are roughly constant over significant periods of time. 6 Tabular values are for dry concrete conditions. For water saturated concrete, water-filled drilled holes, or submurged (underwater) applications multiply design strength by 0.60. 7 Tabular values are for short term loads only. For sustained loads including overhead use, see Section 3.1.8.8. 8 Tabular values are for normal-weight concrete only. For lightweight concrete multiply design strength by λa as follows: For sand-lightweight, λa = 0.51. For all-lightweight, λa = 0.45. 9 Tabular values are for holes drilled in concrete with carbide tipped hammer drill bit. Diamond core drilling is not permitted. 10 Tabular values are for static loads only. For seismic loads, multiply cracked concrete tabular values in tension and shear by αseis = 0.675. See section 3.1.8.7 for additional information on seismic applications.
4 Hilti Middle East | www.hilti.ae | HIT-RE 100 Metric Technical Supplement 2016
.
Adhesive Anchoring Systems
HIT-RE 100 Adhesive Anchoring System Table 4 - Steel design strength for rebar1 BS 4449 Grade B 500B Nominal rebar diameter mm
1 2 3 4 5
Tensile3 ϕNsa kN
Shear4 ϕVsa kN
Seismic shear5 ϕVsa,eq kN
8
17.9
9.9
–
10
28.0
15.6
10.9
12
40.3
22.5
15.8
14
54.9
30.6
21.4
16
71.8
39.9
27.9
20
112.5
61.8
43.3
25
175.5
97.2
68.0
28
220.0
121.8
85.3
32
287.6
159.3
111.5
See Section 3.1.8.6 to convert design strength value to ASD value. BS 4449 Grade 500B rebar is considered brittle steel elements. Tensile = ф Ase,N futa as noted in ACI 318-14 Chapter 17 Shear = ф 0.60 Ase,N futa as noted in ACI 318-14 Chapter 17 Seismic Shear = αV,seis ф Vsa : Reduction for seismic shear only. See section 3.1.8.7 for additional information on seismic applications.
Hilti Middle East | www.hilti.ae | HIT-RE 100 Metric Technical Supplement 2016 5
Adhesive Anchoring Systems
HIT-RE 100 Adhesive Anchoring System 2.4 Hilti HIT-RE 100 adhesive with Hilti HIT-V threaded rod Hilti HIT-V Threaded Rod
Cracked or uncracked concrete
Permissible concete conditions
Permissible drilling methods
Dry concrete Uncracked Concrete
Water-saturated concrete
Cracked Concrete
Water-filled holes
Hammer Drilling with Carbide Tipped Drill Bit
Submerged (underwater)
Table 5 — Hilti HIT-V threaded rod installation specifications Setting information Nominal bit diameter Effective embedment Diameter of fixture hole
Symbol Units
Figure 4 — H IT-V threaded rods
Nominal anchor diameter, d 8
10
12
16
20
24
27
30
10
12
14
18
22
28
30
35
do
mm
hef,min
mm
60
60
70
80
90
96
108
120
mm
160
200
240
320
400
480
540
600
through-set
mm
11
14
16
201
241
301
321
371
preset
mm
9
12
14
18
22
26
30
33
Tinst
Nm
10
20
40
80
150
200
270
300
hmin
mm
cmin
mm
40
50
60
80
100
120
135
150
mm
40
50
60
80
100
120
135
150
minimum maximum
hef,max
min
Installation torque Minimum concrete member thickness Minimum edge distance2 Minimum anchor spacing
smin
hef+30
hef+2do
Figure 5 — Installation with (2) washers
1 Install using (2) washers. See Figure 5.
2 Edge distance of 44mm is permitted provided the installation torque is reduced to 0.30 Tinst for 5d < s < 406 mm and to 0.5 Tinst for s > 406 mm
6 Hilti Middle East | www.hilti.ae | HIT-RE 100 Metric Technical Supplement 2016
.
Adhesive Anchoring Systems
HIT-RE 100 Adhesive Anchoring System Table 6 — Hilti HIT-RE 100 adhesive design strength with concrete / bond failure for metric threaded rod in uncracked concrete 1,2,3,4,5,6,7,8,9,10 Nominal anchor diameter mm 8
10
12
16
20
24
27
30
Tension — ϕNn Shear — ϕVn Effective embedment ƒ´c = 25 MPa ƒ´c = 30 MPa ƒ´c = 40 MPa ƒ´c = 50 MPa ƒ´c = 25 MPa ƒ´c = 30 MPa ƒ´c = 40 MPa ƒ´c = 50 MPa mm kN kN kN kN kN kN kN kN 60 72 96 160 60 90 120 200 70 108 144 240 80 144 192 320 90 180 240 400 96 216 288 480 108 243 324 540 120 270 360 600
9.0 10.7 14.3 23.9 11.2 16.8 22.4 37.3 15.5 23.9 31.9 53.1 22.5 40.5 54.1 90.1 27.7 61.1 81.4 135.7 30.6 85.7 114.3 190.5 36.5 104.3 139.1 231.8 42.7 123.6 164.8 274.7
9.1 10.9 14.6 24.3 11.4 17.1 22.8 38.0 15.8 24.3 32.5 54.1 22.9 41.3 55.0 91.7 30.4 62.2 82.9 138.2 33.5 87.3 116.4 194.0 40.0 106.2 141.6 236.1 46.8 125.9 167.9 279.8
9.4 11.3 15.0 25.0 11.7 17.6 23.5 39.1 16.2 25.1 33.4 55.7 23.6 42.5 56.7 94.4 32.0 64.0 85.3 142.2 38.7 89.8 119.8 199.6 46.1 109.3 145.8 243.0 54.0 129.6 172.8 288.0
9.6 11.5 15.4 25.6 12.0 18.0 24.0 40.0 16.6 25.6 34.2 56.9 24.1 43.4 57.9 96.6 32.7 65.4 87.2 145.4 40.8 91.9 122.5 204.2 49.7 111.8 149.1 248.4 58.9 132.5 176.7 294.5
9.6 23.1 30.9 51.4 12.1 36.2 48.2 80.4 33.4 51.5 68.6 114.4 48.5 87.3 116.4 194.0 59.8 131.5 175.3 292.2 65.8 184.6 246.2 410.3 78.6 224.7 299.6 499.3 92.0 266.3 355.0 591.7
9.8 23.6 31.4 52.4 12.3 36.8 49.1 81.8 34.0 52.4 69.9 116.5 49.4 88.9 118.6 197.6 65.5 133.9 178.6 297.6 72.1 188.0 250.7 417.8 86.1 228.8 305.1 508.5 100.8 271.2 361.6 602.6
10.1 24.3 32.3 53.9 12.6 37.9 50.5 84.2 35.0 54.0 71.9 119.9 50.8 91.5 122.0 203.4 68.9 137.8 183.8 306.3 83.3 193.5 258.0 430.0 99.4 235.5 314.0 523.3 116.4 279.1 372.1 620.2
10.3 24.8 33.1 55.1 12.9 38.8 51.7 86.1 In I 55.2 73.6 122.6 52.0 93.6 124.8 208.0 70.5 140.9 187.9 313.2 87.9 197.9 263.8 439.7 107.0 240.8 321.1 535.1 126.8 285.4 380.5 634.2
1 2 3 4
See Section 3.1.8 for explanation on development of load values. See Section 3.1.8.6 to convert design strength value to ASD value. Linear interpolation between embedment depths and concrete compressive strengths is not permitted. Tabular values represent a single anchor without reductions for edge distance, anchor spacing, or concrete thickness. Shaded cells indicate that bond strength is the controlling failure mode. Compare to the steel values in Table 8. The lesser of the values is to be used for the design. 5 Values are for the following temperature range: maximum short term temperature = 55°C, maximum long term temperature = 43°C. Short term elevated concrete temperatures are those that occur over brief intervals, e.g., as a result of diurnal cycling. Long term concrete temperatures are roughly constant over significant periods of time. 6 Tabular values are for dry concrete conditions. For water saturated concrete, water-filled drilled holes, or submurged (underwater) applications multiply design strength by 0.61. 7 Tabular values are for short term loads only. For sustained loads including overhead use, see Section 3.1.8.8. 8 Tabular values are for normal-weight concrete only. For lightweight concrete multiply design strength by λa as follows: For sand-lightweight, λa = 0.51. For all-lightweight, λa = 0.45. 9 Tabular values are for holes drilled in concrete with carbide tipped hammer drill bit. Diamond core drilling is not permitted. 10 Tabular values are for static loads only. Seismic design is not permitted for uncracked concrete.
Hilti Middle East | www.hilti.ae | HIT-RE 100 Metric Technical Supplement 2016 7
Adhesive Anchoring Systems
HIT-RE 100 Adhesive Anchoring System Table 7 — Hilti HIT- RE 100 adhesive design strength with concrete / bond failure for metric threaded rod in cracked concrete 1,2,3,4,5,6,7,8,9,10 Nominal anchor diameter mm 10
12
16
20
24
27
30
Tension — ϕNn Shear — ϕVn Effective embedment ƒ´c = 25 MPa ƒ´c = 30 MPa ƒ´c = 40 MPa ƒ´c = 50 MPa ƒ´c = 25 MPa ƒ´c = 30 MPa ƒ´c = 40 MPa ƒ´c = 50 MPa mm kN kN kN kN kN kN kN kN 60 90 120 200 70 108 144 240 80 144 192 320 90 180 240 400 96 216 288 480 108 243 324 540 120 270 360 600
5.9 8.8 11.7 19.5 7.3 11.3 15.0 25.0 11.1 20.0 26.7 44.5 14.9 29.8 39.7 66.1 17.6 39.6 52.7 87.9 20.4 45.9 61.2 102.0 21.4 48.1 64.1 106.8
6.0 8.9 11.9 19.9 7.4 11.5 15.3 25.5 11.3 20.4 27.2 45.3 15.2 30.3 40.4 67.4 17.9 40.3 53.7 89.5 20.8 46.7 62.3 103.9 21.8 49.0 65.3 108.8
6.1 9.2 12.3 20.4 7.7 11.8 15.7 26.2 11.7 21.0 28.0 46.6 15.6 31.2 41.6 69.3 18.4 41.5 55.3 92.1 21.4 48.1 64.1 106.9 22.4 50.4 67.2 112.0
6.3 9.4 12.5 20.9 7.8 12.1 16.1 26.8 11.9 21.5 28.6 47.7 15.9 31.9 42.5 70.9 18.8 42.4 56.5 94.2 21.9 49.2 65.6 109.3 22.9 51.5 68.7 114.5
6.3 18.9 25.2 42.0 15.7 24.3 32.3 53.9 24.0 43.1 57.5 95.8 32.1 64.1 85.5 142.5 37.9 85.2 113.6 189.4 43.9 98.9 131.8 219.7 46.0 103.6 138.1 230.1
6.4 19.3 25.7 42.8 16.0 24.7 32.9 54.9 24.4 43.9 58.6 97.6 32.6 65.3 87.0 145.1 38.6 86.8 115.7 192.8 44.7 100.7 134.2 223.7 46.9 105.5 140.6 234.4
6.6 19.8 26.4 44.0 16.5 25.4 33.9 56.5 25.1 45.2 60.3 100.5 33.6 67.2 89.6 149.3 39.7 89.3 119.1 198.5 46.1 103.6 138.2 230.3 48.2 108.5 144.7 241.2
6.8 20.3 27.0 45.0 16.9 26.0 34.7 57.8 25.7 46.2 61.6 102.7 34.4 68.7 91.6 152.7 40.6 91.3 121.8 202.9 47.1 106.0 141.3 235.4 49.3 111.0 148.0 246.6
1 2 3 4
See Section 3.1.8 for explanation on development of load values. See Section 3.1.8.6 to convert design strength value to ASD value. Linear interpolation between embedment depths and concrete compressive strengths is not permitted. Tabular values represent a single anchor without reductions for edge distance, anchor spacing, or concrete thickness. Shaded cells indicate that bond strength is the controlling failure mode. Compare to the steel values in Table 8. The lesser of the values is to be used for the design. 5 Values are for the following temperature range: maximum short term temperature = 55°C, maximum long term temperature = 43°C. Short term elevated concrete temperatures are those that occur over brief intervals, e.g., as a result of diurnal cycling. Long term concrete temperatures are roughly constant over significant periods of time. 6 Tabular values are for dry concrete conditions. For water saturated concrete, water-filled drilled holes, or submurged (underwater) applications multiply design strength by 0.61. 7 Tabular values are for short term loads only. For sustained loads including overhead use, see Section 3.1.8.8. 8 Tabular values are for normal-weight concrete only. For lightweight concrete multiply design strength by λa as follows: For sand-lightweight, λa = 0.51. For all-lightweight, λa = 0.45. 9 Tabular values are for holes drilled in concrete with carbide tipped hammer drill bit. Diamond core drilling is not permitted. 10 Tabular values are for static loads only. For seismic loads, multiply cracked concrete tabular values in tension and shear by αseis = 0.675. See section 3.1.8.7 for additional information on seismic applications
8 Hilti Middle East | www.hilti.ae | HIT-RE 100 Metric Technical Supplement 2016
.
Adhesive Anchoring Systems
HIT-RE 100 Adhesive Anchoring System Table 8 — Steel design strength for Hilti HIT-V threaded rods 1 HIT-V ISO 898-1 Class 5.85
HIT-V ISO 898-1 Class 8.85
HIT-V-R ISO 3506-1 Class A4 stainless5
HIT-V-HCR High corrosion resistant steel5
Nominal anchor diameter mm
Tensile2 ϕNsa kN
Shear3 ϕVsa kN
Seismic Shear4 ϕVsa,eq kN
Tensile2 ϕNsa kN
Shear3 ϕVsa kN
Seismic Shear4 ϕVsa,eq kN
Tensile2 ϕNsa kN
Shear3 ϕVsa kN
Seismic Shear4 ϕVsa,eq kN
Tensile2 ϕNsa kN
Shear3 ϕVsa kN
Seismic Shear4 ϕVsa,eq kN
8 10 12 16 20 25 28 30 32
11.9 18.9 27.3 51.0 79.6 114.7 149.2 182.3 182.3
6.6 8.7 15.3 28.2 44.1 63.6 82.5 101.1 101.1
– 6.1 10.7 19.7 30.9 44.5 57.8 70.8 70.8
19.0 30.2 43.9 81.6 127.4 183.6 238.6 291.9 291.9
10.6 13.8 24.3 45.3 70.5 101.7 132.3 161.7 161.7
– 9.7 17.0 31.7 49.4 71.2 92.6 113.2 113.2
16.6 26.4 38.4 71.4 111.5 160.6 119.0 145.5 145.5
9.2 12.2 21.2 39.5 61.7 89.0 65.9 80.6 80.6
– 8.5 14.9 27.7 43.2 62.3 46.2 56.4 56.4
19.0 30.2 43.8 81.6 127.4 160.6 208.8 255.3 255.3
8.8 13.9 24.3 45.2 70.6 89.0 115.7 141.4 141.4
– 9.7 17.0 31.7 49.4 62.3 81.0 99.0 99.0
1 See Section 3.1.8.6 to convert design strength value to ASD value. 2 Tensile = ϕ Ase,N futa as noted in ACI 318-14 Chapter 17 3 Shear = ϕ 0.60 Ase,V futa as noted in ACI 318-14 Chapter 17. 4 Seismic Shear = αV,seis ϕVsa : Reduction for seismic shear only. See ACI 318-14 Chapter 17 for additional information on seismic applications 5 HIT-V threaded rods are considered brittle steel elements.
Hilti Middle East | www.hilti.ae | HIT-RE 100 Metric Technical Supplement 2016 9
Adhesive Anchoring Systems
HIT-RE 100 Adhesive Anchoring System 2.5 Installation instructions
Installation Instructions For Use (IFU) are included with each product package. They can also be viewed or ed on-line at www.us.hilti.com (US). Because of the possibility of changes, always that ed IFU are current when used. Proper installation is critical to achieve full performance. Training is available on request. Hilti Technical Services for applications and conditions not addressed in the IFU.
2.6 Working time and cure time (approx.)
[°C]
[°F]
5 10 15 20 30 40
41 50 59 68 86 104
t work 2 1/2 h 2h 1 1/2 h 30 min 20 min 12 min
t cure, full ≥ 72 h ≥ 48 h ≥ 24 h ≥ 12 h ≥8h ≥4h
2.7 Materials specifications Table 9 — Material properties of fully cured HIT-RE 100 adhesive Bond Strength ASTM C882-121 2 day cure 14 day cure Compressive Strength ASTM D695-10
20.1 Mpa 21.0 Mpa 1
Table 10 — Resistance of HIT-RE 100 to chemicals Chemical
Alkaline
74.3 Mpa
Compressive Modulus ASTM D695-101
3,731 Mpa
Tensile Strength 7 day ASTM D638-10
11.7 Mpa
Elongation at break ASTM D638-10
0.10%
Heat Deflection Temperature ASTM D648-07
56.8°C
Absorption ASTM D570-10
0.06%
Linear Coefficient of Shrinkage on Cure ASTM D2566-86
0.0001
1 Minimum values obtained as the result of tests at 2°C, 10°C, 24°C, and 43°C.
Chemicals Tested
Not Resistant Resistant
Concrete drilling mud (10%) pH=12.6
+
Concrete drilling mud (10%) pH=13.2
+
Concrete potash solution (10%)
+
pH=14.0
Alkaline
t cure, ini ≥ 18 h ≥ 12 h ≥8h ≥6h ≥4h ≥2h
2.8 Resistance of cured Hilti HIT-RE 100 to chemicals
Solvents
Acetic acid (10%)1
-
Nitric acid (10%)1
-
Hydrochloric acid (10%) 3 month
-
Sulfuric acid (10%)
-
Benzyl alcohol
-
Ethanol
-
Ethyl acetate
-
Methyl ethyl ketone (MEK)
-
Trichlorethylene
Chemicals used on job sites
-
Xylene (mixture)
+
Chemicals Concrete plasticizer
+
used on job Diesel oil
+
sites Oil
+
Petrol
+
Oil for form work (forming oil)
+
Environmental Salt water
+
chemicals de-mineralized water
+
Environmental salt spraying test chemicals SO2
Environment/weather
+ + +
1 Concrete was dissolved by acid
Samples of the HIT-RE 100 resin were immersed in the various chemical compounds for up to one year. At the time of the test period, the samples were analyzed. Any samples showing no visible damage and having less than a 25% reduction in bending (flexural) strength were classified as “Resistant.” Samples that were heavily damaged or destroyed were classified as “Not Resistant.” Note: In actual use, the majority of the resin is encased in the base material, leaving very little surface area exposed.
10 Hilti Middle East | www.hilti.ae | HIT-RE 100 Metric Technical Supplement 2016
.
Adhesive Anchoring Systems
HIT-RE 100 Adhesive Anchoring System 3.0 Ordering information
HIT-RE 100 adhesive Description
Package content
Qty
HIT-RE 100/500/1
Includes (1) foil pack with (1) mixer
1
Item number
2123386
Accessories Description
Item number
Cordless dispenser HDE 500-A22 with (1) black cassette 500 ml, (1) red cassette 500 ml and (1) case
2005637
Cordless dispenser HDE 500-A22
2005630
Manual dispenser HDM 500 box
2005641
Hilti Middle East | www.hilti.ae | HIT-RE 100 Metric Technical Supplement 2016 11